WATER SERVICE
Tyler City Code ch. 19, art. III, div. A
in effectTyler City Code § 19-21 Water meters required; repairs.
Sec. 19-21. Water meters required; repairs.
Except as specifically provided in this Code, all water furnished by the Utility to its users shall be measured by meter. The size, type and right to own and control all meters used by the users of its water shall be determined by the Director and will be provided in accordance with section 19-60 e. Repairs made to correct manufacturing defects and defects caused by normal wear shall be made by the Division without expense to the customer. When replacements, repairs or adjustments of any meter or meter box are rendered necessary by the act, neglect or carelessness of the owner or occupant of any premises, any expenses shall be charged against and collected from the owner or occupant of the premises and if not paid, service will be discontinued. (Ord. No. O-96-54, 6-26-96) (Ord. No. 0-99-80, 10/20/99) (Ord. No. 2009-7, 2/11/09)
Tyler City Code § 19-22 Due date; place of payment.
Sec. 19-22. Due date; place of payment.
Each bill for water or sewer service becomes due and payable each month at the City of Tyler Utilities Office. (Ord. No. O-96-54, 6-26-96) (Ord. No. 0-99-80, 10/20/99)
Tyler City Code § 19-23 Supplying water to another by user.
Sec. 19-23. Supplying water to another by user.
No customer may, without the written permission of the Division, supply water to other persons or to other users or allow them to take it. (Ord. No. O-96-54, 6-26-96) (Ord. No. 0-99-80, 10/20/99)
Tyler City Code § 19-24 Extending water service to another premises.
Sec. 19-24. Extending water service to another premises.
After water is introduced into any building or on any premises, lines from that building may not be extended by any plumber or any other person to another premises. (Ord. No. O-96-54, 6-26-96) (Ord. No. 0-99-80, 10/20/99)
Tyler City Code § 19-25 Separate service lines.
Sec. 19-25. Separate service lines.
Two (2) houses are not permitted to be supplied with one service line. Every user shall be supplied by a single service pipe line and meter from a water main located in a public street or easement adjacent to the property receiving service. An exception may be made by special permission of the Director when separate service lines would create a hardship, but in no case will two (2) users be supplied by a single service line smaller than one (1) inch diameter.
The Director may, at its option, allow the construction of a single service line connection to service two properties using a “y” at the common/joint property line. The Division shall be responsible for maintenance of that portion of service line extending from the main to the “y” and meters located at the common/joint property line. (Ord. No. O-96-54, 6-26-96) (Ord. No. 0-99-80, 10/20/99) (Ord. No. 2009-7, 2/11/09)
Tyler City Code § 19-26 Single connection and commercial classification for certain multiple dwellings.
Sec. 19-26. Single connection and commercial classification for certain multiple dwellings.
Apartment houses, townhouses, condominium dwellings, mobile home parks under single ownership and other buildings designed for or occupied exclusively by three (3) or more families may be provided water service with a single connection to the main and a single meter. Service shall be classified as commercial service and shall be provided at rates established by the City Council. (Ord. No. O-96-54, 6-26-96)
Tyler City Code § 19-27 Tapping of water mains.
Sec. 19-27. Tapping of water mains.
It is unlawful for any person other than an authorized Division employee or contractor employed by the Division to tap any water main, make any connections with the water main, or extend service pipes from a water main or install a curb stop and meter box. All connections shall be under exclusive control of the Division. Water main taps, service lines, curb stops, meters, meter boxes, and all other appurtenances installed shall be paid for in advance according to schedule of prices in Section 19-22. (Ord. No. O-96-54, 6-26-96) (Ord. No. 0-99-80, 10/20/99)
Tyler City Code § 19-28 Diversion of water from metered flow.
Sec. 19-28. Diversion of water from metered flow.
Whoever bypasses a water meter belonging to the Division, or prevents a water meter from registering the amount of water passing through such meter, or in any way interferes with the proper action or just registration of a meter, or, without the consent in writing of the Director, diverts the water from any pipe(s) of the water utilities, or otherwise uses, or causes to be used, without the consent of the Director, any water produced or distributed by the Division, or retains possession of, or refuses to deliver any meter or other appliance loaned by the Division for the purpose of furnishing water through same is guilty of a misdemeanor. The presence at any time on or about a city water meter or pipe or any device or pipes facilitating the:
a. diversion of water or prevention of its free passage and registration by the meter,
b. diversion from the meter,
c. prevention of water reaching the meter,
d. prevention of the just registration of the meter(s),
e. taking of any water except through a meter as above set forth, shall constitute prima facie evidence that the person owning or having custody and control of the room, building, place or premises where such device or pipe is, knows of the pipe or device and is responsible for its use.
