For AI agents: read the machine-readable documentation index at /llms.txt or the single-file full reference at /llms-full.txt.

§ 344.10

New York City Administrative Code (current through L.L. 2026/147, enacted September 12, 2026, and amendments effective through October 10, 2026) · NYC Electrical Code § 344.10

Corpus is an independent public-information project, not the official City of New York website. Stable reference: corpuslaw.us/code/84361467-47ab-4c77-8d2b-30111500c91b

Section 344.10

Section 344.10(A)(2) – Revise Section 344.10(A)(2) to read as follows: (2) Aluminum RMC. Aluminum RMC shall be permitted to be installed where judged suitable for the environment. Rigid aluminum conduit encased in concrete or in direct contact with the earth shall be provided with listed supplementary corrosion protection. Section 344.10(B)(2) – Revise Section 344.10(B)(2) to read as follows: (2) Supplementary Protection of Aluminum RMC. Aluminum RMC shall be provided with listed supplementary corrosion protection where encased in concrete or in direct contact with the earth.

Ask a question about New York law

Corpus searches the New York sections it holds and shows the ones that match, with their citations. Free, no sign-in.