Sec. 49-509. - Location of soil, waste, vent or water pipe in proximity to electric panels.
No soil, waste, vent or water piping shall be installed in the dedicated or working space for electrical panels. (a) Dedicated space shall be defined as the space required for the width and depth of the panel and extending from the floor to a height of six feet above the panel. (See Figure 49-509(a).) (b) Working space shall be defined as follows: (1) The width of the electrical panel or 30 inches whichever is greater. (2) The height of the electrical panel from the floor to the top of the panel or a minimum of six feet six inches whichever is greater. (3) A clear space in front of the panel of four feet. (See Figure 49-509(b).)
(Ord. No. 40524, § 1, 10-20-15)