Proof that a person would be financially benefited by the failure of water to be metered, together with proof that the person had access to the place where diversionary or blocking devices were installed is prima facie evidence that the person is responsible for the installation and use of any device used to divert water from metering. (Ord. No. O-96-54, 6-26-96) (Ord. No. 0-99-80, 10/20/99) (Ord. No. 2009-7, 2/11/09)
Tyler City Code § 19-29 Malicious or willful interference with water service.
Sec. 19-29. Malicious or willful interference with water service.
It is unlawful for any person, individually or in association with others, to break, injure or tamper with any part of the water utility system, or intentionally interfere with or prevent the running and operation of said system. (Ord. No. 0-99-80, 10/20/99)
Tyler City Code § 19-30 Connection to privately owned elevated tanks.
Sec. 19-30. Connection to privately owned elevated tanks.
Elevated water storage tanks located on the roofs of buildings for water distribution shall have a single connection to water mains, six-inch diameter or smaller, and shall fill over the top of the storage tank with a minimum twelve-inch air gap between discharge pipe and maximum water level. Said elevation tanks and service connections thereto may be constructed only after approval of detailed construction plans by the Directorr. (Ord. No. O-96-54, 6-26-96) (Ord. No. 0-99-80, 10/20/99) (Ord. No. 2009-7, 2/11/09)
Tyler City Code § 19-31 Water used in construction charged to property owner.
Sec. 19-31. Water used in construction charged to property owner.
Where a temporary authorization to use water for the construction or repair of property, the water used shall be charged to the property owner. A permanent connection for the property may not be authorized until all temporary use charges are paid. The Director reserves the right to estimate the amount of water used whenever precise metering or measurement is not available. (Ord. No. O-96-54, 6-26-96) (Ord. No. 0-99-80, 10/20/99) (Ord. No. 2009-7, 2/11/09)
Tyler City Code § 19-32 Boilers.
Sec. 19-32. Boilers.
All boilers for heating water shall be provided with safety valves, and check valves shall be placed on service pipes to protect the meters from hot water. Any person failing to comply with this provision shall have the water supply cut off and it shall not be turned on again until such valve shall have been installed. All steam boilers connecting directly with the City supply are required to provide a tank(s) for at least twelve (12) hours storage. Churches, auditoriums, theaters, schools and factories may be supplied through one connection with the water main in the street. (Ord. No. O-96-54, 6-26-96)
Tyler City Code § 19-33 Responsibility for leakage.
Sec. 19-33. Responsibility for leakage.
a. Consumer responsibility for leakage. Tyler Water Utilities is not responsible for locating or repairing leaks on the customer's side of the meter. All property owners, their agents and tenants, shall be held responsible as consumers for loss of water due to visible leakage in pipes, faulty or defective equipment such as toilets, faucets, sprinkler systems, and outdoor spigots, any unauthorized water use (i.e. theft, mischief, vandalism), or plumbing inside the discharge side of the meter on said property. In this instance, lost water will be billed according to the rates provided herein. If lost water is not paid for by the due date, Tyler Water Utilities reserves the right to suspend water service according to Sec. 19-63. Service will not be reconnected until all past due balances and any applicable fees are paid in full, and all leaks have been repaired to the satisfaction of the Director. If customers notice an abnormal water usage amount or a large billing discrepancy, the customer has a responsibility to inform Tyler Water Utilities.
b. Process for seeking a leakage credit. Customers are responsible for keeping plumbing on their property in good working order and are encouraged to be aware of their average consumption of water and water use history. All property owners, their agents, and tenants may request an adjustment to a water bill, i.e., leakage credit, showing excessive use due to a loss of water attributable to a concealed or hidden leak. A concealed or hidden leak is defined as a leak that occurs generally underground, inside a wall, or hidden from view and is difficult to detect or locate, requiring disturbance of the wall to view or repair and would be unnoticed, unheard, or unseen by the customer. Leakage credits are offered as a courtesy to help residents recoup some unexpected repair and water service costs. Leakage credits are not guaranteed. A customer must complete and file the designated leakage credit form with Tyler Water Utilities within twelve (12) months of the date of repair. To apply for a leakage credit, the customer must file the Request For Leakage Credit form with Tyler Water Utilities. A customer may apply for no more than one Leakage Adjustment Credit in any twelve-month period for any one account. A leakage credit is available only for customers with at least three billing cycles of usage history on their account at the subject address at the time of the water loss. Customers are encouraged to file the leakage credit form promptly.
