§ 49-1321 — Venting of water closets

Omaha Municipal Code (Supp. No. 100, Update 2: codified through Ordinance No. 44760, enacted August 4, 2026) · Omaha Municipal Code § 49-1321

Corpus is an independent public-information project, not the official City of Omaha website. Stable reference: corpuslaw.us/code/c2f1f81b-e18e-41a2-b6a0-b4b409aa7867

Sec. 49-1321. - Venting of water closets.

In addition to a properly installed individual vent, a water closet may be vented by one of the following other methods: (a) Battery venting. (1) A horizontal soil branch that is properly sized to receive the discharge of two but not more than eight floor outlet water closets, may be vented by a circuit or a loop vent, which shall be taken off in front of the last fixture. The circuit, loop or relief vent shall not receive the discharge of any soil or waste. (see Figure 49-1321(a)(1).) (2) In multiple-level buildings, the lower floor branches connected to a vertical stack and serve more than three fixtures shall be provided with a relief vent taken off in front of the first fixture connection. (see Figure 49-1321(a)(2).) (3) Circuit, loop or relief vents shall be taken off from the top of the horizontal branch and shall be sized according to sections 49-1304 and 49-1313. (4) Each water closet fixture drain shall connect horizontally to the horizontal branch. The maximum distance of a waste arm shall be five feet from the soil branch to the fixture opening. (5) The horizontal soil branch drain and fixture branch shall be the same size. (6) The maximum slope of the horizontal drain shall be one-half inch per foot. (7) Restroom group fixtures may be added to the battery vented fixtures and vented as required. (See Figures 49-1321(a)(7)(1) and 49-1321(a)(7)(2).) (8) Multiple groups of circuit vented (battery vented) fixtures are permitted to be connected together. Each group of two but not more than eight floor outlet water closets shall be considered a separate battery vent. The size of the horizontal soil branch shall be sized for the total discharge of the branch. (b) Wet venting. (1) A water closet may be vented through a wet vent when the fixture units do not exceed four. The connection for the waste piping shall be within two feet of the opening of the water closet. No water closet except as allowed in subsection (c)(3) below shall be wet vented through the waste of a clothes washer or any fixture vented through the use of a return vent. (See Figure 49-1321(b)(1).) (2) A water closet and a tub may be vented through a lavatory waste when all three fixtures are adjacent to each other on the same wall (as illustrated in Figure 49-1321(b)(3)). The connection for the lavatory waste shall be within two feet of the tub trap. (c) Stack venting. (1) That the highest water closet on a stack may have a soil or waste branch extended to a distance not to exceed five feet developed length from the center of the stack to the fixture opening at the finished floor or wall line without installing a re-vent. (2) On the highest water closets only, if it becomes necessary to extend the soil branch beyond the limits set forth above, and on all water closets below the top closet, a re-vent shall be provided as close as possible to the fixture opening, but in no case shall the re-vent be more than two feet developed length from the vent opening to the finished floor. (3) The maximum number of fixture units permitted to be stack vented above a stack-vented water closet shall not exceed four fixture units. A clothes washer may be discharged above a stack-vented water closet provided that the vertical distance from the fitting in the stack for the connection to the water closet and the invert of the horizontal soil waste is seven feet or more. (4) A water closet that complies with subsection (c)(1) above will be considered stack vented if other fixtures are connected to the water closet branch through a wye or side inlet 90 degree ell provided the fixture units do not exceed four. (d) Horizontal double-wye. (1) Two floor outlet water closets installed back-to-back may be installed using a double wye and vented out the end of the double wye, provided that a long sweep or short sweep of the same size is installed in the double-wye and extended vertically to a cleanout of the same size. (2) A maximum of four fixture units shall be allowed on this vent. (See Figure 49-1321(d)(2).)

(Ord. No. 40524, § 1, 10-20-15; Ord. No. 42654, § 41, 8-13-21)

Ask a question about Omaha law

Corpus searches the Omaha sections it holds and shows the ones that match, with their citations. Free, no sign-in.