§ 49-1544 — Fire suppression systems
Omaha Municipal Code (Supp. No. 100, Update 2: codified through Ordinance No. 44760, enacted August 4, 2026) · Omaha Municipal Code § 49-1544
Corpus is an independent public-information project, not the official City of Omaha website. Stable reference: corpuslaw.us/code/a6ded083-4713-4367-b456-054b5b3a092d
Sec. 49-1544. - Fire suppression systems.
The following provisions shall apply to all water-based fire protection systems: (a) Water-based fire protection systems not utilizing antifreeze shall be isolated by an approved double check valve assembly. (b) Water-based fire protection systems requiring an antifreeze solution: (1) A pharmaceutical grade, propylene glycol or similar, antifreeze shall be used. (2) A certification identifying the type of pharmaceutical grade antifreeze used and the last date concentrations were verified shall be posted near the double check valve. (c) Existing water-based fire protection systems shall be inspected by a certified fire suppression specialist to determine whether pharmaceutical grade antifreeze has been utilized. This shall be done at the expense of the building owner. If it cannot be certified that only pharmaceutical grade antifreeze has been used, then at the expense of the building owner, a reduced pressure principle backflow prevention assembly shall be installed.
(Ord. No. 40524, § 1, 10-20-15)