STANDARD SPRINKLER SYSTEMS (15-16-170 et seq.)
Municipal Code of Chicago tit. 15, ch. 15-16, art. II, pt. 1
in effectMunicipal Code of Chicago § 15-16-180 Reserved. Editor's note – Coun. J. 4-10-19, p. 100029, Art. XXII, § 37, repealed § 15-16-180, which pertained to other definitions.
Municipal Code of Chicago § 15-16-190 Permit and fees.
15-16-190 Permit and fees.
Before the installation or alteration of a sprinkler system required by the provisions of this Code, a plan, setting forth all essential details of the sprinkler system, shall be submitted to the Fire Commissioner. The plans submitted shall include hydraulic calculations when calculated and the type of sprinklers to be used. Upon finding that the plan conforms to the requirements of the Code and after payment of the sprinkler permit fee hereinafter specified, said plan shall be approved by the Fire Commissioner.
The fees charged in connection with a sprinkler system shall be as follows:
If the plan does not conform to the requirements of the Code and a revised plan is submitted, the fee for each revised plan submission shall be $200.00. For the approval of the sprinkler plan and the initial inspection of a sprinkler system required by the provisions of this Code, a fee of $731.00 shall be charged for the first 100 sprinkler heads or less and an additional $500.00 shall be charged for each additional 100 sprinkler heads or fraction thereof. For the test of a fire pump used in connection with a sprinkler system, a fee of $31.50 for each 50 gallons pumping capacity per minute shall be charged with a minimum fee of $315.00. These fees shall not be required for any building used solely as a school operated by the Chicago Board of Education. Where a pump serves both a standpipe and a sprinkler system, only one pump fee shall be charged.
(Prior code § 91-3; Amend Coun. J. 12-15-92, p. 27387; Amend Coun. J. 10-30-96, p. 31216, § 1; Amend Coun, J, 11-16-11, p. 13798, Art. VIII, § 3; Amend Coun. J. 5-18-16, p. 24131, § 117; Amend Coun. J. 11-14-18, p. 90376, Art. V, § 4; Amend Coun. J. 12-19-25, p. 38125, Art. XXIII, § 16)
Municipal Code of Chicago § 15-16-200 Installation certification.
15-16-200 Installation certification.
After completing a sprinkler installation, the contractor shall submit to the Fire Commissioner a written certification that the system has been installed in accordance with the plans approved by the Fire Commissioner and tested in accordance with the provisions of Section 15-16-260. The form of such certification shall be as required in the applicable sprinkler installation standard listed in Chapter 14B-9.
(Prior code § 91-4; Amend Coun. J. 10-30-96, p. 31216, § 1; Amend Coun. J. 5-18-16, p. 24131, § 118; Amend Coun. J. 9-6-17, p. 55278, Art. VII, § 20; Amend Coun. J. 10-7-20, p. 21791, Art. VI, § 9)
Municipal Code of Chicago § 15-16-210 Inspections.
15-16-210 Inspections.
Every standard sprinkler system now existent or which may hereafter be installed shall be inspected annually by an independent contractor licensed under the Illinois Fire Sprinkler Contractor Licensing Act and such inspections may be overseen by or in the presence of the Fire Commissioner. Whenever such annual inspection shows the standard sprinkler system to be in good working order and in compliance with this Code, the Fire Commissioner shall issue a certificate to that effect, and for each such inspection and certificate, a fee of $300.00 shall be charged. Buildings with multiple sprinkler system zones shall rotate the zone to be tested annually, ensuring that the sprinkler system is operating properly. If a doubt exists regarding the capability of any component of a standard sprinkler system, the Fire Commissioner may order any test outlined in NFPA Standard 25, Standards for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems, to determine the capability of that component.
(Prior code § 91-5; Amend Coun. J. 12-15-92, p. 27387; Amend Coun. J. 10-30-96, p. 31216, § 1; Amend Coun. J. 5-18-16, p. 24131, § 119; Amend Coun. J. 10-7-20, p. 21791, Art. VI, § 10)
Municipal Code of Chicago § 15-16-220 Notice of defective conditions.
15-16-220 Notice of defective conditions.
If an inspection or test discloses any condition such as defective parts, frozen tanks, closed valves or obstructed sprinklers, which would handicap the operation of the building's sprinkler equipment, the Fire Commissioner shall immediately be notified. Notice shall then immediately be sent by the Fire Commissioner to the building's owner or owners or to the owner's agent or to the person in control of the building containing such sprinkler systems, to remove or correct the defective condition as set forth in said notice within such time as may be specified by the Fire Commissioner in the notice.
