R326 — HABITABLE ATTICS
The Philadelphia Code (2026 Code: The Philadelphia Code and Home Rule Charter current through October 8, 2026) · Philadelphia Code Subcode R, § R326
Corpus is an independent public-information project, not the official City of Philadelphia website. Stable reference: corpuslaw.us/code/9a32322e-43a4-4179-8423-c4becd4426ca
SECTION R326 HABITABLE ATTICS
* * * [Pursuant to the UCC, delete Section R326.3 and replace as follows:] R-R326.3 Story above grade plane. A habitable attic shall be considered a story above grade plane. Exceptions: A habitable attic shall not be considered to be a story above grade plane provided that the habitable attic meets all the following: 1. The aggregate area of the habitable attic is either of the following: 1.1. Not greater than one-third of the floor area of the story below. 1.2. Not greater than one-half of the floor area of the story below where the habitable attic is located within a dwelling unit equipped with a fire sprinkler system in accordance with Section P2904. 2. The occupiable space is enclosed by the roof assembly above, knee walls, if applicable, on the sides and the floor-ceiling assembly below. * * *