15.32.050 - City of Henderson amendments.
Certain parts, articles, divisions, sections and/or subsections and tables of the International Fire Code and the booklet are hereby amended as follows.
Section 103 CODE COMPLIANCE AGENCY.
Section 103 CODE COMPLIANCE AGENCY is re-titled, amended and replaced as follows:
Section 103 FIRE SAFETY
Section 103.1 General.
Section 103.1 General is amended as follows:
Section 103.1 General: Fire safety is established within the City of Henderson. The function of this division shall include assisting the fire chief in the administration and enforcement of the provisions of the fire code. Management oversight of fire safety is provided by the building official. The fire chief has the final decision-making authority on all technical fire code issues.
Section 103.2.1 Fire Code Official.
A new Section 103.2.1 Fire code official is added as follows:
103.2.1 Fire code official: The fire chief may designate fire department and/or fire safety staff to assist him with his duties as the fire code official to perform the duties as set forth in the fire code.
Section 103.3.1 Fire Safety Personnel, Fire Department, and Police.
A new Section 103.3.1 Fire safety personnel, fire department and police is added as follows:
Section 103.3.1 Fire safety personnel, fire department, and police. The fire chief, members of the fire department, and members of fire safety shall have the powers of a police officer in performing their duties under this code.
Section 104.2 Determination of Compliance / Substantial Compliance.
Revise Determination of Compliance / Substantial Compliance Section 104.2 as follows:
Section 104.2 Determination of compliance / Substantial compliance. The fire code official shall have the authority to determine compliance with this code, to render interpretations of this code and to adopt policies and procedures in order to clarify the application of its provisions. Such interpretations, policies and procedures:
1. Shall be in compliance with the intent and purpose of this code.
2. Shall not have the effect of waiving requirements specifically provided for in this code.
Substantial compliance standard. In the enforcement of specific provisions of this code or adopted standard, the fire chief is authorized to grant minor variations from the strict application of specific code provisions where, in the opinion of the fire chief, the work is in substantial compliance with the intent of the adopted codes and/or standards.
Section 104.4.2 Authority to Inspect.
A new Section 104.4.2 Authority to inspect is added as follows:
Section 104.4.2 Authority to inspect. Fire safety and/or the fire department shall inspect, as often as necessary, buildings and premises, including such other hazards or appliances designated by the fire chief for the purpose of ascertaining and causing to be corrected any conditions which would reasonably tend to cause fire or contribute to its spread, or any violation of the purpose or provisions of the fire code and of any other law or standard affecting fire safety.
Section 105.1.1.1 Permit and Service Fee Schedule.
A new Section 105.1.1.1 Permit and service fee schedule is added as follows:
105.1.1.1 Permit and service fee schedule. Fees for permits, inspections, plan checks and other services shall be as set forth in the development services schedule of fees, as adopted and amended from time to time by the Henderson City Council (HMC 15.02).
Section 105.5.5 Carnivals and fairs.
Section 105.5.5 Carnivals and fairs is amended as follows:
105.5.5 Carnivals and fairs. An operational permit is required to conduct a carnival or fair.
Section 105.5.34 Mobile food preparation vehicles.
Section 105.5.34 Mobile food preparation vehicles is amended as follows:
105.5.34 Mobile food preparation vehicles. An operational permit is required for mobile food preparation vehicles equipped with appliances that produce smoke or grease-laden vapors, where the main business office is located within the boundaries of this jurisdiction.
Exception: Mobile food preparation vehicles that have a valid/current fire operational permit from another Nevada jurisdiction.
Section 105.5.67 Fire Suppression and Extinguishing Systems.
Section 105.5.67 Fire suppression and extinguishing systems is added as follows:
105.5.67 Fire suppression and extinguishing systems. An operational permit is required for facilities that contain a fire suppression or extinguishing system. See Chapter 9 of the 2024 International Fire Code.
Section 105.5.68 Mobile fueling vehicle.
