Austin City Code § 15-13-31 WATER QUALITY REQUIREMENTS.
§ 15-13-31 - WATER QUALITY REQUIREMENTS.
(A) A project applicant shall design and construct the OWRS to achieve the water quality requirements in this article.
(B) A permittee shall maintain and operate an OWRS to achieve the water quality requirements in this article.
(C) To meet the pathogenic microorganism control requirements for enteric virus, parasitic protozoa, and bacteria, an OWRS must include treatment processes that achieve LRTs as shown in Table 1.
Table 1: Pathogen Log Reduction Targets
Alternate Water Source | Enteric Virus | Parasitic Protozoa | Bacteria
Condensate Water | — | — | —
Rainwater | — | 1.5 | —
Stormwater | 3.5 | 3.5 | 3.0
Stormwater Outdoor Use Only | 3.0 | 2.5 | 2.0
Foundation Drain Water | 3.5 | 3.5 | 3.0
Foundation Drain Water Outdoor Use Only | 3.0 | 2.5 | 2.0
Graywater | 6.0 | 4.5 | 3.5
Graywater Outdoor Use Only | 5.5 | 4.5 | 3.5
(D) When operating pursuant to a conditional permit, an OWRS must meet the total coliform limits in Table 2, as well as the LRTs for bacteria.
(E) If the OWRS does not achieve the LRTs for bacteria as required in Subsection (D), the director may not issue an operating permit until the OWRS meets total coliform sampling requirements.
Table 2: Water Quality Limits for Total Coliform
Sample Type | Water Quality Limit | Required U.S. EPA Standard Method
7-sample median | 2.2 MPN/100 mL | SM9223B
30-day maximum | 23 MPN/100 mL
Absolute maximum | 240 MPN/100 mL
(F) For a use with the potential for human contact, the OWRS must disinfect effluent with chlorine, ozone, ultraviolet radiation, or other approved agent.
(G) For an indoor use, the OWRS must maintain a minimum chlorine residual of 0.5 mg/L at or after the effluent enters the plumbing of the distribution system.
Source: Ord. No. 20201210-006, Pt. 2, 12-21-20; Ord. No. 20240307-003, Pt. 9, 4-1-24.