17.12.1015 - Amendment of Chapter 80 - NFPA 13R - 25 - Standard for the installation of sprinkler systems in low-rise residential occupancies.
The following sections of NFPA 13R - 25 edition, Standard for the Installation of Sprinkler Systems in Low-rise Residential Occupancies, are amended to read as follows: 6.6.6.3 is deleted. 6.6.7 is deleted. 6.8.8 Control valves are required to be zoned per floor. 6.11.2 Fire department connections (FDC) shall be 2½ in. inlets with female National Standard Hose threads; all inlets shall be equipped with individual check valves (e.g. clappers). The FDC inlets shall be located at a height of 30 to 36" aboveground. 6.16.4 Where a building fire alarm system is provided, the building sprinkler systems are required to be zoned by floor. 10.2.2.1 Systems shall be hydrostatically tested for leakage at 200 psi for a duration of 2 hours in accordance with NFPA 13. 10.2.2.2 is deleted.