General sewer use requirements
Tyler City Code § 19-73
in effectSec. 19-73. General sewer use requirements
a. Prohibited discharge standards. No industrial user shall introduce or cause to be introduced into the POTW any pollutant or wastewater which causes pass through or interference. These general prohibitions apply to all industrial users of the POTW whether or not they are subject to categorical pretreatment standards or any other federal, state, or local pretreatment standards or requirements. Wastes prohibited by this section shall not be processed or stored in such a manner that they could be discharged to the POTW, except that any floor drains connected to the POTW located in a process or material storage area may be allowed by the Manager provided proper controls are in place. No industrial user may contribute the following substances to the POTW:
1. Pollutants which create a fire or explosive hazard in the municipal wastewater collection system and POTW, including, but not limited to, wastestreams with a closed-cup flash point of less than one hundred forty (140) degrees Fahrenheit (60º C) using the test methods specified in 40 CFR 261.21.
2. Any wastewater having a pH less than five (5.0) or more than eleven and five-tenths (11.5), or otherwise causing corrosive structural damage to the POTW or equipment, or endangering City personnel.
3. Solid or viscous substances in amounts which will cause obstruction of the flow to or within the POTW resulting in interference, but in no case solids greater than five-tenths (0.5) inch in any dimension.
4. Any wastewater containing pollutants, including oxygen demanding pollutants (BOD5, COD, etc.), released in a discharge at a flow rate and/or pollutant concentration which, either singly or by interaction with other pollutants, will cause pass through or interference with the POTW or any wastewater treatment or sludge process; or which will constitute a hazard to human or animal life.
5. Any wastewater having a temperature greater than one hundred fifty (150) degrees Fahrenheit (65° C), or which will inhibit biological activity in the treatment plant resulting in interference, but in no case wastewater which causes the water temperature at the introduction into the treatment plant to exceed one hundred four (104) degrees Fahrenheit (40° C).
6. Petroleum oil, nonbiodegradable cutting oil, or products of mineral oil origin in amounts that will cause interference or pass through. Any discharge of such oil is limited to one hundred (100) mg/l.
7. Any discharge of fats, oils, or greases of animal or vegetable origin in a concentration greater than one hundred (100) mg/l.
8. Any pollutants which result in the presence of toxic gases, vapors or fumes within the POTW in a quantity that may cause acute worker health and safety problems.
9. Any trucked or hauled pollutants, except at discharge points designated by the Manager in accordance with Section 19-74e.
10. Any noxious or malodorous liquids, gases, solids, or other wastewater which, either singly or by interaction with other wastes, are sufficient to create a public nuisance, a hazard to life, or to prevent entry into the sewers for maintenance and repair.
11. Any wastewater which imparts color that cannot be removed by the treatment process, such as, but not limited to, dye wastes or vegetable tanning solutions, and which consequently imparts color to the treatment plant's effluent thereby violating the City's NPDES permit. Color (in combination with turbidity) shall not cause the treatment plant effluent to reduce the depth of the compensation point for photosynthetic activity by more than ten (10) percent from the seasonably established norm for aquatic life.
12. Any wastewater containing any radioactive wastes or isotopes except as specifically approved by the Manager in compliance with applicable state or federal regulations.
13. Any wastewater causing the effluent from the treatment plant to fail a toxicity test.
14. Any wastes containing detergents, surface active agents, or other substances which cause excessive foaming in the POTW.
b. Federal categorical pretreatment standards. The national categorical pretreatment standards found in 40 CFR Chapter I, Subchapter N, Parts 405 through 471 are hereby incorporated.
c. Specific pollutant limitations.
1. The following pollutant limits are established to protect against pass through and interference. No person shall discharge wastewater containing in excess of the following daily maximum limits:
Arsenic (As) 0.60 mg/l
Cadmium (Cd) 0.20 mg/l
Chromium (Cr) 5.00 mg/l
Copper (Cu) 0.60 mg/l
Cyanide 0.30 mg/l
Lead (Pb) 0.30 mg/l
Mercury (Hg) 0.01 mg/l
Nickel (Ni) 2.00 mg/l
Silver (Ag) 0.10 mg/l
Total phenols 2.00 mg/l
Zinc (Zn) 2.00 mg/l
2. Concentrations apply at the point where the industrial waste is discharged to the POTW unless otherwise permitted. All concentrations for metallic substances are for "total" metal unless indicated otherwise. Mass limitations in addition to, or in place of, the concentration based limitations above may be imposed by the Manager.
d. City's right of revision. The City reserves the right to establish, by division or in wastewater discharge permits, more stringent standards or requirements on discharges to the POTW if deemed necessary to comply with:
1. The objectives presented in Section 19-72a. of this division; or
2. The general and specific prohibitions in paragraphs a. through c. of this section.
e. Special agreement. The City reserves the right to enter into special agreements with industrial users setting out special terms under which they may discharge to the POTW. In no case will a special agreement waive compliance with a pretreatment standard or requirement. However, the industrial user may request a net gross adjustment to a categorical standard in accordance with 40 CFR 403.15. They may also request a variance from the categorical pretreatment standard from EPA. Such a request will be approved only if the industrial user can prove that factors relating to its discharge are fundamentally different from the factors considered by EPA when establishing that pretreatment standard. An industrial user requesting a fundamentally different factor variance must comply with the procedural and substantive provisions in 40 CFR 403.13.
f. Dilution. No industrial user shall ever increase the use of process water, or in any way attempt to dilute a discharge, as a partial or complete substitute for adequate treatment to achieve compliance with a discharge limitation unless expressly authorized by an applicable pretreatment standard or requirement. The Manager may impose mass limitations on industrial users when that industry is using dilution to meet applicable pretreatment standards or requirements.
g. Discharge to manholes. No person shall discharge any substance into a sewer appurtenance intended for maintenance, including but not limited to a manhole or inspection port, without written permission from the Manager.
h. Direct discharges. Unless authorized by the Texas Natural Resource Conservation Commission, no person shall deposit or discharge any wastewater, industrial waste, or polluted liquid on public or private property, into or adjacent to any natural outlet, natural watercourse, storm sewer, street, gutter, drainage ditch, or other area within the jurisdiction of the City.
(Ord. No. O-96-4, 1-24-96) (Ord. No. 0-99-80, 10/20/99)
Source: City of Tyler, Texas, Code of Ordinances and Charter (American Legal Publishing, codelibrary.amlegal.com)URL: https://codelibrary.amlegal.com/codes/tyler/latest/tyler_tx/0-0-0-93398Fetched: 11/14/2026