Section 105.5.68 Mobile fueling vehicle is amended as follows:
105.5.68 Mobile fueling vehicle. An operational permit is required to operate a mobile fueling vehicle where the main business office is located within the boundaries of this jurisdiction. See Chapter 57 of the 2024 International Fire Code.
Exception: Mobile fueling vehicles that have a valid/current fire operational permit from another Nevada jurisdiction.
Section 105.5.69 Operational permit for new and existing buildings.
Section 105.5.69 Operational permit for new and existing buildings is added as follows:
105.5.69 Operational permit for new and existing buildings. An annual, biennial or triennial operational permit is required for new and existing buildings. See section 325.
Exception: One- and two-family dwellings; townhouses; and buildings that are regulated by NRS/NAC 477 or NRS/NAC 499.
Section 106.1 Submittals.
Section 106.1 Submittals is amended as follows:
106.1 Submittals. Construction documents and supporting data shall be submitted in electronic format with each application for a permit and in such form and detail as required by the fire code official. Submittals shall demonstrate compliance with the adopted codes and standards, City of Henderson checklists and guidelines. The construction documents shall be prepared by a registered design professional where required by the statutes of the jurisdiction in which the project is to be constructed.
Exception: The fire code official is authorized to waive the submission of construction documents and supporting data not required to be prepared by a registered design professional if it is found that the nature of the work applied for is such that review of construction documents is not necessary to obtain compliance with this code.
Section 108.7 Fire Apparatus Standby.
Section 108.7 Fire apparatus standby is added as follows:
108.7 Fire apparatus standby fee shall be five hundred ($500) dollars per hour with a minimum of four (4) hours for each standby apparatus or unit. Fees for standby rescue unit(s) shall be two hundred and fifty ($250) dollars per hour with a minimum of four (4) hours for each standby rescue.
Section 110.3.1.1 Reporting Means.
Section 110.3.1.1 Reporting means is added as follows:
110.3.1.1 Reporting means shall be by email to the email inbox designated by the fire code official or through an electronic or web-based system approved by the fire code official.
Section 112.1.1 Board of appeals established.
Section 112.1.1 Board of appeals established is amended as follows:
112.1.1 Board of appeals established. A board of appeals is established in HMC 15.01.115.
Section 113.4 Violation Penalties.
Section 113.4 Violation penalties is amended as follows:
113.4 Violation penalties. Persons who shall violate a provision of this code or shall fail to comply with any of the requirements thereof or who shall erect, install, alter, repair or do work in violation of the approved construction documents or directive of the fire code official, or of a permit or certificate used under provisions of this code, shall be guilty of a misdemeanor. Each day that a violation continues after due notice has been served shall be deemed a separate offense.
The penalties referenced in the above paragraph are established in HMC 15.01.120.
Section 114.4 Failure to comply.
Section 114.4 Failure to comply is amended as follows:
114.4 Failure to comply. Any person who shall continue any work after having been served with a stop work order, except such work as that person is directed to perform to remove a violation or unsafe condition, shall be deemed guilty of a misdemeanor and shall be liable for a fine of not more than one thousand dollars ($1,000.00) or by imprisonment for not more than six (6) months, or by both such fine and imprisonment.
A new section 408 NFPA 3000 program is added as follows:
408 NFPA 3000 Program.
408.1 When required by the cities fire code official, police chief, director of emergency management or their designees' plans, reports and program details shall be submitted by the building owner to fire safety in accordance with NFPA 3000.
408.1.1 Submitted documents shall be marked "CONFIDENTIAL" by the applicant.
408.2 Plans, reports and program details shall be prepared in compliance with NFPA 3000.
408.3. Plans, reports and program details shall be prepared by facility/business owners and managers, facility managers, safety and security professionals, architects, fire and life safety engineers or other experts as necessary to comply with NFPA 3000.
Section 325 Periodic fire safety inspections.
A new section 325 periodic fire safety inspections is added as follows:
325 Periodic Fire Safety Inspections.
325.1 General. Periodic fire safety inspections shall be in accordance with this section.
Exceptions:
1. Where approved by the fire code official.
2. Buildings designed and constructed in accordance with the International Residential Code that are not regulated by NRS/NAC 477 or NRS/NAC 499.
