Sec. 49-1304. - Fixture vent pipe sizes.
Fixtures listed below shall have the following minimum vent size: Table 49-1304 Kind of Fixture | Size of Vent Pipe (inches) Bar sink: Residential | 1¼ Commercial | ID Bathtub | 1½ Beer taps (Note 1) | 1¼ Bidets | 1½ Cuspidors | 1¼ Dental units | 1¼ Disposal: Residential | 1½ Commercial | 1½ Drinking fountain | 1¼ Dishwasher: Residential | 1½ Commercial | ID Floor drains (Note 2) | 1½ Floor sink (Note 2) | 1½ Flushing rim sink | 1½ Glass washer | 1½ Laundry sink | 1½ Lavatory (basin) | 1¼ Mop sink (Note 2) | 1½ Service sinks | 1½ Shower stall (Note 2) | 1½ Sink: Residential | 1½ Commercial | 1½ Sitz bath | 1½ Sump pump (Note 4) Urinals | 1½ Water closet | 1½ Wash fountains | 1½ Washer, clothes: Residential | 2 Commercial (Note 3) Note 1: Beer taps should be run indirect when possible (see section 49-1013 note 1). Note 2: A vent may not be required (see section 49-1306). Note 3: See section 49-603. Note 4: See sections 49-907, 49-908 and 49-910. ID = Requires an indirect waste. Fixtures listed in section 49-1306(a) when connected to a soil or waste line or a branch soil or waste line, shall be counted for venting purposes.
(Ord. No. 40524, § 1, 10-20-15; Ord. No. 42654, § 40, 8-13-21)