Philadelphia Code Subcode B, § 704 FIRE-RESISTANCE RATING OF STRUCTURAL MEMBERS
SECTION 704 FIRE-RESISTANCE RATING OF STRUCTURAL MEMBERS
* * *
[Pursuant to the UCC, revise Section B-704.2 by deleting the exception as follows:]
B-704.2 Column protection. Where columns are required to have protection to achieve a fire-resistance rating, the entire column shall be provided individual encasement protection by protecting it on all sides for the full column height, including connections to other structural members, with materials having the required fire-resistance rating. Where the column extends through a ceiling, the encasement protection shall be continuous from the top of the foundation or floor/ceiling assembly below through the ceiling space to the top of the column.
Exception: Columns that meet the limitations of Section 704.4.1.
* * *
704.4 Protection of secondary structural members.
* * *
[Pursuant to the UCC, delete Section B-704.4.1 and replace as follows:]
B-704.4.1 Light-frame construction. Studs and boundary elements that are integral elements in load-bearing walls of light-frame construction shall be permitted to have required fire-resistance ratings provided by the membrane protection provided for the load-bearing wall.
* * *