16.08.145 - Section 903.2 amended—Automatic sprinkler systems.
Section 903 of the California Building Code is hereby amended by amending Section 903.2 to read as follows:
A. Where required. An automatic fire extinguishing system shall be installed and maintained in operable condition in the buildings and locations as set forth in this section. For special provisions on hazardous chemicals, magnesium and calcium carbide, see the Fire Code.
B. All New Buildings. An automatic sprinkler system shall be installed and maintained in operable condition in all new buildings. All systems shall conform to the National Fire Protection Association Standards 13, 13D, and 13R and the Riverside Fire Department Standards and Policies.
1. NFPA 13D local water flow alarm shall be provided on a fire sprinkler system in homes. The water flow alarm shall be located on the exterior of the structure at an approved location by the fire department.
EXCEPTIONS:
1. Buildings less than 1,000 square feet in floor area, other than Group R-1, Group R-2, Group R-3, and Group R-4 occupancies, unless specifically required by other provisions of the California Fire Code.
2. Group U occupancy buildings accessory to Group R-3 occupancies other than additional R-1, R-2, R-3, or R-4 occupancies.
3. Group S occupancies, less than 5,000 square feet in floor area, that are accessory to uses such as golf courses, tree nurseries, parks, farms, etc. Administrative and clerical office use area may not exceed 25 percent of the floor area of the major use. Additionally, the site must be zoned RE, RA-5 or RC.
4. Structures that have no occupant load as determined by the Building Official.
5. Swimming pools, spas, gazebos, shade structures or other open-air structures that meet California Building Code requirements for separation.
6. Structures which do not require building permits.
7. Mausoleums, crypts, and similar structures.
8. Agricultural buildings as defined in the California Building Code, Appendix C.
9. Structures and buildings designed exclusively to shelter or protect equipment such as pump houses, substations, and similar structures.
10. Aircraft hangars, pursuant to California Fire Code, Section 914.8.
11. Temporary modular construction offices.
12. Group R occupancies for which a fire station development fee as set forth in Chapter 16.52 has been paid prior to March 1, 1993 or Group R occupancies situated within a community facilities district or an assessment district formed prior to March 1, 1993 when said district has agreed to pay for a proportionate share for construction of a fire station to serve the area of the district.
C. Existing Buildings. Buildings in existence prior to March 1, 1993 or buildings for Group R, Division 3 and Group U occupancies for which plans were submitted and plan check fees paid to the City prior to March 1, 1993 shall be exempt from the requirements of this section.
EXCEPTIONS:
1. Pursuant to California Fire Code, Section 903 in its entirety.
2. Remodels equaling 50% or greater of the existing square footage, regardless of year built, shall have an automatic sprinkler system installed.
D. Conflict. Where in any case, there are conflicting provisions between the California Fire Code as adopted by the City and this section, the more restrictive shall govern.
E. Standards. All automatic fire sprinkler systems required by this section shall comply with N.F.P.A. 13, 13D and 13R.
(Ord. 7612 § 28, 2022; Ord. 7510 § 6, 2020; Ord. 7357 §23, 2016; Ord. 7237 §8, 2013; Ord. 7103 §8, 2010; Ord. 6971 §6, 2007; Ord. 6634 §5, 2002; Ord. 6472 §6, 1999; Ord. 6260 §2, 1996: Ord. 6253 §8, 1995: Ord. 6019 §1, 1992; Ord. 5996 §10, 1992; Ord. 5964 §1, 1991; Ord. 5830 §8, 1990; Ord. 5259 §24, 1985)