c. Determination of leakage credit. Upon receipt of a properly completed leakage credit form, the Director or Business Office Manager shall review the form. To determine the amount of leakage credit, the Director or Business Office Manager shall verify the applicant's average water usage (based on historical usage and other relevant factors) prior to the billing cycle(s) in which the water loss occurred and consider all supporting documentation submitted with the leakage credit form. If the Director or Business Office Manager determines that water loss has occurred due to a concealed or hidden leak, and without the knowledge of the customer, the Director or Business Office Manager may make an adjustment to no more than three (3) monthly water bills affected by the leak. After the account has been read for the next billing cycle, if the consumption use has returned to the normal average consumption use, any approved leakage credit will be applied to the account. Any approved leakage credit will not be applied while the consumption usage amount remains above the customer's normal average consumption amount. If the amount of consumption used remains above the customer's normal average consumption amount, the Director or Business Office Manager will review the leakage credit request within the next billing cycle. If the customer has already paid the bill for which a leakage credit is authorized, any excess amount actually paid by the customer shall be applied as a credit to the applicant's account. An actual payment refund will only be provided when the customer has closed the water account before the leakage credit process has been completed. Before the customer can request a refund check for any remaining credit balances, the final bill would have to be issued by Tyler Water Utilities. (Ord. No. O-96-54, 6-26-96) (Ord. No. 0-99-80, 10/20/99) (Ord. 0-2004-93, 11/24/04) (Ord. No. 2009-7, 2/11/09) (Ord. No O-2024-63, 6/12/2024)
Tyler City Code § 19-34 Right of entry by Division.
Sec. 19-34. Right of entry by Division.
a. Every consumer shall at all reasonable times permit a Division representative to enter the premises and building for examination of pipes and fixtures, and the manner in which the water is used, and refusal by any consumer shall result in refusal of water supply from the Division until such permission is granted.
b. Every consumer who uses a an unmetered sprinkler system for the purpose of fire protection shall at all reasonable times permit the Division inspector to enter the premises and building for examination of pipes and fixtures and the manner in which the water is used, and refusal by any consumer shall result in refusal of water supply from the Division until such permission is granted. (Ord. No. O-96-54, 6-26-96) (Ord. No. 0-99-80, 10/20/99)
Tyler City Code § 19-35 Repair or renewing of water service lines.
Sec. 19-35. Repair or renewing of water service lines.
The Division reserves the right to make all repairs and renewals of service lines from main to meter and it is unlawful for any other person to repair or renew service lines from main to meter without written consent of the Director. (Ord. No. O-96-54, 6-26-96) (Ord. No. 0-99-80, 10/20/99) (Ord. No. 2009-7, 2/11/09)
Tyler City Code § 19-36 Cutting off water for repair work.
Sec. 19-36. Cutting off water for repair work.
a. The Division reserves the right to discontinue temporarily and to reconnect without notice the water supply to all users for making repairs, connections, extensions and cleaning of mains, machinery, storage reservoirs or any other appurtenances to the water supply and distribution system. All users having boilers, air conditioning equipment or other water consuming devices, which may become damaged due to interruption of water, connect to the City utility system at their own risk. City shall not be liable for any damage that may occur to water consuming devices due to the water being cut off for any purpose. Further, the City shall not be liable for any damage to plumbing, pipes or fixtures on premises caused by pressure from City water system or for the freezing of pipes.
b. The City further reserves the right to discontinue water service to enforce a user’s obligation to repair water or sewer facilities owned by the user whenever such failure causes waste of water, contamination of potable supplies, or unsanitary conditions. (Ord. No. O-96-54, 6-26-96) (Ord. No. 0-99-80, 10/20/99)
Tyler City Code § 19-37 Cross-Connection Control Program.