(Prior code § 91-6; Amend Coun. J. 10-30-96, p. 31216, § 1; Amend Coun. J. 5-18-16, p. 24131, § 120; Amend Coun. J. 10-7-20, p. 21791, Art. VI, § 11)
Municipal Code of Chicago § 15-16-230 Reserved. Editor's note – Coun. J. 4-10-19, p. 100029, Art. XXII, § 37, repealed § 15-16-230, which pertained to requirements for light hazard occupancies.
Municipal Code of Chicago § 15-16-240 Reserved. Editor's note – Coun. J. 4-10-19, p. 100029, Art. XXII, § 37, repealed § 15-16-240, which pertained to requirements for extra hazardous occupancies.
Municipal Code of Chicago § 15-16-250 Reserved. Editor's note – Coun. J. 4-10-19, p. 100029, Art. XXII, § 37, repealed § 15-16-250, which pertained to requirements for special systems.
Municipal Code of Chicago § 15-16-260 System tests.
15-16-260 System tests.
Upon completion of the installation of an automatic sprinkler system, an acceptance test shall be performed by the installing contractor.
All portions of each system shall be tested for two hours at a cold water pressure of not less than 200 pounds per square inch if the normal pressure in the system does not exceed 150 pounds per square inch or at a pressure of not less than 50 pounds per square inch above the normal pressure, if such normal pressure is more than 150 pounds per square inch. Interior piping shall show no leaks. Underground piping shall show a leakage rate not greater than two quarts per hour per 100 gaskets or joints irrespective of pipe diameter.
Dry pipe systems, if tested during seasons of the year which will not permit the use of water, may be tested with air under a pressure of not less than 50 pounds per square inch.
Brine or other corrosive or toxic chemicals shall not be used for testing.
If the dry pipe valves are of the differential type, they shall be pumped up and allowed to stand 24 hours and shall show not more than one and one-half pounds per square inch loss of pressure during that period of time. A working test of each dry pipe valve shall be made before acceptance. When dry pipe valves are subjected to hydrostatic test pressures, the clapper of a differential type valve shall be held off its seat to prevent damaging the valve.
Fire pumps, air compressors, filling pumps and other equipment shall be tested for a period of two hours or such portion of this time as is necessary to show they are of the required capacities. Initial tests of fire pumps shall be made in the presence of a representative of the Fire Commissioner and the installing contractor.
Every fire pump shall provide its rated capacity at its rated pressure. Fire pumps rated at less than 1,500 GPM shall furnish at least 150 percent of the rated capacity at 65 percent of its rated pressure. The pressure at the intake side of the pump shall not be less than five pounds per square inch under any flow rate.
Fire pumps shall be tested annually by an independent contractor licensed under the Illinois Fire Sprinkler Contractor Licensing Act. Such inspections shall be scheduled with, and may be overseen by or in the presence of, the Fire Commissioner.
(Prior code § 91-10; Amend Coun. J. 10-30-96, p. 31216, § 1; Amend Coun. J. 5-18-16, p. 24131, § 121; Amend Coun. J. 10-7-20, p. 21791, Art. VI, § 12)
Municipal Code of Chicago § 15-16-270 Reserved. Editor's note – Coun. J. 4-10-19, p. 100029, Art. XXII, § 37, repealed § 15-16-270, which pertained to water supply requirements.
Municipal Code of Chicago § 15-16-280 Reserved. Editor's note – Coun. J. 4-10-19, p. 100029, Art. XXII, § 37, repealed § 15-16-280, which pertained to use of pressure tank for other services.
Municipal Code of Chicago § 15-16-290 Reserved. Editor's note – Coun. J. 4-10-19, p. 100029, Art. XXII, § 37, repealed § 15-16-290, which pertained to gravity tanks.
Municipal Code of Chicago § 15-16-300 Reserved. Editor's note – Coun. J. 4-10-19, p. 100029, Art. XXII, § 37, repealed § 15-16-300, which pertained to pressure tanks.
Municipal Code of Chicago § 15-16-310 Reserved. Editor's note – Coun. J. 4-10-19, p. 100029, Art. XXII, § 37, repealed § 15-16-310, which pertained to fire pumps.
Municipal Code of Chicago § 15-16-311 Reserved. Editor's note – Coun. J. 4-10-19, p. 100029, Art. XXII, § 37, repealed § 15-16-311, which pertained to test manifold.
Municipal Code of Chicago § 15-16-320 Reserved. Editor's note – Coun. J. 4-10-19, p. 100029, Art. XXII, § 37, repealed § 15-16-320, which pertained to supply to tanks.
