Sec. 49-1313. - Size of vent piping.
The maximum fixture unit load and maximum length of horizontal and vertical vent piping shall be as follows: Table 49-1313 Size of Vent (inches) | Maximum Number of Drainage Fixture Units | Maximum Length of Vent (feet) 1¼ | 1 | 45 1½ (See Note 1) | 8 | 60 2 | 18 | 120 2½ | 36 | 180 3 | 72 | 212 4 | 244 | 300 5 | 550 | 390 6 | 1296 | 510 8 | 3500 | 750 Note 1: (a) No more than one water closet. (b) A restroom group containing one water closet, one lavatory and one urinal may be vented with 1½-inch vent. _____
(Ord. No. 40524, § 1, 10-20-15)