325.2 Permits. Permits shall be required as set forth in this Section and Section 105.5.
325.3 Fire safety inspection frequency. Periodic fire safety inspections of new and existing buildings shall be performed on an annual, biennial, triennial or other frequency based on hazards, risks and staffing as determined by the City's fire safety division.
Section 503.1.1 Buildings and facilities.
Section 503.1.1 Buildings and facilities is amended as follows:
503.1.1 Buildings and facilities. Approved fire apparatus access roads shall be provided for every facility, building or portion of a building hereafter constructed or moved into or within the jurisdiction. The fire apparatus access road shall comply with the requirements of this section and shall extend to within 150 feet (45 720 mm) of all portions of the facility and all portions of the exterior walls of the first story of the building as measured by an approved route around the exterior of the building or facility.
Exceptions:
1. Where suitable mitigation is provided through an acceptable alternate method or code modification the fire code official is authorized to increase the dimension of 150 feet (45 720 mm).
2. Where approved by the fire code official, fire apparatus access roads shall be permitted to be exempted or modified for solar photovoltaic power generation facilities.
3. Where approved by the fire code official for development within the Hillside Overlay District - HMC Title 19, driveways more than 150 feet (45 720 mm) in length providing fire apparatus access to facilities or buildings constructed in accordance with the International Residential Code, shall be permitted to be modified in accordance with the Fire Safety division design criteria for hillside driveways.
Section 503.1.2 Additional access.
Section 503.1.2 Additional access is amended by adding a second paragraph and an exception as follows:
503.1.2 Additional access. The fire code official is authorized to require more than one fire apparatus access road based on the potential for impairment of a single road by vehicle congestion, condition of terrain, climatic conditions or other factors that could limit access.
Approved secondary access shall be provided for 20 or more dwelling units, road(s) with dead ends or with a single point of access more than 600 feet (182 880 mm), and for all commercial and industrial developments.
Exception: Hillside Overlay District - HMC Title 19.
Section 503.2.1.1 Group R, Division 3 Residential Subdivisions.
A new section 503.2.1.1 Group R, Division 3 Residential Subdivisions is added as follows:
503.2.1.1 Group R, Division 3 Residential Subdivisions. For Group R, Division 3 Residential Subdivisions, the minimum width of a fire apparatus access road is 36 feet (10 973 mm), measured face of curb to face of curb (i.e., 20 feet (6096 mm) driving lane with 8 feet (2438 mm) of parking on each side).
Exceptions:
1. For cluster housing developments, the last 150 feet (45 720 mm) may be reduced to 24 feet (7315 mm) in width (face of curb to face of curb) provided the homes are provided with an approved automatic sprinkler system and on-street parking is prohibited.
2. Hillside Overlay District - HMC Title 19.
Section 503.2.7 Grade.
Section 503.2.7 Grade is amended by adding an exception as follows:
503.2.7 Grade. The grade of the fire apparatus access road shall not exceed 12 percent 0.75 rad. The maximum cross-slope curve shall not exceed two (2) percent 0.13rad.
Exception: Hillside Overlay District - HMC Title 19.
Section 505.1.1 Building Addressing.
A new section 505.1.1 Building addressing is added as follows:
505.1.1 Building Addressing. Building addressing shall comply with HMC Title 19.
Section 506.1 Key Boxes. Where required.
Section 506.1 Key Boxes. Where required is amended as follows:
506.1 Key Boxes. Where required - Restricted access. Where access to or within a structure or area is restricted because of secured openings or where immediate access is necessary for lifesaving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. Buildings with fire sprinkler or fire alarm systems, or buildings not equipped with an exterior means of electrical disconnect, shall be provided with a key box. The key box shall be of an approved type listed in accordance with UL 1037 and shall contain keys to gain necessary access as required by the fire code official.
Recessed Knox Boxes are required except on individual dwelling units when approved by the Fire Chief or designee.
