Sec. 36-38. - Use of non-potable water for fire protection.
(a) All commercial structures for which a building permit is issued after June 30, 1985, adjacent to golf courses using non-potable or reclaimed water for irrigation with sufficient storage capacity on site, may be sprinklered using this supply.
(b) Irrigation systems shall be designed to meet the fire department's standards of gallons per minute flow and pressure necessary to supply adequate fire flow.
(c) Standby power supply for pumping station supplying fire flow shall be provided.
(d) Fire hydrants on domestic supply shall be placed in close proximity to the fire department connection for structural sprinkler systems to provide a secondary water supply.
(e) Fire hydrants placed on approved non-potable, reclaimed water supply systems, shall have caps and bonnet painted with a prime coat plus two (2) coats of purple paint. A placard shall be affixed to the hydrant in English and Spanish, "DO NOT DRINK WATER." Non-potable water supplies shall use approved material for construction of all mains and supply lines and shall have the written approval of the fire code official.
(f) All water inlets for non-potable systems shall be required to have sufficient straining and filtering capacity to eliminate all foreign objects from blocking sprinkler orifice. Chlorination of inlet lines shall be required.