§ 9-17 — Amendments to the 2024 International Building Code

Code of the City of Glendale, Arizona (Supp. No. 115: codified through Ordinance No. O26-19, adopted April 14, 2026) · Glendale City Code § 9-17

Corpus is an independent public-information project, not the official City of Glendale website. Stable reference: corpuslaw.us/code/862a832f-e68f-4de9-9c67-b7765b53c3c9

Sec. 9-17. - Amendments to the 2024 International Building Code.

The 2024 International Building Code is amended in the following respects: Section 101.1 is amended to read as follows: 101.1 Title. These regulations shall be known as the Building Code of the City of Glendale, Arizona, hereinafter referred to as "this code." Section 103.1 is amended to read as follows: 103.1 Creation of Enforcement Agency. The Building Safety Division is hereby created and the official in charge thereof shall be known as the building official. The function of the agency shall be the implementation, administration and enforcement of the provisions of this code. Section 104.2.3, Alternative materials, design and methods of construction and equipment, delete the Exception. Section 104.2.4.1, Flood Hazard Areas is amended as follows: Replace the words "building official" with "city engineer or functional equivalent" Section 104.7 Official records is amended to read as follows: The building official shall keep official records as required by Sections 104.7.1 through 104.7.5. Such official records shall be retained in accordance with the regulations of the State of Arizona and City Clerk's Office. Section 104.8, Liability is amended by replacing "member of the board of appeals" with "hearing officer" in the first sentence. Section 105.2, Work Exempt from Permit, item 2, is amended to read as follows: 2. Fences, other than swimming pool barriers and perimeter subdivision fences, not over 7 feet (2134 mm) high. Section 105.2, Work exempt from permit, Building, add the following item: 14. Hoophouses and polyhouses used exclusively for producing and storing live plants, constructed in accordance with A.R.S. § 9-469. Mechanical, plumbing and electrical systems constructed in these structures shall require the appropriate permits in accordance with this code. Section 105.6, Suspension or Revocation is amended by adding the following: It shall be unlawful to proceed with any work for which a permit was issued after notice of permit suspension or revocation is served on the permit holder, the owner, or the person having responsible charge of the work. Reinstatement of a suspended permit shall be by written notice from the building official authorizing work to resume, with or without conditions. Revoked permits shall be canceled and the permit fee shall not be refunded. Section 109 is deleted and replaced by the following: Section 109 Fees 109.1 Fee Schedule. Fees shall be assessed in accordance with the provisions of this section and shall be as established by council resolution. 109.2 Permit Fees. Fees shall be as established by council resolution. 109.3 Plan Review Fees. When submittal documents are required by Section 107 of this code, a plan review fee shall be paid at the time of submitting the documents for plan review. The plan review fees specified in this section and as by council resolution are separate fees from, and in addition to, the permit fees specified in Section 109.2 of this code. 109.4 Building Permit Valuations. The determination of valuation under any provisions of the code shall be made by the building official. The valuation to be used in computing the building permit and building plan review fees shall be the total value of all construction work including all materials, labor, overhead and profit for which the permit is issued including all finish work, painting, roofing, electrical, plumbing, heating, air-conditioning, elevators, fire- extinguishing systems, and other permanent equipment. 109.5 Work Commencing Before Permit Issuance. Whenever work for which a permit is required by this code has been commenced without first obtaining a permit, a special investigation shall be made before a permit may be issued for such work. An investigation fee, in addition to the permit fee, shall be collected whether or not a permit is then or subsequently issued. The investigation fee shall be as adopted by council resolution. The payment of such investigation fee shall not exempt an applicant from compliance with all other provisions of either this code or other adopted laws and ordinances of this city. 109.6 Reinspection fees. Permit fees provide for customary inspections only. A reinspection fee may be assessed for each inspection or reinspection when such portion of the work for which inspection is called is not complete or when corrections called for are not made. Reinspection fees may be assessed when the inspection record card is not posted or otherwise readily available to the inspector, for failure to provide access on the date for which inspection is requested, or for deviating from plans requiring the approval of the building official. In instances where reinspection fees have been assessed, additional inspection of the work will not be performed until the required fees have been paid. Section 110.1, Inspections, General is amended by adding the following paragraph: Property owners shall obtain and display on the residence, business, or otherwise, the correct building number or numbers as assigned to such property(ies) by the Planning Department or functional equivalent in accordance with established street assignment policy, prior to final inspection and /or issuance of a certificate of occupancy. The building numbers shall be of a durable material, permanently attached to the building and must be