Key boxes shall be located as follows:
1. Adjacent to the fire command center, if applicable.
2. Adjacent to the exterior entrance door to each fire sprinkler riser room.
3. Adjacent to the main entry for buildings with fire alarm systems or sprinklered buildings without a riser room.
4. Adjacent to the exterior entrance door to the fire pump room.
5. Adjacent to the exterior entrance door to each electrical equipment room provided with a service disconnect.
6. At each elevator bank at the lobby nearest the lowest level of fire department access.
7. Other locations where required by the fire code official.
Key boxes shall be installed within 5 feet (1524 mm) to 6 ½ feet (1981 mm) to the top of the box above finished grade.
In new and existing buildings, keys for all lockable doors, exterior or interior, utilized to access fire alarm panel(s), main fire sprinkler control valve(s) and fire pump(s) shall be placed into the key box. Contents of elevator boxes shall be limited to fire service elevator keys. Whenever locks are changed, the building owner or tenant shall replace old keys inside the key box with new keys.
Section 507.2.1.1 Post Indicator Valves.
A new section 507.2.1.1 Post Indicator Valves is added as follows:
507.2.1.1 Post Indicator Valves. Post indicator valve(s) shall be a minimum of five (5) feet (1524 mm) from the building footing.
Section 507.4 Water supply test.
Section 507.4 Water supply test is amended as follows:
507.4 Water supply test - Permit required. A construction permit is required to use or operate fire hydrants or valves controlling fire hydrants.
Section 507.4.1 Fire flow or Fire Sprinkler Design water supply information.
A new section 507.4.1 Fire flow or Fire Sprinkler Design water supply information is added as follows:
507.4.1 Fire flow or Fire Sprinkler Design water supply information. Water supply information for fire flow or fire sprinkler system design is provided by the City of Henderson. Requests for the available flow at 20 psi shall be submitted on the designated form to the City. When available, hydraulically modeled water supply information provided by the City shall be used as the basis for fire flow or fire sprinkler design.
The City will process the request and provide the applicant with the available flow based upon hydraulic modeling. The information provided by the City shall be valid for a period of six (6) months from the date of issuance.
The available flow provided is predicted using a computer hydraulic model of the City's water distribution system which is based on the City's GIS data and approved civil utility plans. The results are from the model's maximum day demand scenario with no part of the water system upstream of the fire flow demand point having less than 20 psi residual pressure. The available flow information is typically provided at a water main and does not account for any pressure losses downstream from that location (for example: from the service or hydrant lateral, backflow devices, meters or any onsite piping to the fire sprinkler system).
The City makes no guarantee that the flow is presently available, nor does it guarantee that these flows will be available in the future due to continued growth which places additional demands for water on our distribution system. Availability of flow is also subject to periodic shutdowns and variations required by the operation of the City's distribution system.
It is the contractor's responsibility to obtain the approved civil utility plans to verify the appropriate backflow device(s) have been or will be installed on the system and to verify the existing on-site pressure prior to final system acceptance. The Contractor shall notify the City's fire safety staff immediately upon discovery of any major pressure discrepancies.
Section 507.4.2 Water supply field test.
A new section 507.4.2 Water supply field test is added as follows:
507.4.2 Water supply field test. Water supply field testing is strongly discouraged. Prior to applying for a permit, specific acceptance in writing by the fire code official is required. This acceptance shall be provided with the permit application. When approved, a manual water supply test may be permitted. A request for permit shall be made on a form provided by the City. Prior to performing the water supply field test, the Utilities Services Department must be notified at 702-267-5908. The fire code official shall be notified prior to the water supply test. The water supply field test shall be witnessed by the fire code official. The test shall be documented by the contractor. Water supply information obtained through this test shall be valid for a period of six (6) months.
Section 507.5.4.1 Debris Caps.
A new section 507.5.4.1 Debris caps is added as follows:
507.5.4.1 Debris caps. Debris caps are required to be installed beneath the road caps of all private fire systems and fire hydrant water valves to prevent the buildup of obstructions such as dirt, rocks, and plant matter.
