1105.5.4.2. Permissible Omissions.

The following features required in new high-rise buildings are not required in systems installed under the provisions of this section: 1. Redundant fire pump; 2. Two-hour rated fire pump room; 3. Secondary on-site supply of water; 4. Water supply from two underground water lines; 5. Connection of the system to two risers on each floor. Hydraulic calculations may consider all risers in service. See California Fire Code Section 903.3.1.1.1 for additional permissible sprinkler omissions. CODIFICATION NOTE 1. So in Ord. 39-26.