AMENDMENTS, ADDITIONS, AND DELETIONS TO THE 2023 NATIONAL ELECTRICAL CODE.
Sioux Falls Code of Ordinances § 150.201.1
in effect§ 150.201.1 AMENDMENTS, ADDITIONS, AND DELETIONS TO THE 2023 NATIONAL ELECTRICAL CODE.
The following articles and subsections of the National Electrical Code, 2023 edition, shall be amended, added, or not adopted by the city as follows. All other sections or subsections of the National Electrical Code, 2023 edition, as published shall remain the same.
ARTICLE 100 Definitions. Part 1. Definitions. Equipment. A general term, including fittings, devices, appliances, luminaires, apparatus, and the like used as a part of, or in connection with, an electrical installation.
ARTICLE 100. Definitions. Part 1. Definitions. Kitchen. An area with a sink and permanent provisions for food preparation and cooking. A fixed or portable single microwave does not constitute a permanent cooking facility.
ARTICLE 100 Definitions. Strict Liability Offense. An offense in which the prosecution in a legal proceeding is not required to prove criminal intent as a part of its case. It is enough to prove that the defendant either did an act which was prohibited, or failed to do an act which the defendant was legally required to do.
110.2 Approval. The conductors and equipment required or permitted by this Code shall be acceptable only if approved.
The local electrical inspector shall enforce all rules and specifications in this article as necessary to determine conformity of electrical materials, devices, or appliances with approved methods of construction in order to protect life and property. The label of a nationally recognized electrical testing laboratory, inspection agency, or other organization concerned with product evaluation that maintains periodic inspection during production of equipment or materials, whose label indicates compliance with nationally recognized standards or tests to determine suitable usage in a specified manner, is prima facie evidence that the electrical materials, devices, or appliances are conforming and listed for installation under the provisions of this article.
Exception: Machinery that is reviewed and approved per the machinery policy as adopted by the South Dakota electrical commission.
Informational Note: See 90.7, Examination of Equipment for Safety, and 110.3, Examination, Identification, Installation, and Use of Equipment. See definitions of Approved, Identified, Labeled, and Listed.
110.3 Examination, Identification, Installation, Use, and Listing (Product Certification) of Equipment.
(A) Examination. In judging equipment, considerations such as the following shall be evaluated:
(1) Suitability for installation and use in conformity with this Code.
Informational Note No. 1: Equipment may be new, reconditioned, refurbished, or remanufactured.
Informational Note No. 2: Suitability of equipment use may be identified by a description marked on or provided with a product to identify the suitability of the product for a specific purpose, environment, or application. Special conditions of use or other limitations and other pertinent information may be marked on the equipment, included in the product instructions, or included in the appropriate listing and labeling information. Suitability of equipment may be evidenced by listing or labeling.
(2) Mechanical strength and durability, including, for parts designed to enclose and protect other equipment, the adequacy of the protection thus provided.
(3) Wire bending and connection space.
(4) Electrical insulation.
(5) Heating effects under normal conditions of use and also under abnormal conditions likely to arise in service.
(6) Arcing effects.
(7) Classification by type, size, voltage, current capacity, and specific use.
(8) Cybersecurity for network-connected life safety equipment to address its ability to withstand unauthorized updates and malicious attacks while continuing to perform its intended safety functionality.
Informational Note No. 3: See the ANSI/ISA 62443 series of standards for industrial automation and control systems, the UL 2900 series of standards for software cybersecurity for network-connectable products, and UL 5500, Standard for Remote Software Updates, which are standards that provide frameworks to mitigate current and future security cybersecurity vulnerabilities and address software integrity in systems of electrical equipment.
(9) Other factors that contribute to the practical safeguarding of persons using or likely to come in contact with the equipment.
The state electrical commission may grant special approval of materials, devices, or appliances if no standard has been prepared or adopted to which they should conform. Special approval applies only to the particular sample approved and not to the line as manufactured, stored, sold, installed, or attached and may be granted only for those materials, devices, or appliances which, in the opinion of the state electrical commission, are safe for the use intended. The details of decisions made by the commission shall be recorded and entered into the files of the electrical inspection division. The city does not assume any liability for damage or injury to persons or property because of the use of those materials, devices, or appliances.