Section 901.4.4.1 Non-Separated and Separated Occupancies.
A new Section 901.4.4.1 Non-Separated and Separated Occupancies is added as follows:
901.4.4.1 Non-Separated and Separated Occupancies. The total occupant load shall be applied using the predominant occupancy group within each fire area to determine the threshold so as not to exceed the limits established for requiring a fire protection system in accordance with this chapter.
Exception: When the total occupant load of an non-predominant occupancy group exceeds the threshold requiring a fire protection system the system shall be required throughout the fire area.
Section 903.3.1.3 NFPA 13D sprinkler systems.
A section 903.3.1.3 NFPA 13D sprinkler systems is amended as follows:
903.3.1.3 NFPA 13D sprinkler systems. Automatic sprinkler systems installed in group R-3; Group R-4, condition 1 shall be permitted to be installed throughout in accordance with NFPA 13D, 2022 edition including local amendments. Automatic sprinkler systems installed in one- and two-family dwellings; and townhouses shall be permitted to be installed throughout in accordance with NFPA 13D, 2022 edition including local amendments.
Section 903.3.8.5 Calculations.
Section 903.3.8.5 Calculations is amended as follows:
903.3.8.5 Calculations. Hydraulically calculated fire sprinkler systems shall be designed to ensure the available supply pressure is a minimum of ten (10) psi above the required system pressure. The fire code official is authorized to approve a lower safety margin for 903.3.1.3 systems. The safety margin shall be shown on the plans.
Sections 903.4.3.1 and 904.3.2.
Sections 903.4.3.1 and 904.3.2 are added as follows:
903.4.3.1 Interior audible notification appliances provided in R occupancies shall produce a 520 Hz low frequency signal.
903.4.3.2 In sprinklered one- and two-story self-storage occupancies audible and visual waterflow alarm notification appliances shall be provided throughout interior corridors in lieu of each tenant space. Additionally, one interior audible and visual notification appliance shall be provided near the main entrance or in a normally occupied location and any sleeping units. Sleeping unit audible notification appliances shall produce a 520 Hz low frequency signal.
Section 905.3 Required installations.
Section 905.3 Required installations is amended as follows:
905.3 Required installations. Standpipe systems shall be installed where required by Sections 905.3.1 through 905.3.9. Standpipe systems are allowed to be combined with automatic sprinkler systems.
Exception: Unless required by Section 905.3.9, standpipe systems are not required in Group R-3 occupancies.
The standpipe design shall be approved by the fire code official. Standpipes in buildings with fire pumps shall be automatic.
Exceptions:
1. When approved by the fire code official, standpipes in buildings not subject to freezing shall be wet and shall be permanently connected to a water supply.
2. When approved by the fire code official, standpipes in buildings subject to freezing shall be dry with supervised air or nitrogen and shall be permanently connected to a water supply.
3. When approved by the fire code official, standpipes in areas subject to freezing shall be permitted to be manual dry when equipped with both KNOX locking caps and/or KNOX plugs for fire department connections (FDC).
Section 905.3.9 Residential Manual Dry Standpipes.
A new section 905.3.9 Residential Manual Dry Standpipes is added as follows:
905.3.9 Residential Manual Dry Standpipes. An approved residential manual dry standpipe system shall be installed for Group R-3 occupancies and structures constructed in accordance with the International Residential Code with driveways over 150 feet (45 720 mm) long to mitigate the lack of fire access for structures constructed in the hillside overlay (Hillside Overlay District - HMC Title 19).
The quantity and locations of hose valve outlets shall be approved by the fire code official.
The permittee shall be responsible for providing all equipment, including pumper truck, necessary for acceptance testing.
Section 905.12 Signage.
Replace Section 905.12 as follows:
905.12 Signage. In addition to all signage required by NFPA Standard 14, an approved architectural floor plan with room numbers shall be provided adjacent to each standpipe hose valve outlet. The plan shall graphically show the area reachable by 100 feet (30 480 mm) of hose from the specific outlet and the location of adjacent outlets (if any) and the distance away.
