Sec. 49-1610. - Water heaters ASME-rated.

Any water heater with an input rating of 200,000 BTU/Hr. shall meet ASME section 4 part HLW. The following provisions will be observed regarding ASME-rated water heaters: (a) A thermometer indicating discharge water temperature shall be installed at or near the outlet between the heater and any valve. The thermometer shall be easily readable from the floor. (b) There shall be 18 inches of clearance (or as required by the manufacturer) from any side or back wall and there shall be 24 inches by the width of the heater space as measured from the front of the burner to any obstruction. (c) Boiler manholes shall have not less than five-foot clearance as measured to any obstruction for maintenance. Hand holes shall have not less than two feet as measured to any obstruction for maintenance. (d) All relief valves shall be readily accessible.

(Ord. No. 40524, § 1, 10-20-15)