Sec. 19-37. Cross-Connection Control Program.
a. No water service connection shall be made to any establishment where a potential or actual contamination hazard exists unless the water supply is protected in accordance with the Texas Commission on Environmental Quality Rules and Regulations for Public Water Systems and this ordinance. The City of Tyler Director and Public Works shall discontinue water service if a required backflow prevention assembly is not installed, maintained and tested in accordance with the Texas Commission on Environmental Quality Rules and this ordinance.
b. Definitions
1. Air gap -- The unobstructed vertical distance through the free atmosphere between the lowest opening from any pipe or faucet conveying water to a tank, fixture, receptor, sink, or other assembly and the flood level rim of the receptacle.
2. Backflow prevention assembly -- A device that is designed to prevent a physical connection between the public drinking water supply and a potential source of contamination.
3. Connection -- A single family residential unit or each commercial or industrial establishment to which drinking water is supplied from the system.
4. Contamination--The presence of any foreign substance (organic, inorganic, radiological or biological) in water which tends to degrade its quality so as to constitute a health hazard or impair the usefulness of the water.
5. Cross-connection--A physical connection between a public water system and either another supply of unknown or questionable quality, any source which may contain contaminating or polluting substances, or any source of water treated to a lesser degree in the treatment process.
6. Health hazard--A cross-connection, potential contamination hazard, or other situation involving any substance that can cause death, illness, spread of disease, or has a high probability of causing such effects if introduced into the potable drinking water supply.
c. Backflow Prevention Assembly Installation, Testing and Maintenance
1. All backflow prevention assemblies shall be tested upon installation by a recognized backflow prevention assembly tester and certified to be operating within specifications. Backflow prevention assemblies which are installed to provide protection against high health hazards must also be tested and certified to be operating within specifications at least annually by a recognized backflow prevention assembly tester.
2. All backflow prevention assemblies shall be installed and tested in accordance with the manufacture's instruction, the American Water Works Association's Recommended Practice for Backflow Prevention and Cross-connection Control (Manual M14) or the University of Southern California Manual of Cross-connection Control.
3. Assemblies shall be repaired, overhauled or replaced at the expense of the customer whenever said assemblies are found to be defective. Original forms of such tests, repairs and overhauls shall be kept and submitted to Tyler Water Utilities within five (5) working days of the test, repair or overhaul of each backflow prevention assembly.
4. No backflow prevention assembly or device shall be removed from use, relocated or other assembly or device substituted without the approval of the Director or his designee. Whenever the existing assembly or device is moved from the present location or can not be repaired, the backflow assembly or device shall be replaced with a backflow assembly or device that complies with this section, the American Water Works Association's Recommended Practice for Backflow Prevention and Cross-connection Control, current edition, or the University of Southern California's Manual of Cross-Connection Control, current edition or the current Plumbing Code of the city of Tyler, Texas, whichever is more stringent.
5. Test gauges used for the backflow prevention assembly testing shall be calibrated at least annually in accordance with the American Water Works Association's Recommended Practice for Backflow Prevention and Cross-Connection Control (Manual M14), current edition, or the University of Southern California's Manual of Cross-Connection Control, current edition. Copies of the latest calibration reports, verifying the last date of equipment calibration, shall be submitted with each assembly device test report to Tyler Water Utilities.
6. A recognized backflow prevention assembly tester must hold a current endorsement from the Texas Commission on Environmental Quality.
d. Customer Service Inspections
1. A customer service inspection shall be completed prior to providing continuous water service to all new construction or on any existing service when:
(a) the Director or his representative has reason to believe that cross-connections or other contamination hazard exist, or
(b) after any material improvement, correction or addition to the private water distribution facilities.
2. Only individuals with the following credentials shall be recognized as capable of conducting a customer service inspection:
(a) Plumbing Inspectors and Water Supply Protection Specialists that have been licensed by the Texas State Board of Plumbing Examiners.
(b) Certified Waterworks Operators and members of other water related professional groups who have completed a training course, passed an examination administered by the commission or its designated agent and hold a current endorsement issued by the Commission.
3. The customer service inspection must certify that:
(a) No direct connection between the public drinking water supply and a potential source of contamination is permitted. Potential sources of contamination shall be isolated from the public water system by a properly installed air gap or an appropriate backflow prevention assembly.
(b) No cross-connection between the public water system and a private water system exists. Where an actual properly installed air gap is not maintained between the public water supply and a private water supply, approved reduced pressure-zone backflow prevention is properly installed and a service agreement exists for annual inspection and testing by a recognized backflow prevention assembly tester.