Section 907.6.6.1 Expanded Monitoring.
A new section 907.6.6.1 Expanded Monitoring is added as follows:
907.6.6.1 Expanded Monitoring. Signals from two-way communication, emergency responder communication enhancement coverage systems, dedicated function elevator recall systems and other systems shall be transmitted to a supervising station as required by the Authority Having Jurisdiction.
Section 1009.8. Two-Way Communication.
Section 1009.8 Two-way communication is amended as follows:
1009.8 Two-way communication.
A two-way communication system complying with Sections 1009.8.1 and 1009.8.2 shall be provided at the landing serving each elevator or bank of elevators on each accessible floor and occupiable mezzanine that is one or more stories above or below the level of exit discharge.
Exceptions:
1. Two-way communication systems are not required at the landing serving each elevator or bank of elevators where the two-way communication system is provided within areas of refuge in accordance with Section 1009.6.5.
2. Two-way communication systems are not required on floors provided with ramps conforming to the provisions of Section 1012.
3. Two-way communication systems are not required at the landings serving only service elevators that are not designated as part of the accessible means of egress or serve as part of the required accessible route into a facility.
4. Two-way communication systems are not required at the landings serving only freight elevators.
5. Two-way communication systems are not required at the landing serving a private residence elevator.
6. Two-way communication systems are not required in Group I-2 or I-3 facilities. 905.3.9 Residential Manual Dry Standpipes.
Sections 4106.4.3.1.1 and 4106.4.3.2.1.
Sections 4106.4.3.1.1 and 4106.4.3.2.1 are added as follows:
4106.4.3.1.1 LP-gas alarms. A listed LP-gas alarm shall be installed within the vehicle in the vicinity of LP-gas system components, in accordance with the manufacturer's instructions.
4106.4.3.2.1 Methane alarms. A listed methane gas alarm shall be installed within the vehicle in accordance with manufacturer's instructions.
Section 5601.2.2 Sale and retail display.
Section 5601.2.2 Sale and retail display is amended as follows:
5601.2.2 Sale and retail display. All sales and retail displays of fireworks and explosives are prohibited.
Exceptions:
1. Consumer fireworks 1.4G (safe and sane) offered for sale at portable retail fireworks stands that are in accordance with the current Fire Prevention Association of Nevada (FPAN) Guidelines for Fireworks. Stands or booths constructed of non-combustible materials providing an acceptable equivalent level of safety to the prescriptive FPAN guidelines may be approved by the fire code official.
2. Novelties complying with NFPA 1124 section C.3.2 & C.3.3 including: party popper; snapper; toy smoke devices; snakes, glow worms; wire sparklers, dipped sticks; and toy caps.
Section 5607.1.1 Blasting Regulations.
A new section 5607.1.1 Blasting Regulations is added as follows:
5607.1.1 Blasting Regulations. Blasting for new development such as subdivisions and commercial uses is regulated in HMC 15.33 entitled "Blasting Regulations." The fire code official is authorized to exercise discretionary authority in utilizing any of the requirements from HMC 15.33 when evaluating other requests for blasting.
Section 5608.1.1 Additional Requirements for Outside Fireworks Displays.
A new section 5608.1.1 Additional Requirements for Outside Fireworks Displays is added as follows:
5608.1.1 Additional Requirements for Outside Fireworks Displays. The following conditions apply to fireworks displays:
1. Fireworks displays shall not exceed twelve (12) times per calendar year at any one location.
2. Fireworks displays shall only occur on Friday and Saturday nights, with the sole exception of New Year's Eve and July 4 th . On New Year's Eve and July 4 th , fireworks must conclude by 12:30 a.m. (including misfires). On any other occasion, fireworks must conclude by 10:30 p.m. (including misfires).
3. Notification (a vicinity map depicting the subject site, the proposed date(s), time(s) and contact information) shall be provided by the applicant to the mailing addresses on the list provided by staff via first-class mail postmarked not more than thirty (30) days and not less than ten (10) days in advance of the fireworks display. Notification shall also be provided to City of Henderson fire safety staff and community police staff at least 10 calendar days prior to the fireworks display date. A copy of the notification plan shall be included with the permit application.
