§ 14.04.150 — Subsections 1905.8 through 1905.10 are added to Chapter 19 of the 2025 California Building Code to read as follows
Pasadena Municipal Code, California (Supp. No. 79: codified through Ordinance No. 7469, enacted May 18, 2026) · Pasadena Municipal Code § 14.04.150
Corpus is an independent public-information project, not the official City of Pasadena website. Stable reference: corpuslaw.us/code/84f555c1-9b74-4dd8-86d5-708b8bab9864
14.04.150 - Subsections 1905.8 through 1905.10 are added to Chapter 19 of the 2025 California Building Code to read as follows.
1905.8 ACI 318, Section 18.7.5. Modify ACI 318, Section 18.7.5, by adding Section 18.7.5.8 and 18.7.5.9 as follows: 18.7.5.8 Where the calculated point of contraflexure is not within the middle half of the member clear height, provide transverse reinforcement as specified in ACI 318 Sections 18.7.5.1, Items (a) through (c), over the full height of the member. 18.7.5.9 At any section where the design strength, φP n , of the column is less than the sum of the shears V e computed in accordance with ACI 318 Sections 18.7.6.1 and 18.6.5.1 for all the beams framing into the column above the level under consideration, transverse reinforcement as specified in ACI 318 Sections 18.7.5.1 through 18.7.5.3 shall be provided. For beams framing into opposite sides of the column, the moment components are permitted to be assumed to be of opposite sign. For the determination of the design strength, φP n , of the column, these moments are permitted to be assumed to result from the deformation of the frame in any one principal axis. 1905.9 ACI 318, Section 18.10.4. Modify ACI 318, Section 18.10.4, by adding Section 18.10.4.7 as follows: 18.10.4.7 Walls and portions of walls with P u > 0.35P o shall not be considered to contribute to the calculated shear strength of the structure for resisting earthquake-induced forces. Such walls shall conform to the requirements of ACI 318 Section 18.14. 1905.10 ACI318, Section 18.12.6. Modify ACI 318, by adding Section 18.12.6.2 as follows: 18.12.6.2 Collector and boundary elements in topping slabs placed over precast floor and roof elements shall not be less than 3 inches (76 mm) or 6 d b in thickness, where d b is the diameter of the largest reinforcement in the topping slab.
(Ord. No. 7461, § 5, 11-10-2025)
Ask a question about Pasadena law
Corpus searches the Pasadena sections it holds and shows the ones that match, with their citations. Free, no sign-in.