(c) No connection exists which allows water to be returned to the public drinking water supply is permitted.
(d) No pipe or pipe fitting which contains more than 8% lead may be used for the installation or repair of plumbing at any connection that provides water for human consumption.
(e) No solder or flux which contains more than 2% lead can be used for the installation or repair of plumbing at any connection that provides water for human use. A minimum of one (1) lead test shall be performed for each inspection. (Ordinance 0-2006-100, 12/13/06) (Ord. No. 2009-7, 2/11/09)
Tyler City Code § 19-38 Fluoridation of water.
Sec. 19-38. Fluoridation of water.
The Tyler Municipal Water Supply is fluoridated to maintain a fluoride concentration at the level as recommended by public health authorities. (Ord. No. O-96-54, 6-26-96) (Ord. No. 0-99-80, 10/20/99)
Tyler City Code § 19-39 Water well permit.
Sec. 19-39. Water well permit.
Any person proposing to dig, bore or drill a water well within the City limits shall obtain a permit from the Director before beginning work. (Ord. No. O-96-54, 6-26-96) (Ord. No. 0-99-80, 10/20/99) (Ord. No. 2009-7, 2/11/09)
Tyler City Code § 19-40 Application for permit.
Sec. 19-40. Application for permit.
The owner of the land on which the well is to be placed shall file permit application containing the following:
1. Legal description of the property;
2. Location of the well site on the property;
3. Proposed depth of the well;
4. Name and registration number from the water well drillers' board of the well driller;
5. Size of casing, tubing and pump proposed;
6. Method of well completion proposed;
7. Maximum volume of water per day to be used from the well and the purposes for which it is to be used. (Ord. No. O-96-54, 6-26-96)
Tyler City Code § 19-41 Vending water.
Sec. 19-41. Vending water.
It is unlawful for any person to sell or resell City water for domestic or any other uses within or without the City without receiving a permit to do so from the Director. (Ord. No. O-96-54, 6-26-96) (Ord. No. 0-99-80, 10/20/99) (Ord. No. 2009-7, 2/11/09)
Tyler City Code § 19-42 Exposing meter or fire hydrant to damage; moving meter or hydrants.
Sec. 19-42. Exposing meter or fire hydrant to damage; moving meter or hydrants.
It is unlawful to build driveways or other traffic ways so as to expose any meter or fire hydrant to damage from traffic. Whenever the property owner requests the moving of any meter or fire hydrant, the moving cost is the expense of the property owner. Upon deposit of any estimated cost of moving the same, the Division shall make the desired change in location. (Ord. No. O-96-54, 6-26-96) (Ord. No. 0-99-80, 10/20/99)
Tyler City Code § 19-43 Use of fire hydrants.
Sec. 19-43. Use of fire hydrants.
It is unlawful for any person except a Fire Department or Division employee to take off a cap, to open or use water from a fire hydrant. In exceptional cases where water for construction is not otherwise available on a temporary basis, the Director may issue a letter of authorization to allow the use of fire hydrants for construction water. In the event such permission is granted, it shall be according to terms prescribed by the Director in said letter of authorization. (Ord. No. O-96-54, 6-26-96) (Ord. No. 0-99-80, 10/20/99) (Ord. No. 2009-7, 2/11/09)
Tyler City Code § 19-44 Private Fire Hydrants and Maintenance.
Sec. 19-44. Private Fire Hydrants and Maintenance.
Where required by the Fire Department, or insurance companies for adequate fire protection on private premises, property owners shall be permitted to install and maintain private fire hydrants. All hydrants shall conform to current City standards and shall be approved by the Director and the Fire Marshal prior to installation. The owners shall grant the City permission to inspect, flow and paint the hydrant.
If the need for fire hydrant repairs are discovered during a periodic inspection by Division, the property owner will be notified of the necessary repairs and instructed to complete the repairs at the owner’s expense, within thirty (30) calendar days. At the end of the thirty (30) day period, a follow- up inspection of the fire hydrant will be performed by the City. If the indicated repairs have not been completed, the Director may undertake the necessary repairs, including the installation of a new fire hydrant, and bill the property owner for all costs incurred plus an additional $250.00 penalty for failure of the property owner to make the repairs.
Failure to reimburse the City for all expenses incurred and penalties levied may result in discontinuation of both domestic and fire protection water service. (Ord. No. O-96-54, 6-26-96) (Ord. No. 0-99-80, 10/20/99) (Ord. No. 2009-7, 2/11/09)
Tyler City Code § 19-45 Sprinkler or fire service.
