18.40.150 - Amend CBC Section 905.4 Subsection 1—Location of Class I standpipe hose connections.
Subsection 1 of Section 905.4 of the California Building Code is amended to read as follows: 1. In every required interior exit stairway or exterior exit stairway, a hose connection shall be provided for each floor level. Hose connections shall be located at the floor landing of each floor, unless otherwise approved by the Fire Code Official. See Section 909.20.2.3 for additional provisions in smokeproof enclosures.