Sec. 40-349. - Protection of aboveground storage.
In the event liquefied petroleum gas storage is located above ground within ten feet of the adjacent outer edge of a driveway or parking area, the storage shall be protected by a barricade of four-inch pipe filled with concrete or the equivalent thereof and set in concrete a minimum of four feet above ground, a distance of not more than four feet apart, not less than three feet from such storage container or any piping above the level of the top of the barricade.
(Ord. No. 36424, § 1, 10-21-03)