readily distinguished and readable from the nearest paved public/common roadway fronting that property. The size of the building numbers shall comply with the city's adopted fire code and its amendments. Section 110.3.3, Lowest Floor Elevation is amended as follows: Replace "building official" with "City Engineer or functional equivalent." Section 110.3.4, Frame Inspection is amended by adding the following sentence: The building shall be weather-tight at the time of the frame inspection. Section 110.3.11 is deleted and amended by the following text: 110.3.11 Special Inspections. In addition to the inspections required by Section 110, the engineer or architect of record acting as the owner's agent shall employ one or more special inspectors who shall provide inspections during construction for types of work outlined in Chapter 17 and as outlined below: 110.3.11.1 Electrical Special Inspections. 1. Ground-fault protection performance tests for equipment are required to be provided with ground-fault protection. 2. Switchboards, panelboards, motor control centers, and other equipment rated 1,000 amps or more; or over 600 volts. 3. Emergency and standby power systems, including switchboards, panel boards, distribution boards, transfer equipment, power source, conductors, fire pumps, and exhaust and ventilation fans. 110.3.11.2 Electrical Observation. Electrical observation shall be provided for the following installations: 1. Installation or alteration of that portion of health care facility electrical systems which fall within the scope of Article 517, Chapter III of the adopted National Electric Code where critical care areas are present. 2. Installations or alterations of high-voltage electrical systems, which exceed 600 volts. Installations or alterations of electrical systems within locations classified as hazardous by the provisions of adopted the National Electric Code, or the International Fire Code, except for gasoline dispensing installations and systems located within storage garages, repair garages or lubritorium's. 3. When such observation is specifically required by the building official. The owner shall employ the engineer responsible for the electrical design, or another engineer designated by the engineer responsible for the electrical design to perform visual observation of complex electrical equipment and systems for general conformance to the interconnection of equipment. Electrical observation shall be performed at significant stages of the construction and when the installation is complete and ready to be inspected by the building official. Section 110.3.13 is added as follows: 110.3.13 Building Service Equipment Inspections. All building service equipment inspections for which a permit is required by this code shall be inspected by the building official. No portion of any building service equipment intended to be concealed by any permanent portion of the building shall be concealed until inspected and approved. When the installation of any building service equipment is complete, an additional and final inspection shall be made. Building service equipment regulated by the technical codes shall not be connected to the water, fuel or power supply or sewer system until authorized by the building official. 1. Electrical inspections. A rough-in inspection is required for all conduit, semi-rigid piping or wiring after installation but prior to being concealed. Final inspection is required when all conduit, wires, fixtures and equipment including covers, have been installed and connected. 2. Mechanical inspections. All mechanical equipment and systems for which a permit is required by the code, including all associated ductwork, flues, condensate and refrigeration lines, shall be subject to inspection and shall remain accessible and exposed for inspection purposes until approved. 3. Plumbing inspections. A rough-in or underground inspection is required for all sewer, drainage and vent piping, and for all water and gas distribution systems prior to their being buried or concealed. A final inspection is required when all fixtures are set and operating or ready to operate. Tests shall be performed as required by the currently adopted plumbing code. Section 111.5 is added as follows: 111.5 Certificate of Completion for Shell Buildings. The building official is authorized to issue a Certificate of Completion for all commercial shell/ non-occupied buildings and/ or structures. This document will be utilized to indicate the building official's approval and completion of non-occupied buildings and/or structures also defined or labeled as "Shell Buildings, Vanilla Shell, Grey Shell, Equipment Installation and Spec Suites." The Certificate of Completion document must specify the following: 1. Specify "No occupancy" or "Occupancy of one (1) person allowed only for maintenance, security or fire watch" 2. Certificate/ permit number 3. Date 4. Premises, address, suite number 5. Legal description, Assessor's Parcel Number (APN) 6. Type of construction 7. Occupancy group: UNOCCUPIED 8. Owner 9. General contractor 10. Date of permit 11. Valuation 12. Comments (building area, AFES, occupant load) 13. Other conditions (specified by the building official) Section 113 is deleted and replaced by the following: 113 MEANS OF APPEALS 113.1 General. Decisions of the building official shall be appealed to Glendale City Court. An application for an appeal of any order, decision or interpretation made by the building official shall be filed in writing, along with the appropriate fee established by resolution or pursuant to Glendale City Code Sec. 2-3, and shall be delivered to the Court and to the building official within thirty (30) calendar days of the date of the order, decisions or interpretation. The fee shall not be refundable. The decision of the building official may be reversed or modified by the Court upon finding that: a. The decision of the building official is not supported by a reasonable interpretation and application of the city code to the specific facts presented, or the city code does not apply to the facts presented. b. The reversal or modification of the building official's decision will not create or manifest injustice or affect the intent of the city code. c. The reversal of the building official's decision will not be detrimental to the public health, safety and welfare. 