For AI agents: read the machine-readable documentation index at /llms.txt or the single-file full reference at /llms-full.txt.

§ 49-509 — Location of soil, waste, vent or water pipe in proximity to electric panels

Omaha Municipal Code (Supp. No. 100, Update 2: codified through Ordinance No. 44760, enacted August 4, 2026) · Omaha Municipal Code § 49-509

Corpus is an independent public-information project, not the official City of Omaha website. Stable reference: corpuslaw.us/code/9dcdaec1-dcbc-4650-9313-fa3d5f5a8386

Sec. 49-509. - Location of soil, waste, vent or water pipe in proximity to electric panels.

No soil, waste, vent or water piping shall be installed in the dedicated or working space for electrical panels. (a) Dedicated space shall be defined as the space required for the width and depth of the panel and extending from the floor to a height of six feet above the panel. (See Figure 49-509(a).) (b) Working space shall be defined as follows: (1) The width of the electrical panel or 30 inches whichever is greater. (2) The height of the electrical panel from the floor to the top of the panel or a minimum of six feet six inches whichever is greater. (3) A clear space in front of the panel of four feet. (See Figure 49-509(b).)

(Ord. No. 40524, § 1, 10-20-15)

Ask a question about Omaha law

Corpus searches the Omaha sections it holds and shows the ones that match, with their citations. Free, no sign-in.