Sec. 49-1314. - Stack venting.
The highest fixture on a stack may have a soil or waste branch extended from a sanitary tee, figure-five fitting or a fixture fitting not exceeding the distance listed in Table 49-1403 from the center of the stack to the fixture opening at the finished floor (or wall line) without installing a re-vent. (a) A maximum of four fixture units shall be permitted to be stack vented on a three-inch or larger stack above a stack-vented water closet. (b) Bathtubs or shower baths may be stack vented when connected through a sanitary tee with a side inlet at the same level as the stack vented water closet, when installed in a three-inch or larger stack. The maximum number of fixtures units permitted to be stack vented above the water closet shall be four. (See Figure 49-1314(b).)
(Ord. No. 40524, § 1, 10-20-15)