113.2 Limitations of Authority. The Court shall have no authority relative to interpretation of the administrative provisions of the codes set forth in Sec. 9-16, nor shall the Court be empowered to waive the requirements of the codes set forth in Sec. 9-16. Section 116, Unsafe Structures and Equipment is amended as follows: Section 116.1, Unsafe conditions. The requirements for the abatement of unsafe buildings, structures and equipment shall be governed by the 2024 International Property Maintenance Code and its related amendments. The balance of the text of IBC Section 116 is deleted. Section 201.4, Terms Not Defined is amended by adding to the end of this subsection: Mirriam-Webster's Unabridged Dictionary of the English Language shall be considered as providing ordinarily accepted meanings. Section 202, Definitions is amended by revising the following definitions: ELECTRIC VEHICLE CHARGING STATION. One or more vehicle spaces served by an electric vehicle charging system, including the vehicle charging system. EXISTING BUILDING. A building erected prior to the date of adoption of the appropriate code, or one for which a legal building permit has been issued and all required inspections have been approved. EXISTING STRUCTURE. A structure erected prior to the date of adoption of the appropriate code, or one for which a legal building permit has been issued and all required inspections have been approved. Section 406.3 is amended by adding the following subsection: 406.3.4 Open Carports. Carports for other than single family residential use which are open on all sides and constructed entirely of noncombustible materials, except for an approved fascia, shall not exceed 5,000 square feet and shall be located no closer than 3 feet to an adjacent lot line, nor closer than 6 feet to any projecting element of an adjacent building or structure. The edge of the carport roof shall be used to measure the separation distance to adjacent lot lines, buildings or structures. Section 406.3, Private Garages and Carports is amended by adding the following subsection: 406.3.5 Electric vehicle (EV) receptacle outlets in private garages. In a minimum of 10% of the attached private, enclosed garages and in a minimum of 10% of the detached private, enclosed garages, associated with Group R-2 occupancy dwelling units, provide a minimum of one EV-capable outlet in each garage, not more than 48 inches above and not less than 18 inches above the floor. EV-capable outlets serving accessible parking spaces shall be installed in accordance with Section 1107 and ICC A117.1. Each EV-capable outlet installation shall include a junction box with cover and a continuous raceway to the electrical distribution equipment (panelboard). The installed raceway shall be sized and rated to supply a minimum 50-amp circuit capacity. The electrical distribution equipment shall have sufficient dedicated space and spare electrical capacity for a 50-amp circuit breaker. The electrical outlet (junction box) and the electrical distribution equipment directory shall be labeled: "For future electric vehicle supply equipment (EVSE)." All components shall be installed in compliance with the National Electrical Code. Section 420.4 Automatic sprinkler system. Revise the first sentence to read: Other than where preempted by Arizona State Law, Group R occupancies shall be equipped throughout with an automatic sprinkler system in accordance Section 903.2.8 and Glendale City Code Section 16-52. Section 707.3.12 Electrical Rooms with Service Entrance Equipment is added and shall read as follows: Fire barrier walls and/ or fire-resistance-rated horizontal assemblies with a fire-resistance rating of one hour shall be provided to separate an electrical room containing service entrance equipment from adjacent rooms and spaces. Section 708.3, Fire-resistance rating; the first paragraph is amended as follows: Fire partitions shall have a fire-resistance rating of not less than 1 hour except when required by Section 420.2 in a building that does not have an automatic sprinkler system in accordance with Section 903.2.8. Where fire partitions are required by Section 420.2 and the building does not have an automatic sprinkler system the fire-resistance rating shall be not less than 2 hours. Where the fire partitions have a required fire-resistance rating of more than 1 hour, opening protectives shall be provided in accordance with Table 716.1(2) for fire barriers having a fire- resistance rating greater than 1 hour. (The Exceptions shall remain unchanged.) Section 903.2, Automatic Sprinkler Systems is amended by replacing the first sentence with the following: Approved automatic sprinkler systems in new buildings and structures, and in existing buildings and structures, that are modified, expanded, remodeled, renovated or change occupancy classifications, shall be provided in accordance with the Glendale City Code, Chapter 16, Article III. Where preempted by Arizona State Law, automatic fire sprinkler systems shall not be required in newly constructed three-family dwellings (triplexes) and in newly constructed four-family