§ 14.28.310 — Table B105.2 of Appendix B of the 2025 California Fire Code titled "REQUIRED FIRE-FLOW FOR BUILDINGS OTHER THAN ONE- AND TWO-FAMILY DWELLINGS, GROUP R-3 AND R-4 BUILDINGS AND TOWNHOUSES" is amended as follows
Pasadena Municipal Code, California (Supp. No. 79: codified through Ordinance No. 7469, enacted May 18, 2026) · Pasadena Municipal Code § 14.28.310
Corpus is an independent public-information project, not the official City of Pasadena website. Stable reference: corpuslaw.us/code/9a155692-28de-43ee-b798-a1015dcfd8f3
14.28.310 - Table B105.2 of Appendix B of the 2025 California Fire Code titled "REQUIRED FIRE-FLOW FOR BUILDINGS OTHER THAN ONE- AND TWO-FAMILY DWELLINGS, GROUP R-3 AND R-4 BUILDINGS AND TOWNHOUSES" is amended as follows.
TABLE B105.2 REQUIRED FIRE-FLOW FOR BUILDINGS OTHER THAN ONE- AND TWO-FAMILY DWELLINGS, GROUP R-3 AND R-4 BUILDINGS AND TOWNHOUSES AUTOMATIC SPRINKLER SYSTEM (Design Standard) | MINIMUM FIRE FLOW (gallons per minute) | FLOW DURATION (hours) No automatic sprinkler system | Value in Table B105.1(2) | Duration in Table B105.1(2) Section 903.3.1.1 of the California Fire Code | 50% of the value in Table B105.1(2) a | Duration in Table B105.1(2) at the reduced required fire flow rate Section 903.3.1.2 of the California Fire Code | 50% of the value in Table B105.1(2) b | Duration in Table B105.1(2) at the reduced required fire flow rate For SI: 1 gallon per minute = 3.785 L/m. a. The reduced fire-flow shall be not less than 1,000 gallons per minute. b. The reduced fire-flow shall be not less than 1,500 gallons per minute.
(Ord. No. 7461, § 6, 11-10-2025)