110.26 Spaces About Electrical Equipment. (1) Depth of Working Space. The depth of the working space in the direction of live parts shall not be less than that specified in Table 110.26(A)(1) unless the requirements of 110.26(A)(1)(a), (A)(1)(b), or (A)(1)(c) are met. Distances shall be measured from the exposed live parts or from the enclosure or opening if the live parts are enclosed.
In new structures other than dwelling units, additional working space for switchboards, panelboards, switchgear, and motor control centers operating at 600 volts, nominal or less to ground, shall extend up 2 feet above the required working space from the front face of the switchboard, panelboards, switchgear, and motor control centers. This applies only to equipment not part of the electrical installation. Building construction materials shall be allowed in the 2-foot area.
Table 110.26(A)(1) Working Spaces
Nominal Voltage to Ground | Minimum Clear Distance
Condition 1 | Condition 2 | Condition 3
0–150 | 914 mm (3 ft) | 914 mm (3 ft) | 914 mm (3 ft)
151–600 | 914 mm (3 ft) | 1.0668 m (3 ft 6 in) | 1.22 m (4 ft)
600–1000 | 914 mm (3 ft) | 1.22 m (4 ft) | 1.524 m (5 ft)
Note: Where the conditions are as follows:
Condition 1—Exposed live parts on one side of the working space and no live or grounded parts on the other side of the working space, or exposed live parts on both sides of the working space that are effectively guarded by insulating materials.
Condition 2—Exposed live parts on one side of the working space and grounded parts on the other side of the working space. Concrete, brick, or tile walls shall be considered as grounded.
Condition 3—Exposed live parts on both sides of the working space.
(a) Dead-Front Assemblies. Working space shall not be required in the back or sides of assemblies, such as dead-front switchboards, switchgear, or motor control centers, where all connections and all renewable or adjustable parts, such as fuses or switches, are accessible from locations other than the back or sides. Where rear access is required to work on nonelectrical parts on the back of enclosed equipment, a minimum horizontal working space of 762 mm (30 in) shall be provided.
(b) Low Voltage. By special permission, smaller working spaces shall be permitted where all exposed live parts operate at not greater than 30 volts rms, 42 volts peak, or 60 volts dc.
(c) Existing Buildings. In existing buildings where electrical equipment is being replaced, Condition 2 working clearance shall be permitted between dead-front switchboards, switchgear, panelboards, or motor control centers located across the aisle from each other where conditions of maintenance and supervision ensure that written procedures have been adopted to prohibit equipment on both sides of the aisle from being open at the same time and qualified persons who are authorized will service the installation.
110.27 Guarding of Live Parts. (D) Electric Fences. Electric fencing is not allowed to be installed in the city except as approved by the electrical board of appeals and examiners.
210.8(A) Dwelling Units. All 125-volt through 250-volt receptacles installed in the following locations and supplied by single-phase branch circuits rated 150 volts or less to ground shall have ground-fault circuit-interrupter protection for personnel.
(1) Bathrooms.
(2) Garages and also accessory buildings that have a floor located at or below grade level not intended as habitable rooms and limited to storage areas, work areas, and areas of similar use.
(3) Outdoors.
(4) Crawl spaces—at or below grade level.
(5) Basements.
(6) Kitchens.
(7) Areas with sinks and permanent provisions for food preparation, beverage preparation, or cooking.
(8) Sinks—where receptacles are installed within 1.8 m (6 ft) from the top inside edge of the bowl of the sink.
(9) Boathouses.
(10) Bathtubs or shower stalls—where receptacles are installed within 1.8 m (6 ft) of the outside edge of the bathtub or shower stall.
(11) Laundry areas—where receptacles are installed within 3.0 m (10 ft) of the laundry box or water supply laundry hookups.
(12) Indoor damp and wet locations.
Exception No. 1: Receptacles that are not readily accessible and are supplied by a branch circuit dedicated to electric snow melting, deicing, or pipeline and vessel heating equipment shall be permitted to be installed in accordance with 426.28 or 427.22, as applicable.
Exception No. 2: A receptacle supplying only a permanently installed premises security system shall be permitted to omit ground-fault circuit-interrupter protection.