4. Fireworks displays will be cancelled or postponed when the wind velocity is more than 15 mph for aerial displays and when the wind velocity is more than 20 mph for ground displays. All advertising for the fireworks display shall contain a disclaimer advising that "The fireworks displays will be cancelled or postponed when the wind velocity is in excess of 15 mph."
5. Other firework displays for special events may be considered on an individual basis.
6. Notification to Henderson Fire Department Dispatch shall be made the day of the fireworks display. Notification by the permit holder shall be provided no later than four (4) hours prior to the fireworks display by calling dispatch at 702-267-4913.
5704.2.9.6.1 Locations where above-ground tanks are prohibited.
Section 5704.2.9.6.1 Locations where above-ground tanks are prohibited is amended as follows:
5704.2.9.6.1. Locations where above-ground tanks are prohibited. Storage of Class I and II liquids in above-ground tanks in control areas exceeding an aggregate capacity of 500 gallons (1893 L) outside of buildings is prohibited for the protection of heavily populated or congested areas.
Exception: When approved by the planning or zoning authority and when approved by the fire code official. Note: The fire code official may require UL2085 listed protected tanks or other appropriate mitigation measures.
Chapter 80
Revise Chapter 80 reference NFPA standards as follows:
NFPA
…
54-24 National Fuel Gas Code.
…
140-24 Motion Picture and Television Production Studio Soundstages, Approved Production Facilities, and Production Locations.
…
3000-24 Standard for an Active Shooter/Hostile Event Response (ASHER) Program.
…
(Note: The list before and after the revisions and insertions are unchanged.)
Section B103.1.1: Utility water storage tank sites.
A new section B103.1.1: Utility water storage tank sites is added as follows:
B103.1.1: Utility water storage tank sites. The fire code official is authorized to reduce or eliminate the fire-flow requirements for utility storage sites where the development of fire-flow requirements is impractical.
Table B105.1(1)
Table B105.1(1) is revised and replaced as follows:
TABLE B105.1(1)
REQUIRED FIRE FLOW FOR ONE- AND TWO-FAMILY DWELLINGS, GROUP R-3 AND R-4 BUILDINGS AND TOWNHOUSES
FIRE FLOW CALCULATION AREA (square feet) | MINIMUM FIRE FLOW (gallons per minute) | FLOW DURATION (hours)
0-3,600 | 1,500 | 1
3,601 and greater | ½ Value in Table B105.1(2) but not less than 1,500 | Duration in Table B105.1(2) at the required fire-flow rate
For SI: 1 square foot = 0.0929 m 2 , 1 gallon per minute = 3.785 L/m
NFPA 13
Section 16.4.1.5.1 is revised as follows:
16.4.1.5.1 Design Temperature and Duration. The minimum criteria for an engineered solution in calculating heat loss for the requirement to maintain 40ºF (4.4ºC) shall be 0º F (-17.8ºC) for 8 hours. The initial starting temperature of the water shall be no greater than 50ºF (10ºC).
To maintain 40º F (4°C), the temperature analysis must use a starting temperature of 50º F (10°C) and use an outside temperature of 0º F (-17.8°C) for a period of 8 hours. To maintain 100º F (37.8°C), the temperature analysis must use a starting temperature of 90º F (32.2°C) and use an outside temperature of 120º F (48.9°C) for a period of 8 hours.
NFPA 13D
A new section 6.5.4 is added as follows:
6.5.4 A supply line from the sprinkler system loop shall feed into the toilet in the master bathroom. In multi-level dwellings, if the lowest protected level is below the elevation of the water supply, a supply line shall also feed into a toilet at that level.
Section 8.4 is amended as follows:
8.4 Protection Matrix for Group R Division 3 Occupancies and Buildings Built Under the IRC.
8.4.1 General. When a sprinkler system is being upgraded or installed to mitigate the minimum Fire Code requirements for fire flow, number of fire hydrants, or fire department access, the design requirements in Table 8.4.1 shall be applied.
