17.12.1020 - Amendment of Chapter 80 - NFPA 14 - 24 - Standard for the installation of standpipe and hose systems.
The following sections of NFPA 14 - 24 edition, Standard for the Installation of Standpipe and Hose Systems, are amended to read as follows: 9.6.10 Non-Combined Standpipe Systems. The water supply shall be made prior to the sprinkler system water flow indicator. The standpipe priming connection shall be equipped with a monitored control valve, check valve, flow switch, and include a pipe restriction of three-eighth inch (3/8") orifice or less.
(Ord. 31258.)