§ 207-11. - Machine exhaust system.

Each dry-cleaning machine shall be equipped with an exhaust system that maintains a minimum of 100 feet per minute velocity through the loading door whenever the door is open. The duct work connections to this system shall be sealed (soldered or taped) and the discharge outlet extended to a minimum height of five feet above the roof line and shall be located so that the effluent may not re-enter the premises or become a nuisance to occupants of adjoining buildings.

[Amended 6-25-2025 by Ord. No. 25-072]