Sec. 8-407. - Required devices.
(1) An approved backflow prevention assembly shall be installed downstream of the meter on each service line to a customer's premises at or near the property line or immediately inside the building being served, but in all cases, before the first branch line leading off the service line, when any of the following conditions exist: a. It is impractical to provide an effective air gap separation. b. The owner/occupant of the premises cannot or is not willing to demonstrate to the general manager that the water use and protective feature of the plumbing are such as to pose no threat to the public water supply. c. The nature and mode of operation within a premises are such that frequent alterations are made to the plumbing. d. There is likelihood that protective measures may be subverted, altered or disconnected. e. The nature of the premises is such that the use of the structure may change to a use wherein backflow prevention is required. f. The plumbing from a private well or other water source enters the premises served by the public water system. (2) The protective devices shall be of the reduced pressure zone type (except in the case of certain fire protection systems) approved by the Tennessee Department of Environment and Conservation, Division of Water Supply and the general manager, as to manufacture, model, size and application. The method of installation of backflow prevention devices shall be approved by the general manager prior to installation and shall comply with the criteria set forth by the Tennessee Department of Environment and Conservation, Division of Water Supply. The installation and maintenance of backflow prevention devices shall be at the expense of the owner or occupant of the premises. (3) Applications requiring backflow prevention devices shall include, but shall not be limited to, domestic water service and/or fire flow connections for all commercial and educational buildings, construction sites, all industrial and medical facilities, all fountains, lawn irrigation systems, wells, water softeners and other treatment systems, swimming pools and on all fire hydrant connections other than those by the fire department in combating fires. a. Class 1, 2 and 3 fire protection systems shall generally require a double check valve assembly except a reduced pressure backflow prevention device shall be required where: i. Underground fire sprinkler lines are parallel to and within ten feet of pipes carrying sewage or toxic materials. ii. Premises have unusually complex piping systems. iii. Pumpers connecting to the system have corrosion inhibitors or other chemicals added to the tankers. b. Class 4, 5, and 6 fire protection systems shall require reduced pressure backflow prevention devices. c. Wherever the fire protection system piping is not an acceptable potable water system material, or chemicals such as foam concentrates or antifreeze additives are used, a reduced pressure backflow prevention device shall be required.
(Ord. No. 30-1998-99, 1-7-99)
Ask a question about Clarksville law
Corpus searches the Clarksville sections it holds and shows the ones that match, with their citations. Free, no sign-in.