14.04.160 - Section 2304.10.3.1 of the 2025 Edition of the California Building Code is amended to read as follows.

2304.10.3.1 Quality of Nails. In Seismic Design Category D, E or F, mechanically driven nails used in wood structural panel shear walls shall meet the same dimensions as that required for hand-driven nails, including diameter, minimum length and minimum head diameter. Clipped head or box nails are not permitted in new construction. The allowable design value for clipped head nails in existing construction may be taken at no more than the nail-head-area ratio of that of the same size hand-driven nails.

(Ord. No. 7461, § 5, 11-10-2025)