Sec. 49-1124. - Sizing criteria for non-certified exterior grease interceptor.
The following formulas shall be applied to grease interceptor sizing: (a) The grease interceptor capacity for commercial kitchens with seating or beds (including restaurants, cafeterias, hospitals, schools, institution, care facilities, clubs, bars and dance halls) shall be calculated according the following formula: Size = T.O.R. × C.U.F. × 2.0 × S.C. Where: Size = Total volume (in gallons) of the grease interceptor. T.O.R. = Turnover rate which averages two meals (place settings) per table per hour. C.U.F. = Categorical use factor. 2.0 = The average water (in gallons) used per place setting. S.C. = Seating capacity in subject facility (or bed usage for care facilities). (b) The grease interceptor capacity for commercial kitchens without seating or beds (including deli stores with meat cutting, super markets with meat cutting, bakeries, catering and butcher shops) shall be calculated according to the following formula: Size = H.O. × C.U.F. × 10 Where: Size = Total volume (in gallons) of the grease interceptor. H.O. = Number of hours of operation per day. C.U.F. = Categorical use factor.
(Ord. No. 40524, § 1, 10-20-15)