37.20 - 903.4.2 Alarms.

Section 903.4.2 entitled "Alarms" is hereby repealed and replaced with a new Section 903.4.2 as follows: Section 903.4.2 Alarms. Approved audible visual devices shall be connected to every automatic sprinkler system. Such sprinkler water-flow alarm devices shall be activated by water flow equivalent to the flow of a single sprinkler of the smallest orifice size installed in the system. An approved audible visual sprinkler flow alarm device shall be provided on the exterior of the building in an approved location, typically above the Fire Department Connection, tied only to the sprinkler water flow alarm and shall not be activated by other fire alarm system devices, such as a manual pull or a smoke detector. Approved audible visual alarm(s) to alert the occupants shall be installed on each level or in each suite of the interior of the building in normally occupied location(s) as required by the fire code official. Where a fire alarm system is installed, actuation of the automatic sprinkler system shall actuate the building fire alarm system. (039-24)