21-0604. - Provisions for flood hazard reduction.
A. General standards—In all areas of special flood hazard, the following standards shall apply: 1. Anchoring a. All new construction and substantial improvements shall be anchored to prevent flotation, collapse, or lateral movement of the structure and shall be capable of resisting the hydrostatic and hydrodynamic loads. b. All manufactured homes which are placed or substantially improved must be elevated and anchored to resist flotation, collapse or lateral movement and shall be capable of resisting the hydrostatic and hydrodynamic loads. Methods of anchoring shall include, but are not limited to, the following: i. Over-the-top ties shall be provided at each of the four corners of the manufactured home, with two additional ties per side at intermediate locations, provided that manufactured homes less than 50 feet long shall have one additional tie per side. ii. Frame ties shall be provided at each corner of the home with five additional ties per side at intermediate points, provided that manufactured homes less than 50 feet long shall have four additional ties per side; iii. All components of the anchoring system shall be capable of carrying a force of 4,800 pounds. Any additions to a manufactured home shall be similarly anchored. 2. Construction materials and methods a. All new construction and substantial improvements shall be constructed with materials which are resistant to flood damage. b. All new construction and substantial improvements shall be constructed using methods and practices that minimize flood damage. c. All new construction and substantial improvements shall be constructed with electrical, heating, ventilation, plumbing, and air conditioning equipment and other service facilities that are designed and/or located so as to prevent water from entering or accumulating within the components during conditions of flooding. 3. Utilities a. All new and replacement water supply systems shall be designed to minimize or eliminate infiltration of flood waters into the system. b. New and replacement sanitary sewage systems shall be designed to minimize or eliminate infiltration of flood waters into the systems and discharge from the systems into flood waters. c. On-site waste disposal systems shall be located to avoid impairment or contamination during flooding. 4. Subdivisions a. All proposed subdivisions shall be consistent with the need to minimize flood damage. b. All subdivisions shall have public utilities and facilities such as sewer, gas, electrical, and water systems located and constructed to minimize flood damage. c. All subdivisions shall have adequate drainage provided to reduce exposure to flood damage. d. Base flood elevation data shall be provided for proposed subdivisions and other development proposals which contain at least 50 lots or five acres (whichever is less). 5. Specific standards—In all areas of special flood hazard where base flood elevation data has been provided as set forth in § 21-0602 or 21-0603, the following provisions are required: a. New construction and substantial improvement of any structure shall: i. Conform to structural and technical provisions set forth in the floodproofing code. ii. Be constructed in accordance with the Floodproofing Construction Requirements, on file in the Inspections Office of the city of Fargo, North Dakota. A registered professional engineer or architect shall develop and/or review structural design, specifications, and plans for the construction, and shall certify that the design methods of construction are in accordance with accepted standards of practice. iii. Have structural components capable of resisting hydrostatic and hydrodynamic loads and effects of buoyancy. Fully enclosed areas below the lowest floor that are subject to flooding shall be designed to automatically equalize hydrostatic flood forces on exterior walls by allowing for the entry and exit of floodwaters. Designs for meeting this requirement must either be certified by a registered professional engineer or architect or must meet or exceed the following minimum criteria: - A minimum of two openings having a total net area of not less than one square inch per square foot of enclosed area subject to flooding shall be provided; - The bottom of all openings shall be no higher than one foot above grade. - Openings may be equipped with screens, louvers, or other coverings or devices provided that they permit the automatic entry and exit of floodwaters. 6. Manufactured homes. a. Require all manufactured homes placed within Zone A shall be installed using methods and practices which minimize flood damage. For the purposes of this requirement, manufactured homes must be elevated and anchored to resist floatation, collapse, or lateral movement. Methods of anchoring may include, but are not limited to, use of over-the-top or frame ties to ground anchors. This requirement is in addition to applicable State and local anchoring requirements for resisting wind forces. b. Require all manufactured homes placed or substantially improved within Zones A 1-30, AH, or AE on sites (i) outside of a manufactured home park or subdivision, (ii) in a new manufactured home park or subdivision, (iii) in an expansion to an existing manufactured home park or subdivision, or (iv) in an existing manufactured home park or subdivision which has incurred substantial damage, be elevated on a permanent foundation so the lowest floor of the manufactured home is elevated one foot above the base flood elevation and be securely anchored to an adequately anchored foundation system to resist floatation, collapse, and lateral movement. c. Require that manufactured homes placed or substantially improved on sites in an existing manufactured home park or subdivision within Zones A 1-30, AH, or AE not subject to other requirements of this section be elevated so that either: (i) the lowest floor of the manufactured home is one foot above the base flood elevation, or (ii) the manufactured home chassis is supported by reinforced piers or other foundation elements of at least equivalent strength that are no less than 36" in height above grade and be securely anchored to an adequately anchored foundation system to resist floatation, collapse, and lateral movement. 7. Recreational Vehicles. a. In A1-30, AH, and AE Zones, all recreational vehicles to be placed on a site must: (i) be elevated and anchored to meet the requirements in 5.2-3; OR (ii) be on the site for less than 180 consecutive days; AND (iii) be fully licensed and highway ready 8. Encroachment Analysis. a. When a regulatory floodway has not been designated, the building inspector must require that no new construction, substantial improvements, or other development (including fill) shall be permitted within Zones A1-30 and AE on the community's FIRM, unless it is demonstrated that the cumulative effect of the proposed development, when combined with all other existing and anticipated development, will not increase the water surface elevation of the base flood more than one foot at any point within the community. b. Under the provisions of 44 CFR Chapter 1, Section 65.12, of the National Flood Insurance Program regulations, a community may approve certain development in Zones A1-30, AE, AH, on the community's FIRM which increases the water surface elevation of the base flood by more than one foot, provided that the community first applies for and receives a Conditional Letter of Map Revision (CLOMR) through FEMA. 9. Floodways—The following provisions shall apply to any development or construction in the floodway: a. Any development or construction is prohibited unless a registered professional engineer certifies that such development or construction shall not result in any increase in flood levels during the occurrence of the base flood discharge. Any increase, as used in this section, means any modeled impacted greater than 0.0 feet. b. All new construction and substantial improvements shall comply with all applicable flood hazard reduction provisions of this section. c. Under the provisions of 44 CFR Section 65.12 of the NFIP Regulations, a community may permit encroachments within the adopted regulatory floodway that would result in an increase in BFEs, provided that the community first applies for and receives a Conditional Letter of Map Revision (CLOMR) through FEMA.
Source: 2325 (1987), 2939 (1998), 4956 (2014), 5494 (2025).
Ask a question about Fargo law
Corpus searches the Fargo sections it holds and shows the ones that match, with their citations. Free, no sign-in.