Municipal Code of Chicago § 15-16-330 Reserved. Editor's note – Coun. J. 4-10-19, p. 100029, Art. XXII, § 37, repealed § 15-16-330, which pertained to filling pipe.
Municipal Code of Chicago § 15-16-340 Reserved. Editor's note – Coun. J. 4-10-19, p. 100029, Art. XXII, § 37, repealed § 15-16-340, which pertained to small equipment.
Municipal Code of Chicago § 15-16-350 Reserved. Editor's note – Coun. J. 4-10-19, p. 100029, Art. XXII, § 37, repealed § 15-16-350, which pertained to location and arrangement of sprinklers.
Municipal Code of Chicago § 15-16-351 Temporary display booths.
15-16-351 Temporary display booths.
Sprinklers may be omitted from structures erected and used as temporary display booths situated within any assembly occupancy having at least 500,000 square feet devoted exclusively for use as an exhibition area. Temporary display booths shall comply with the following requirements:
(1) Height and Area:
a. Total height of a temporary display booth shall not exceed 30 feet above floor level and total stories shall not exceed two.
b. Temporary display booths of two stories shall be open and uncovered at the second story.
c. Temporary display booths shall not exceed 5,000 square feet in area.
(2) Construction:
a. All wood materials used in construction of a temporary display booth shall comply with NFPA 703 (1992 ed. or later), Chapter 2, Standard for Fire Retardant Impregnated Wood.
b. All non-wood materials used in the construction of a temporary display booth shall be non-combustible in accordance with Chapter 14B-7.
(3) Fire Prevention and Detection:
a. Scenery and decorations used within temporary display booths shall comply with combustibility standards at Sections 15-4-580 through 15-4-620 of this code.
b. Temporary display booths shall be equipped with:
i. One battery-operated smoke alarm for each 1,000 square feet of enclosed area; and
ii. One fire extinguisher for each 1,000 square feet of enclosed area.
c. Temporary display booth diagrams required to be filed with the fire commissioner under Section 15-4-690 shall identify each temporary display booth having greater than one story.
d. Temporary display booths shall, in addition to the number and location requirements for exhibition area fire guards in Section 15-4-640 of this code, be patrolled by one fire guard for each booth in excess of one story in height at all times during which the show or exhibition is closed for business.
(Added Coun. J. 9-15-93, p. 37767; Amend Coun. J. 10-30-96, p. 31216, § 1; Amend Coun. J. 5-18-16, p. 24131, § 122; Amend Coun. J. 9-6-17, p. 55278, Art. VI, § 36; Amend Coun. J. 10-7-20, p. 21791, Art. VI, § 13)
Municipal Code of Chicago § 15-16-360 Reserved. Editor's note – Coun. J. 4-10-19, p. 100029, Art. XXII, § 37, repealed § 15-16-360, which pertained to sprinklers.
Municipal Code of Chicago § 15-16-370 Reserved. Editor's note – Coun. J. 4-10-19, p. 100029, Art. XXII, § 37, repealed § 15-16-370, which pertained to sprinkler piping.
Municipal Code of Chicago § 15-16-380 Reserved. Editor's note – Coun. J. 4-10-19, p. 100029, Art. XXII, § 37, repealed § 15-16-380, which pertained to piping supports.
Municipal Code of Chicago § 15-16-390 Reserved. Editor's note – Coun. J. 4-10-19, p. 100029, Art. XXII, § 37, repealed § 15-16-390, which pertained to siamese connections.
Municipal Code of Chicago § 15-16-400 Reserved. Editor's note – Coun. J. 4-10-19, p. 100029, Art. XXII, § 37, repealed § 15-16-400, which pertained to valves.
Municipal Code of Chicago § 15-16-410 Reserved. Editor's note – Coun. J. 4-10-19, p. 100029, Art. XXII, § 37, repealed § 15-16-410, which pertained to system drainage.
Municipal Code of Chicago § 15-16-420 Reserved. Editor's note – Coun. J. 4-10-19, p. 100029, Art. XXII, § 37, repealed § 15-16-420, which pertained to hand hose connections.
Municipal Code of Chicago § 15-16-430 Reserved. Editor's note – Coun. J. 4-10-19, p. 100029, Art. XXII, § 37, repealed § 15-16-430, which pertained to protection against freezing.
Municipal Code of Chicago § 15-16-440 Reserved. Editor's note – Coun. J. 4-10-19, p. 100029, Art. XXII, § 37, repealed § 15-16-440, which pertained to protection against corrosion.
