§ 18.40.600 — Amend CBC Section 2308.10.9—Attachment of sheathing
Long Beach Municipal Code (Supp. No. 53, Update 1: codified through Ordinance No. ORD-26-0027, enacted October 13, 2026) · Long Beach Municipal Code § 18.40.600
Corpus is an independent public-information project, not the official City of Long Beach website. Stable reference: corpuslaw.us/code/84efba20-2e33-4a55-bc3d-42b421388dac
18.40.600 - Amend CBC Section 2308.10.9—Attachment of sheathing.
Section 2308.10.9 of the California Building Code is amended to read as follows: 2308.10.9 Attachment of sheathing. Fastening of braced wall panel sheathing shall not be less than that prescribed in Tables 2308.10.1 or 2304.10.2. Wall sheathing shall not be attached to framing members by adhesives. Staple fasteners in Table 2304.10.2 shall not be used to resist or transfer seismic forces in structures assigned to Seismic Design Category D, E or F. Exception: Staples may be used to resist or transfer seismic forces when the allowable shear values are substantiated by cyclic testing and approved by the Building Official. All braced wall panels shall extend to the roof sheathing and shall be attached to parallel roof rafters or blocking above with framing clips (18 gauge minimum) spaced at a maximum of 24 inches (6,096 mm) on center with four 8d nails per leg (total eight 8d nails per clip, minimum). Braced wall panels shall be laterally braced at each top corner and at intervals not to exceed 24 inches (6,096 mm) along the top plate of discontinuous vertical framing.
(ORD-25-0019 § 1(Exh. A), 2025)