Table 8.4.1 Protection Matrix for Group R Division 3 Occupancies and Buildings Built Under the IRC 4
Fire Lane Distance per IFC 503.1.1 | Building Area SIZE RANGE 5 | Mitigation Residential SYSTEM TYPE 1,3 | MINIMUM WATER METER SIZE 6 | SPRINKLERS REQUIRED IN AREAS SUBJECT TO FREEZING
≤350 FT | ≤10,000 SQ. FT. | Enhanced NFPA 13D 1,2 2-head calculation 1,2 | 3/4"/1" 7 | No
≤350 FT | >10,000 SQ. FT. | Enhanced NFPA 13D 4-head calculation 1,2,8 | 1-1/2" 7 | No
>350 FT | Any Size | Enhanced NFPA 13D 4-head calculation 1,2,8 | 1-1/2" 7 | No
1. This mitigation constitutes a building "protected with an approved fire sprinkler system" per the IFC.
2. Domestic demand of 5 gpm is required to be added to the sprinkler demand in the hydraulic calculations.
3. Free-standing detached buildings with habitable space (as defined in the IRC) shall be protected by a minimum Enhanced NFPA 13D system with a 2-head calculation.
4. Excluding Group Care Homes with two or less persons being cared for per NRS 449.1865.
5. Building area is defined as the areas under roof except for porches, patios, balconies, carports, and porte cocheres.
6. Water meters used for residential sprinkler systems shall be residential fire service meters (RFM) or other meters approved by the water purveyor.
7. Existing homes with ¾" water meters may be allowed to install a ¾" RFM meter subject to approval. Minimum 1" water meters shall be installed when a 2-head calculation is permitted. Minimum 1-1/2" water meters shall be installed when a 4-head calculation is required.
8. Enhanced 13D 4-head calculation design requires the hydraulic design area to include all sprinklers within a compartment, up to a maximum of four sprinklers.
8.4.2 Where required. When Table 8.4.1 requires an Enhanced 13D design, sprinklers shall be installed throughout the structure except where omissions are permitted by the following:
1. Unheated attic spaces.
2. Floor/ceiling spaces.
3. Concealed combustible spaces with no access for storage or living purposes.
4. Exterior overhangs, porches, and carports.
5. Showers, saunas, steam rooms or other areas that would necessitate the installation of corrosion proof heads.
6. Unconditioned spaces such as storage rooms or exterior accessible spaces that are subject to freezing.
NFPA 14
A new section 10.2.5.1 is added as follows:
10.2.5.1 The contractor is responsible for pressure testing and verifying the integrity and capacity of the drain line.
A new section 12.6.2.2 is added as follows:
12.6.2.2 The installing contractor is responsible for providing all equipment for the acceptance testing of a manual standpipe acceptable to the authority having jurisdiction.
NFPA 72
The 2022 edition of NFPA 72 is adopted except Chapter 29 as follows:
The 2022 edition of NFPA 72 is adopted except Chapter 29 is deleted. (Note: For requirements like Chapter 29, refer to the requirements found in the International Residential Code HMC 15.09.)
Section 12.4 is revised as follows:
12.4* Pathway Survivability. All pathways shall comply with 12.2.3 and NFPA 70.
Section 17.4.7.3 is revised as follows:
17.4.7.3 Detectors installed in concealed locations where the specific detector alarm or supervisory signal is indicated at the control unit (and on the drawings with its specific location and functions) shall be required to be provided with remote alarm indicators unless approved by the Authority Having Jurisdiction.
Section 24.10.9.1 is added as follows:
24.10.9.1 Elevator lobby call stations shall be within 10-feet of the elevator door or bank of elevators served unless approved by the Authority Having Jurisdiction.
(Ord. No. 4138, § 5, 12-16-2025; Ord. No. 4090, § 7, 7-15-2025; Ord. No. 3909, § 6, 9-13-2022; Ord. No. 3510, § 2, 8-7-2018)