§ 48-585 — Gas or liquid storage tanks
Wilmington City Code, Delaware (Supp. No. 72: codified through Ordinance No. 25-073, enacted December 11, 2025) · Wilmington City Code § 48-585
Corpus is an independent public-information project, not the official City of Wilmington website. Stable reference: corpuslaw.us/code/9c3da577-477d-4bd0-9f95-117b29011edf
Sec. 48-585. - Gas or liquid storage tanks.
(a) Underground tanks in special flood hazard areas shall be anchored to prevent flotation, collapse or lateral movement resulting from hydrostatic loads, including the effects of buoyancy, during conditions of the base flood. (b) Above-ground tanks in special flood hazard areas shall be elevated and anchored to or above the base flood elevation plus 18 inches or shall be anchored at- grade and designed and constructed to prevent flotation, collapse, or lateral movement resulting from hydrodynamic and hydrostatic loads, including the effects of buoyancy, during conditions of the base flood. (c) In special flood hazard areas, tank inlets, fill openings, outlets and vents shall be: (1) At or above the base flood elevation or fitted with covers designed to prevent the inflow of floodwater or outflow of the contents of the tanks during conditions of the base flood. (2) Anchored to prevent lateral movement resulting from hydrodynamic and hydrostatic loads, including the effects of buoyancy, during conditions of the base flood.
(Ord. No. 14-053(sub 1), § 2, 12-18-14)