§ 49-1533 — Water pipe sizing for dwelling units and townhouses
Omaha Municipal Code (Supp. No. 100, Update 2: codified through Ordinance No. 44760, enacted August 4, 2026) · Omaha Municipal Code § 49-1533
Corpus is an independent public-information project, not the official City of Omaha website. Stable reference: corpuslaw.us/code/ab13d45f-4e95-4926-a977-4a4055987e00
Sec. 49-1533. - Water pipe sizing for dwelling units and townhouses.
The following provisions shall be observed regarding water pipe sizing requirements in dwelling units and townhouses: (a) Up to 40 fixture units requires a three-quarters inch cold water supply from the water meter to the water heater. The following also applies: (1) Hot and cold water supply from the water heater shall be at least three-fourths inch to each one-half inch branch. (2) A maximum of nine fixture units shall be connected to any one-half inch hot or cold water line. (3) In no case shall there be more than one water closet connected to a one-half inch cold line. (b) No more than 40 fixture units shall be connected to any three-quarters inch hot or cold water line. (c) From 41 to 49 fixture units requires a one inch cold water supply from the water meter to the water heater. The hot and cold water supply from water heater shall be one inch until the fixture unit load is reduced to the provisions of subsections (a) and (b). (d) Lines serving 50 fixture units or more shall be sized according Table 49-1532. (e) In existing dwelling units and townhouses where the water pipe is being replaced from the meter to the fixture connection or at a point below the floor, the pipe sizing shall also conform to the above requirements.
(Ord. No. 40524, § 1, 10-20-15)
Ask a question about Omaha law
Corpus searches the Omaha sections it holds and shows the ones that match, with their citations. Free, no sign-in.