MC 406 — Ventilation of Uninhabited Spaces
New York City Administrative Code (current through L.L. 2026/147, enacted September 12, 2026, and amendments effective through October 10, 2026) · NYC Mechanical Code § MC 406
Corpus is an independent public-information project, not the official City of New York website. Stable reference: corpuslaw.us/code/9bf265ef-d2c7-4c40-865f-9327fe2b1215
Section MC 406: Ventilation of Uninhabited Spaces
406.1 General. Uninhabited spaces, such as crawl spaces and attics, shall be provided with natural ventilation openings as required by the New York City Building Code or shall be provided with a mechanical exhaust and supply air system. The mechanical exhaust rate shall be not less than 0.02 cfm per square foot (0.00001 m3/s • m2) of horizontal area and shall be automatically controlled to operate when the relative humidity in the space served exceeds 60 percent. 406.1.1 Methane and radon venting. The design and materials used in the installation of the methane and radon vent systems shall be approved by the commissioner and shall comply with all applicable rules of the Fire Department.
Ask a question about New York law
Corpus searches the New York sections it holds and shows the ones that match, with their citations. Free, no sign-in.