Exception No. 3: Listed weight-supporting ceiling receptacles (WSCR) utilized in combination with compatible weight-supporting attachment fittings (WSAF) installed for the purpose of supporting a ceiling luminaire or ceiling-suspended fan shall be permitted to omit ground-fault circuit-interrupter protection. If a general-purpose convenience receptacle is integral to the ceiling luminaire or ceiling-suspended fan, GFCI protection shall be provided.
Exception No. 4: Factory-installed receptacles that are not readily accessible and are mounted internally to bathroom exhaust fan assemblies shall not require GFCI protection unless required by the installation instructions or listing.
Informational Note: See 760.41(B) and 760.121(B) for power supply requirements for fire alarm systems.
Exception No. 5: Properly labeled recreational vehicle (RV) receptacles other than 125-volt, single-phase, fifteen- and twenty-ampere receptacles are exempt from ground-fault circuit interrupter (GFCI) requirements in section 210.8(A).
Exception No 6: Any outlet in a dwelling unit supplying a specific appliance in Section 210.8(D)(8) through (12) is exempt from GFCI requirements.
210.8(F) Outdoor Outlets. Not adopted by the State or the City.
210.52 Dwelling Unit Receptacle Outlets. (C) (1) Wall Spaces. Receptacle outlets shall be installed so that no point along the wall line is more than 600 mm (24 in) measured horizontally from a receptacle outlet in that space. The location of the receptacles shall be in accordance with 210.52(C)(3). Wall counter space receptacle outlet requirements shall apply to island and peninsula counter spaces provided with backsplash and permanent vertical wall components.
Exception No. 1: Receptacle outlets shall not be required directly behind a range, counter-mounted cooking unit, or sink in the
installation described in Figure 210.52(C)(1).
Exception No. 2: Where a required receptacle outlet cannot be installed in the wall areas shown in Figure 210.52(C)(1), the receptacle outlet shall be permitted to be installed as close as practicable to the countertop area to be served. The total number of receptacle outlets serving the countertop shall not be less than the number needed to satisfy 210.52(C)(1). These outlets shall be located in accordance with 210.52(C)(3).
Figures 210.52(C)(1) Determination of Area Behind a Range, Counter-Mounted Cooking Unit, or Sink.
[image omitted; see the official code]
210.52 Dwelling Unit Receptacle Outlets. (J.) Water softening equipment. In one- and two-family dwellings and town houses, a receptacle outlet shall be installed within 3 feet of the water softener loop or 3 feet of the water heater if no loop exists for water softening equipment.
210.52 Dwelling Unit Receptacle Outlets. (K.) Sump pit. In one- and two-family dwellings and town houses, a GFI-protected receptacle outlet shall be installed within 3 feet of the sump pit on an individual circuit.
210.52 Dwelling Unit Receptacle Outlets. (L) Gas Ranges. In one- and two-family dwellings and town houses, a receptacle outlet shall be installed within 3 feet of the gas range on an individual circuit.
230.28 Service Masts as Supports.
(A) Strength. The service or feeder mast shall be of adequate strength or be supported by braces or guy wires to withstand safely the strain imposed by the service drop or overhead service conductors. Hubs intended for use with a conduit that serves as a service mast shall be identified for use with service entrance equipment.
To gain height, a perpendicular mast shall be installed for the support of service drops to low buildings. This mast must be installed according to the following requirements:
(1) If conduit is used, it must be not less than 2-inch trade-size galvanized, rigid conduit, or intermediate metal conduit.
(2) If a wood mast is used, it must be not smaller in cross section than 4 inches by 6 inches.
(3) If the mast extends more than 48 inches above its last support, the mast must be at least 96 inches long, attached to the structure at a minimum of two locations, and guyed with 1/4-inch minimum guy strand or equivalent, or braced with guy fittings and approved according to Article 90.4 of the National Electrical Code. The measurement is taken from the bottom of the weather head to the top of the first support.
(4) If the mast extends more than 72 inches above its last support, the mast must be at least 120 inches long, attached to the structure at a minimum of three locations, and guyed with fittings in two directions to provide support.
