§ 29.58 — 704.6.1.2 Groups R-2, R-3, R-4 and I-1
Cedar Rapids, Iowa, Municipal Code (Supp. No. 25, Update 1: codified through Ordinance No. 025-26, passed July 28, 2026) · Cedar Rapids Municipal Code § 29.58
Corpus is an independent public-information project, not the official City of Cedar Rapids website. Stable reference: corpuslaw.us/code/a71aad6b-d5fe-4849-9fff-4b9b2d96089d
29.58 - 704.6.1.2 Groups R-2, R-3, R-4 and I-1.
Section 704.6.1.2 of the IMPC is hereby amended by adding the following as items 4 and 5 to said section: 4. Smoke alarms must be listed in accordance with UL 217 Standard for Smoke Alarms or UL 268 Smoke Detectors for Fire Alarm Systems. 5. A battery-powered smoke alarm listed in accordance with UL 217 that is newly installed or replaces an existing battery-powered smoke alarm must be powered by a nonremovable, nonreplaceable battery that powers the alarm for at least ten years. The battery requirements of this subrule do not apply to a fire alarm, smoke detector, smoke alarm, or ancillary component that is electronically connected as a part of a centrally monitored or supervised alarm system; that uses a low-power, radio frequency wireless communication signal. (033-24)