14.28.300 - Table B105.1(1) of Appendix B of the 2025 California Fire Code titled "Required fire flow for one- and two-family dwellings, Group R-3 and R-4 buildings and townhouses" is amended as follows.
TABLE B105.1(1) REQUIRED FIRE-FLOW FOR ONE- AND TWO-FAMILY DWELLINGS, GROUP R-3 AND R-4 BUILDINGS AND TOWNHOUSES Fire Flow Calculation Area (square feet) | AUTOMATIC SPRINKLER SYSTEM (Design Standard) | MINIMUM FIRE FLOW (gallons per minute) | FLOW DURATION (hours) 0—3,600 | No automatic sprinkler system | 1,000 | 1 3,601 and greater | No automatic sprinkler system | Value in Table B105.1(2) | Duration in Table B105.1(2) at the required fire flow rate 0—3,600 | Section 903.3.1.3 of the California Fire Code or Section 313.3 of the California Residential Code | 1,000 | ½ 3,601 and greater | Section 903.3.1.3 of the California Fire Code or Section 313.3 of the California Residential Code | 1,500 | 1 For SI: 1 square foot = 0.0929 m 2 , 1 gallon per minute = 3.875 L/m.
(Ord. No. 7461, § 6, 11-10-2025)