(5) Only the power company’s service drop conductors shall be attached to a service mast. Phone loops, cable TV conduits, grounding clamps, and the like shall not be attached to the service mast. Conduit couplings shall not be installed above the roof line.
230.91 Location. The service overcurrent device shall be an integral part of the service disconnecting means or shall be located immediately adjacent thereto. Where fuses are used as the service overcurrent device, the disconnecting means shall be located ahead of the supply side of the fuses.
The raceway containing conductors to the service entrance disconnect enclosure may not extend more than 5 feet inside the structure, except with the written permission of the state electrical or local electrical inspector. The raceway or cable assembly may not extend more than 5 feet once inside the structure to the main disconnect. Metering enclosures and junction boxes are not included when determining these lengths. Additional lengths in the structure may be installed only with the prior written permission of the electrical inspector or approval of the electrical board of appeals and examiners.
250.24 Grounding of Service-Supplied Alternating-Current Systems. (A) System Grounding Connections. (1) General. The grounding electrode conductor connection shall be made at any accessible point from the load end of the overhead service conductors, service drop, underground service conductors, or service lateral to the terminal or bus to which the grounded service conductor is connected at the service disconnecting means. All grounding electrode conductors of the system grounding connection must terminate on the neutral bus inside the service equipment unless they are inspected before the service is energized by the power supplier.
Informational Note: See Article 100 for definitions of Service Conductors, Overhead; Service Conductors, Underground; Service Drop; and Service Lateral.
250.53 Grounding Electrode System Installation. (D) Metal Underground Water Pipe. (1) Continuity. Continuity of the grounding path or the bonding connection to interior piping shall not rely on water meters or filtering devices and similar equipment.
A bonding jumper size in accordance with Table 250.66 shall be installed between the hot and cold water lines at the water heater and cold hard and soft lines even if the softener is not in place.
300.5 Underground Installations. (D) Protection from Damage. Direct-buried conductors and cables shall be protected from damage in accordance with 300.5(D)(1) through (D)(5).
(1) Emerging from Grade. Direct-buried conductors and cables emerging from grade and specified in columns 1 and 4 of Table 300.5(A) shall be protected by enclosures or raceways extending from the minimum cover distance below grade required by 300.5(A) to a point at least 2.5 m (8 ft) above finished grade. In no case shall the protection be required to exceed 450 mm (18 in) below finished grade.
(2) Conductors Entering Buildings. Conductors entering a building shall be protected to the point of entrance.
(3) Service Conductors. Underground service conductors that are not encased in concrete and that are buried 450 mm (18 in) or more below grade shall have their location identified by a warning ribbon that is placed in the trench at least 300 mm (12 in) above the underground installation.
(4) Enclosure or Raceway Damage. Where the enclosure or raceway is subject to physical damage, the conductors shall be installed in electrical metallic tubing, rigid metal conduit, intermediate metal conduit, RTRC-XW, Schedule 80 PVC conduit, or equivalent.
(5) Underground Conductors to Comply with Installation Requirements. All underground conductor installations, in addition to complying with the requirements of the National Electrical Code, laws of the state of South Dakota, and the state electrical commission, shall comply with the requirement that direct burial underground service conductors or feeders shall be installed in a raceway from the building to a point beyond any concrete or asphalt slabs, stoops, footings, or driveways, which may interfere with future conductor replacement.
300.13 Mechanical and Electrical Continuity— Conductors. (B) Device Removal. The continuity of a conductor shall not depend on device connections such as lampholders, receptacles, and so forth, where the removal of such devices would interrupt the continuity.
310.10 Uses Permitted. (C) Wet Locations. Insulated conductors and cables used in wet locations shall comply with one of the following:
(1) Be moisture-impervious metal-sheathed.
(2) Be types MTW, RHW, RHW-2, TW, THW, THW-2, THHW, THWN, THWN-2, XHHW, XHHW-2, XHWN, XHWN-2, or ZW.
(3) Be of a type listed for use in wet locations.
For the installation of cables and equipment that are not approved for a wet location, the structure must meet the following:
(1) Must maintain a minimum of 20 degrees Fahrenheit temperature in building.
(2) Must have a weatherproofed roof.
(3) Must be totally enclosed.