Municipal Code of Chicago § 15-16-450 Reserved. Editor's note – Coun. J. 4-10-19, p. 100029, Art. XXII, § 37, repealed § 15-16-450, which pertained to test pipes.
Municipal Code of Chicago § 15-16-451 Reserved. Editor's note – Coun. J. 4-10-19, p. 100029, Art. XXII, § 37, repealed § 15-16-451, which pertained to test pipes for high-rise buildings.
Municipal Code of Chicago § 15-16-460 Reserved. Editor's note – Coun. J. 4-10-19, p. 100029, Art. XXII, § 37, repealed § 15-16-460, which pertained to dry pipe systems.
Municipal Code of Chicago § 15-16-470 Reserved. Editor's note – Coun. J. 4-10-19, p. 100029, Art. XXII, § 37, repealed § 15-16-470, which pertained to dry pipe system capacity limits.
Municipal Code of Chicago § 15-16-480 Reserved. Editor's note – Coun. J. 4-10-19, p. 100029, Art. XXII, § 37, repealed § 15-16-480, which pertained to quick opening devices.
Municipal Code of Chicago § 15-16-490 Reserved. Editor's note – Coun. J. 4-10-19, p. 100029, Art. XXII, § 37, repealed § 15-16-490, which pertained to non-freezing systems.
Municipal Code of Chicago § 15-16-500 Reserved. Editor's note – Coun. J. 4-10-19, p. 100029, Art. XXII, § 37, repealed § 15-16-500, which pertained to gauges.
Municipal Code of Chicago § 15-16-510 Reserved. Editor's note – Coun. J. 4-10-19, p. 100029, Art. XXII, § 37, repealed § 15-16-510, which pertained to relief valves.
Municipal Code of Chicago § 15-16-520 Reserved. Editor's note – Coun. J. 4-10-19, p. 100029, Art. XXII, § 37, repealed § 15-16-520, which pertained to painting or finishing.
Municipal Code of Chicago § 15-16-530 Reserved. Editor's note – Coun. J. 4-10-19, p. 100029, Art. XXII, § 37, repealed § 15-16-530, which pertained to alarms.
Municipal Code of Chicago § 15-16-540 Reserved. Editor's note – Coun. J. 4-10-19, p. 100029, Art. XXII, § 37, repealed § 15-16-540, which pertained to spare sprinklers.
Municipal Code of Chicago § 15-16-550 Reserved. Editor's note – Coun. J. 10-30-96, p. 31216, § 1, repealed § 15-16-550, pertaining to fire pumps for open sprinkler system.
Municipal Code of Chicago § 15-16-560 Reserved. Editor's note – Coun. J. 10-30-96, p. 31216, § 1, repealed § 15-16-560, pertaining to arrangement of open sprinkler system.
Municipal Code of Chicago § 15-16-570 Reserved. Editor's note – Coun. J. 10-30-96, p. 31216, § 1, repealed § 15-16-570, pertaining to sprinkler heads for open sprinkler system.
Municipal Code of Chicago § 15-16-580 Reserved. Editor's note – Coun. J. 10-30-96, p. 31216, § 1, repealed § 15-16-580, pertaining to piping for open sprinkler system.
Municipal Code of Chicago § 15-16-590 Reserved. Editor's note – Coun. J. 10-30-96, p. 31216, § 1, repealed § 15-16-590, pertaining to siamese connections for open sprinkler system.
Municipal Code of Chicago § 15-16-600 Reserved. Editor's note – Coun. J. 4-10-19, p. 100029, Art. XXII, § 37, repealed § 15-16-600, which pertained to hydraulically calculated sprinkler systems.
Municipal Code of Chicago § 15-16-601 Reserved. Editor's note – Coun. J. 4-10-19, p. 100029, Art. XXII, § 37, repealed § 15-16-601, which pertained to residential sprinklers.
Municipal Code of Chicago § 15-16-610 Reserved. Editor's note – Coun. J. 4-10-19, p. 100029, Art. XXII, § 37, repealed § 15-16-610, which pertained to retroactivity.
Municipal Code of Chicago § 15-16-611 Reserved. Editor's note – Coun. J. 4-10-19, p. 100029, Art. XXII, § 37, repealed § 15-16-611, which pertained to carbon dioxide extinguishing systems.
Source: City of Chicago, Municipal Code of Chicago (American Legal Publishing, codelibrary.amlegal.com)URL: https://codelibrary.amlegal.com/codes/chicago/latest/chicago_il/0-0-0-2677514Fetched: 10/24/2026