Sec. 19-45. Sprinkler or fire service.
a. No connection for a sprinkler or fire service may be permitted unless application has been made to and granted by the Director. A meter of the kind and size prescribed by the Director shall be required.
b. The furnishing, installation, maintenance and inspection of all meters and services, checks, bypasses, valves, piping, etc., necessary for the operation of sprinkler systems and fire services shall be at the expense of the consumer.
c. When ground storage reservoirs or fire pumps are installed on private property, such pumps shall discharge into a fire system approved by the Director. An approved check valve to prevent backflow from the fire pump into City distribution system shall be installed in the owner's fire service between the point where the pump discharges into such service and the connection of such fire service to City mains. The water in such fire storage tanks will be maintained in a potable condition and subject to periodic inspection by City personnel. The tanks and water quality shall be maintained in compliance with the requirements of the appropriate state agency (Texas Natural Resource Conservation Commission) and the City. Such tanks shall not be of the pressure type. The delivery of City water to the tank shall be above the tank flow line with a one-foot air gap. The supply line to this tank shall not be controlled by a quick acting valve which will cause water hammer in the distribution system. Water tanks shall be equipped with an overflow pipe at least twelve (12) inches below the City inlet pipe. The overflow pipe shall be protected from access of insects, birds or animal life. The pipe shall be at least two (2) inches in diameter larger than the inlet supply line from the City distribution system. Such storage tank shall be provided with a drain pipe and valve for easy drainage. The drain pipe may not be connected to the City sanitary sewer system. (Ord. No. O-96-54, 6-26-96) (Ord. No. 0-99-80, 10/20/99) (Ord. No. 2009-7, 2/11/09)
Tyler City Code § 19-46 Division regulations constitute contract.
Sec. 19-46. Division regulations constitute contract.
All provisions of this article pertaining to the Division shall be deemed to be incorporated in every contract between the Division and its customers, and each customer shall be charged with the knowledge of such provisions, and, by applying for and accepting water from Division, to have assented to the provisions hereof. (Ord. No. O-96-54, 6-26-96)
Tyler City Code § 19-47 Water and sanitary sewer service furnished to City Departments.
Sec. 19-47. Water and sanitary sewer service furnished to City Departments.
All City Departments shall be provided water and sanitary sewer services under the same terms and at the rates established herein, which they shall pay for from their budgeted funds. (Ord. No. O-96-54, 6-26-96)
Tyler City Code § 19-48 Damage in water system.
Sec. 19-48. Damage in water system.
It is unlawful for any person to deface the houses, walls, machinery, equipment or fixtures connected with or pertaining to the Water Utility System. (Ord. No. 0-99-80, 10/20/99)
Tyler City Code § 19-49 Sanitary Control for Protection of Public Water Wells
Sec. 19-49. Sanitary Control for Protection of Public Water Wells
Groundwater sources shall be protected from the danger of pollution caused by flooding or unsanitary surroundings, such as privies, sewage, sewage treatment plants, livestock and animal pens, solid waste disposal sites or underground petroleum and chemical storage tanks and liquid transmission pipelines, or abandoned and improperly sealed wells, as follows:
a. The following items are not allowed within a 50-foot radius of a well site: tile or concrete sanitary sewer, sewerage appurtenance, septic tank, storm sewer, cemetery, or livestock in pastures.
b. The following items are not allowed within a 150-foot radius of a well site: septic tank perforated drainfield, areas irrigated by low dosage, low angle spray on-site sewage facilities, absorption bed, evapotranspiration bed, improperly constructed water well, or underground petroleum and chemical storage tank or liquid transmission pipeline.
c. Sanitary or storm sewers constructed of ductile iron or polyvinyl chloride (PVC) pipe meeting American Water Works Association (AWWA) standards, having a minimum working pressure of 150 pounds per square inch (psi) or greater, and equipped with pressure type joints may be located at distances of less than 50 feet from a well site, but in no case shall the distance be less than 10 feet. (0-2008-131; 9/24/08)
Source: City of Tyler, Texas, Code of Ordinances and Charter (American Legal Publishing, codelibrary.amlegal.com)URL: https://codelibrary.amlegal.com/codes/tyler/latest/tyler_tx/0-0-0-93072Fetched: 11/14/2026