25.07.020 - Amendments.
The 2018 International Fuel Gas Code is amended and changed in the following respects:
CHAPTER 1 IS AMENDED AS FOLLOWS:
Change Section 101.1 to read as follows:
101.1 Title. These regulations shall be known as the Fuel Gas Code of the City of Saint Louis, hereafter referred to as "this code."
Delete Sections 103 thru 110 in their entirety.
Add new Section 103 to read as follows:
SECTION 103 ADMINISTERING OF THIS CODE
103.1 General. Authority, permitting, fees, penalties, inspections, duties, and means of appeal shall be as set forth in the Mechanical Code.
CHAPTER 2 IS AMENDED AS FOLLOWS:
Change Section 201.3 to read as follows:
201.3 Terms Defined in Other Codes. Where terms are not defined in this code and are defined in the Building Code, Fire Code, Mechanical Code, Plumbing Code and NFPA, such terms shall have meanings ascribed to them as in those codes.
Add Section 201.5 to read as follows:
201.5 Referenced Other Codes and Standards. Any codes or standards referenced in this code shall be taken to mean the applicable City of Saint Louis code.
Change Section 202 by the addition or modification of the following definitions:
Diversity factor. Ratio of the maximum probable demand to the maximum possible demand.
Heating value, total. The number of Btu's produced by the combustion, at constant pressure, of 1 cubic foot (0.0283 m3) of gas when the products of combustion are cooled to the initial temperature of the gas and air, when the water vapor formed during combustion is condensed, and when all necessary corrections have been applied.
Purge. To clear of air, water, or other foreign substances.
Workmanlike. Executed in a skilled manner; e.g., generally plumb, level, square, in line, undamaged, and without marring adjacent work.
CHAPTER 3 IS AMENDED AS FOLLOWS:
Change Section 301.6 to read as follows:
301.6 Plumbing Connections. Potable water supply and building drainage system connections to appliances regulated by this code shall be in accordance with the Plumbing Code.
Add Section 302.8 to read as follows:
302.8 Stud Guards. When the edge of bored holes is less than one inch (25mm) from the edge of a stud or joist and when notched studs or joists are covered, stud guards shall be installed to protect service lines from fastener damage.
Change Section 307.3 to read as follows:
307.3 Drain Pipe Materials and Sizes. Components of the condensate disposal system shall be cast iron, galvanized steel, copper, cross-linked polyethylene, polyethylene, ABS, CPVC PVC or polypropylene pipe or tubing. Components shall be selected for the pressure and temperature rating of the installation. Joints and connections shall be made in accordance with the applicable provisions of the Plumbing Code relative to the material type. Condensate waste and drain line size shall not be less than ¾-inch internal diameter and shall not decrease in size from the drain pan connection to the place of condensate disposal. Where the drain pipes from more than one unit are manifolded together for condensate drainage, the pipe or tubing shall be sized in accordance with an approved method.
CHAPTER 4 IS AMENDED AS FOLLOWS:
Add Section 403.4.2.1 to read as follows:
403.4.2.1 Galvanized Steel Pipe and Fittings. Galvanized steel pipe and galvanized steel fittings (steel pipe and fittings coated in zinc) shall not be used in any fuel-gas piping systems, including, but not limited to, natural gas, propane, fuel oil, gasoline, or other types of gaseous or liquid fuel.
Add Section 404.1.1 to read as follows:
404.1.1 Valves and Regulators. Manual valves, automatic valves, and regulators shall not be installed above drop ceilings or in concealed locations.
CHAPTER 6 IS AMENDED AS FOLLOWS:
Change Sections 624.1.1 and 624.2 to read as follows:
624.1.1 Installation Requirements. The requirements for water heaters relative to sizing, relief valves, drain pans and scald protection shall be in accordance with the Plumbing Code.
624.2 Water Heaters Utilized for Space Heating. Water heaters utilized both to supply potable hot water and provide hot water for space-heating applications shall be listed and labeled for such applications by the manufacturer and shall be installed in accordance with the manufacturer's instructions and the Plumbing Code.
CHAPTER 8 IS AMENDED AS FOLLOWS:
Change Chapter 8 by the addition of the following:
IAPMO International Association of Plumbing and Mechanical Officials
5001 E. Philadelphia Street
Ontario, CA 91761-2816
UPC-09-Uniform Plumbing Code
201.3, 301.6, 307.3, 624.1.1, 624.2
(Ord. No. 70801, § 3, 8-6-2018.)