Exception. Areas located outside of an area measured from the top and sides of an opening at a 1 to 1 ratio.
334.30 Securing and Supporting. Nonmetallic-sheathed cable shall be supported and secured by nonconductive insulated staples, cable ties listed and identified for securement and support, or straps, hangers, or similar fittings designed and installed so as not to damage the cable, at intervals not exceeding 1.4 m (4 ½ ft) and within 300 mm (12 in) of every cable entry into enclosures such as outlet boxes, junction boxes, cabinets, or fittings. The cable length between the cable entry and the closest cable support shall not exceed 450 mm (18 in). Flat cables shall not be stapled on edge.
Sections of cable protected from physical damage by raceway shall not be required to be secured within the raceway.
358.12 Uses Not Permitted. EMT shall not be used under the following conditions:
(1) Where subject to severe physical damage.
(2) For the support of luminaires or other equipment except conduit bodies no larger than the largest trade size of the tubing.
(3) Electrical metallic tubing may not be used in concrete below grade or in concrete slab or masonry in direct contact with earth nor embedded in earth or fill. The use of a vapor barrier has no effect on the requirements of this section.
408.36 Overcurrent Protection. In addition to the requirement of 408.30, a panelboard shall be protected by an overcurrent protective device having a rating not greater than that of the panelboard. This overcurrent protective device shall be located within or at any point on the supply side of the panelboard. Installation of 120-volt plug-in circuit breakers in three-phase, four-wire panelboard on a delta system is prohibited.
Exception No. 1: Individual protection shall not be required for a panelboard protected by two main circuit breakers or two sets of fuses in other than service equipment, having a combined rating not greater than that of the panelboard. A panelboard constructed or wired under this exception shall not contain more than 42 overcurrent devices. For the purposes of determining the maximum of 42 overcurrent devices, a 2-pole or a 3-pole circuit breaker shall be considered as two or three overcurrent devices, respectively.
Exception No. 2: For existing panelboards, individual protection shall not be required for a panelboard used as service equipment for an individual residential occupancy.
422.12 Central Heating Equipment. Central heating equipment other than fixed electric space- heating equipment shall be supplied by an individual branch circuit and a disconnect shall be provided in sight and within 6 feet of the unit.
Exception No. 1: Auxiliary equipment, such as a pump, valve, humidifier, or electrostatic air cleaner directly associated with the heating equipment, shall be permitted to be connected to the same branch circuit.
Exception No. 2: Permanently connected air- conditioning equipment shall be permitted to be connected to the same branch circuit.
517.13 Equipment Grounding Conductor for Receptacles and Fixed Electrical Equipment in Patient Care Spaces. (B) Insulated Equipment
Grounding Conductors and Insulated Equipment Bonding Jumpers. (1) General. All receptacles installed in a patient care area shall be listed “Hospital Grade” and shall be so identified and the identification shall be visible after installation. An insulated copper equipment grounding conductor that is clearly identified along its entire length by green insulation and installed with the branch circuit conductors within the wiring method in accordance with 517.13(A) shall be connected to the following:
(1) Grounding terminals of all receptacles other than isolated ground receptacles.
(2) Metal outlet boxes, metal device boxes, or metal enclosures.
(3) All non-current-carrying conductive surfaces of fixed electrical equipment likely to become energized that are subject to personal contact, operating at over 100 volts.
Exception No. 1: For other than isolated ground receptacles, an insulated equipment bonding jumper that directly connects to the equipment grounding conductor shall be permitted to connect the box and receptacle(s) to the equipment grounding conductor. Isolated ground receptacles shall be connected in accordance with 517.16.
Exception No. 2: Metal faceplates shall be connected to an effective ground-fault current path by means of a metal mounting screw(s) securing the faceplate to a metal yoke or strap of a receptacle or to a metal outlet box.
Exception No. 3: Luminaires more than 2.3 m (7 ½ ft) above the floor and switches located outside of the patient care vicinity shall be permitted to be connected to an equipment grounding return path complying with 517.13(A) or (B).
(Ord. 62-17, passed 7-18-2017; Ord. 68-20, passed 9-1-2020; Ord. 58-25, passed 10-7-2025)