15.48.180 - Ventilation requirements.
To maintain an acceptable concentration of carbon dioxide and oxygen in any shelter, a minimum amount of three cubic feet of air per minute per person should be introduced into the shelter based on the area requirements. If this is not practicable one of the following shall be used: A. If no mechanical ventilation is available, a net volume of five hundred (500) cubic feet per person shall be used for estimating the capacity of any shelter. B. If the mechanical ventilation does not supply the three cubic feet per minute the following table shall be used to determine the capacity of the shelter by a volume space basis: Air Supply | Volume per person 2.95 cfm | *65 cu. ft. 2.86 cfm | 100 cu. ft. 2.5 cfm | 150 cu. ft. 2.0 cfm | 200 cu. ft. 1.5 cfm | 300 cu. ft. 1.0 cfm | 400 cu. ft. 0.75 cfm | 450 cu. ft. 0.5 cfm | 500 cu. ft. All others use five hundred (500) cubic feet as in subsection A above.
(Prior code 13.32.180)