dwellings (fourplexes). Section 1010.2.8.2, Rooms with Electrical Equipment is amended to read as follows: Exit or exit access doors serving transformer vault, rooms designated for batteries or energy storage systems, or modular data centers shall be equipped with panic hardware or fire exit hardware. Exit or exit access doors serving rooms containing electrical equipment rated 800 amperes or more that contain overcurrent devices, switching devices or control devices shall be equipped with panic hardware or fire exit hardware. The doors shall swing in the direction of exit travel. Section 1028.3 Exit discharge width or capacity, add the following sentence: The minimum width of an exterior sidewalk serving as a component of the exit discharge shall be 60 inches (effective sidewalk width) or as determined by Section 1005.3, whichever is greater. Effective sidewalk width is defined as the usable sidewalk area for pedestrian travel, excluding obstructions such as building walls, trees, poles, or other elements that might restrict pedestrian movement. Typically, 1 foot is subtracted from each side in which one of these listed obstructions is present. Sidewalks adjacent to parking stalls shall be a minimum of 72 inches wide or can be 60 inches wide if a landscape buffer is present. Section 1101.1 Scope, revise to read as follows: The provisions of this chapter and the Arizona Revised Statutes Section ARS 41-1492 shall control the design and construction of facilities for accessibility for individuals with disabilities. Section 1102.1 Design, revise to read as follows: Buildings and facilities shall be designed and constructed to be accessible in accordance with this code and ICC A117.1-17 and in accordance with provisions State of Arizona Attorney General Administrative Rules R10-3-401 through R-10-3-404 (2010 ADA Standards for Accessible Design, referred to as "2010 Standards", adopted by the U.S. Department of Justice), whichever standard provides the greatest degree of accessibility. Section 1104.1 Site arrival points, revise the first paragraph to read as follows: All pedestrian routes within the site provided from public transportation stops, accessible parking, accessible passenger loading zones, and public streets or public sidewalks to all building entrances shall be accessible. The minimum width of sidewalks serving as accessible routes shall be 60 inches (effective sidewalk width). Effective sidewalk width is defined as the usable sidewalk area for pedestrian travel, excluding obstructions such as building walls, trees, poles, or other elements that might restrict pedestrian movement. Typically, 1 foot is subtracted from each side in which one of these listed obstructions is present. Sidewalks adjacent to parking stalls shall be a minimum of 72 inches wide or can be 60 inches wide if a landscape buffer is present. At existing sites, the minimum width of sidewalks serving as accessible routes shall be 36 inches (effective sidewalk width). This includes accessible routes adjacent to Extension of Premises areas. All components of accessible routes shall comply with the 2010 ADA Standards for Accessible Design and ICC A117.1-17. Section 1109.2 Assembly area seating, revise the last sentence to read: Dining areas shall comply with Section 1109.2.9 and Section 1110.14. Section 1110.2 Toilet and bathing facilities. Amend Exception #3 by deleting the words "or bathing rooms." Revise to read as follows: 3. Where multiple single-user toilet rooms are clustered at a single location, at least 50 percent but not less than one room at each cluster shall be accessible. Section 1607.1, Table 1607.1. Amend this table by revising item #27, Residential habitable attics and sleeping areas uniform live load value to 40 psf. Section 1609.4.3 Exposure Categories is amended by adding the following: The City of Glendale is predominantly categorized as exposure category C. Deviating from this shall require additional proof and verification from the registered design professional in responsible charge. The engineer shall provide a surface roughness analysis, provide aerials, etc. proving that the proposed site meets exposure category B as defined in ASCE 7-22, Section 26.7.3. Exception: Single story one- and two-family dwellings are permitted to use exposure category B for wind design. Section 1705.4 Masonry Construction is amended by deleting Exception 2. Section 1806.1 Load Combinations is amended by adding the following: In lieu of the presumptive load-bearing values of Table 1806.2, a geotechnical investigation report is required for all new construction. Section 1806.2 Presumptive Load-Bearing Values is amended by adding the following: In lieu of the presumptive load-bearing values of Table 1806.2, a geotechnical investigation report is required for all new construction. Section 1809.4 Depth and width of footings is amended by revising the first sentence to read as follows: The minimum depth of footings below the undisturbed ground surface shall be 18 inches (458 mm), unless otherwise recommended by a geotechnical investigation report. Table 2902.1 Minimum Number of Required Plumbing Fixtures is amended as follows. These amendments also apply to Table 403.1 of the 2024 International Plumbing Code. Revise footnote "e" to "50 or fewer." Add new footnote "g" to read as follows: g. 24 inches (610 mm) of wash sink or 18 inches (457 mm) of a circular wash basin shall be considered equivalent to one lavatory. Section 2902.6, Small Occupancies (Minimum Plumbing Facilities) is amended by revising "15" to "50."

(Ord. No. O25-51, § 1, 12-9-25)

Ask a question about Glendale law

Corpus searches the Glendale sections it holds and shows the ones that match, with their citations. Free, no sign-in.