Chandler City Code § 29-4 International Plumbing Code adopted.
29-4. - International Plumbing Code adopted.
The City Council of Chandler adopts by reference the International Plumbing Code, 2024 edition, ("IPC") and incorporates it herein as if fully set out in this Article IV of Chapter 29 with the additions, insertions, deletions, and changes set forth herein. The term "code" or "IPC" without further description when used in the portions of the IPC which are not amended and in this Article IV of Chapter 29 shall mean the IPC as amended herein by the additions, insertions, deletions, and changes set forth and adopted herein. Whenever the code refers to publications of the International Code Council, which have been adopted by the City, such references shall be to the version of the publications as amended by the City.
29-4.1. Chapter 1 "Scope and Administration" is hereby amended by deleting in its entirety.
29-4.2. Chapter 1 "Scope and Administration" is hereby amended to comply with the provisions along with the amendments as described in the Chapter 1 Scope and Administration of the 2024 International Building Code.
29-4.3. Subsection 410.4 "Substitutions" is amended by deleting the second sentence and replacing it with the following:
In all other occupancies where drinking fountains are required, water dispensers connected to the potable water system shall be permitted to be substituted for the first required fountain and any water dispenser shall be permitted to be substituted for not more than 50 percent of the required number of drinking fountains.
29-4.4. Subsection 1003.3.7 "Gravity grease interceptors and gravity grease interceptors with fats, oils, and greases disposal systems" is amended by deleting the first sentence and replacing it with the following:
The required capacity of gravity grease interceptors and gravity grease interceptors with fats, oils, and greases disposal systems shall be sized per the City of Chandler DFU Conversion Chart:
Total DFU Conversion to Grease Interceptor Size
Total DFUs* | Interceptor Volume (Gallons)
0 to 21 | 750
22 to 35 | 1,000
36 to 90 | 1,250
91 to 172 | 1,500
173 to 216 | 2,000
217 to 307 | 2,500
308 to 342 | 3,000
*Establishments resulting in total DFU's > 342 shall be designed by a professional engineer, registered in the State of Arizona.
(Ord. No. 1687, § 2, 10-9-86; Ord. No. 2127, §§ 1.E.1, 1.E.2, 4-26-90; Ord. No. 2284, 6-25-92; Ord. No. 2431, § 1, 1-27-94; Ord. No. 2512, §§ A, B, 11-3-94; Ord. No. 2553, § 1, 5-11-95; Ord. No. 3030, § 2, 10-14-99; Ord. No. 3409, § 4, 1-23-03; Ord. No. 3610, 1-27-05; Ord. No. 4082, § 7, 8-28-08; Ord. No. 4303, § 5, 5-26-11, eff. 7-1-11; Ord. No. 4452, § 5, 6-27-13, eff. 8-1-13; Ord. No. 4700, § 4, 5-12-16, eff. 7-1-16; Ord. No. 4847, § 3(Exh.), 12-10-18, eff. 7-1-19; Ord. No. 4993, § 3(Exh.), 2-24-22, eff. 7-1-22; Ord. No. 5108, § 3(Exh.), 12-9-24, eff. 7-1-25)