GENERALLY
Scottsdale Revised Code ch. 36, art. II, div. 1
in effectScottsdale Revised Code § 36-16.1 Reserved.
Scottsdale Revised Code § 36-17 Assumption of jurisdiction; adoption.
Sec. 36-17. - Assumption of jurisdiction; adoption.
(a) Pursuant to the provisions of A.R.S. § 41-2163(a)(2), the City of Scottsdale, having in effect a nationally recognized fire code, does hereby assume jurisdiction from the state fire safety committee for prescribing and enforcing minimum fire and life safety codes and standards within the City of Scottsdale.
(Code 1972, § 9-201; Ord. No. 1709, § I, 6-4-85; Ord. No. 1925, § 1, 8-31-87; Ord. No. 2308, 9-17-90; Ord. No. 2453, 6-15-92; Ord. No. 2786, §§ 1, 2, 12-18-95; Ord. No. 2939, § 1, 9-30-96; Ord. No. 3100, § 1, 2-17-98; Ord. No. 3507, § 6, 6-17-03; Ord. No. 3738, § 1, 7-10-07; Ord. No. 4045, § 1, 12-4-12)
Scottsdale Revised Code § 36-18 Automatic sprinkler systems.
Sec. 36-18. - Automatic sprinkler systems.
SECTION 903 AUTOMATIC SPRINKLER SYSTEMS
903.2 Where required. Approved automatic sprinkler systems shall be installed throughout all levels of all new Group A, B, E, F, H, I, M, R, S and U occupancies of more than zero (0) square feet. In accordance with section 903, and the fire department interpretation and applications manual, and as set in this section.
1. In every story or basement of all buildings. Fire-resistive substitutions in accordance with provisions in the International Building Code, chapter 6 footnote d, are allowed for this subsection for Group R occupancies and for other occupancies, provided that the automatic sprinkler is not otherwise required throughout the building by any other provision or section of the unamended building code.
2. At the top of rubbish and linen chutes and in their terminal rooms. Chutes extending through three or more floors shall have additional sprinkler heads installed within such chutes at alternate floors. Sprinkler heads shall be accessible for servicing.
3. In rooms where nitrate film is stored or handled. See also International Fire Code section 306.
4. In protected combustible fiber storage vaults.
5. In any building that has a change in occupancy as defined in the building code.
Exception: The following accessory structures shall be exempt from fire sprinkler requirements:
1. Gazebos, ramadas and pool equipment for residential and multi-family public use.
2. Independent rest room buildings that are associated with golf courses, parks and similar uses, up to 1500 square feet (139.35 m 2 ).
3. Guardhouses for residential and commercial developments.
4. Detached non-combustible carports for residential and commercial developments with covered parking less than 15,000 square feet (1394 m 2 ).
5. Barns and agricultural buildings for private, residential, non-commercial use, not exceeding 1,500 square feet (139.35 m 2 ), with no habitable areas.
6. Detached storage sheds for private, residential, or non-commercial use, not exceeding 1,500 square feet (139.35 m 2 ).
7. Detached garages not exceeding 1,000 square feet (m 2 )(without habitable spaces) in existing R-3 developed parcels which contain existing non-sprinklered subdivision requirements (i.e. 700 foot (213.36 m) hydrant spacing.
8. For fuel dispensing canopies not exceeding 1,500 square feet (139.35 m 2 ).
9. Open shade horse stalls of non-combustible construction for private, residential, non-commercial use, not exceeding 5,000 square feet (464.52 m 2 ) and no storage of combustible products, vehicles, or agricultural equipment.
10. Detached one story accessory building used as tool or storage shed of non-hazardous materials, and not exceeding 200 square feet (11.15 m 2 ).
11. Special use non-combustible structures as approved by fire code official, such as pump rooms.
12. Open equestrian arenas for riding only.
13. Detached cell phone equipment structures that have no occupiable space.
14. New addition, alteration or repair, less than 25%, by value, to a detached single family residence in non-sprinklered developments which contain existing fire hydrant spacing of 700 feet (213,360 mm) or less.
903.2.1 Group A. An automatic sprinkler system shall be provided throughout buildings and portions thereof used as Group A occupancies in accordance with NFPA 13 installation of sprinkler systems and the fire department interpretation and applications manual.
903.2.2 Group B. An automatic sprinkler system shall be installed throughout all Group B occupancies in accordance with NFPA 13 installation of sprinkler systems as modified by the fire department interpretation and applications manual.
903.2.3 Group E. An automatic sprinkler system shall be provided for Group E occupancies in accordance with NFPA 13 installation of sprinkler systems and the fire department interpretation and applications manual.
903.2.4 Group F-1. An automatic sprinkler system shall be provided throughout all Group F-1 occupancies in accordance with NFPA 13 installation of sprinkler systems and the fire department interpretation and applications manual.
903.2.5 Group H. Automatic sprinkler systems shall be provided throughout all high-hazard occupancies in accordance with NFPA 13 installation of sprinkler systems and the fire department interpretation and applications manual.
903.2.6 Group I. An automatic sprinkler system shall be provided throughout all Group I occupancies in accordance with NFPA 13 installation of sprinkler systems and the fire department interpretation and applications manual.
903.2.7 Group M. An automatic sprinkler system shall be provided throughout all Group M occupancies in accordance with NFPA 13 installation of sprinkler systems and the fire department interpretation and applications manual.
903.2.8 Group R and IRC. An automatic sprinkler system shall be provided throughout all Group R and IRC occupancies in accordance with NFPA 13,13-R or 13-D installation of sprinkler systems and the fire department interpretation and applications manual.
903.2.9 Group S-1. An automatic sprinkler system shall be provided throughout all Group S-1 occupancies in accordance with NFPA 13 installation of sprinkler systems and the fire department interpretation and applications manual.
903.2.10 Group S-2. An automatic sprinkler system shall be provided throughout all Group S-2 occupancies in accordance with NFPA 13 installation of sprinkler systems and the fire department interpretation and applications manual.
903.2.15 Additions, alterations and repairs. When additions, alterations or repairs within a twelve-month period exceed fifty (50) percent of the value of an existing building or structure, such building or structure shall be made to conform to the requirements for new buildings or structures.
Exception: Such buildings or structures shall be equipped with an approved fire sprinkler system when work exceeds ten (10) percent of the value for an existing Group A (assembly) building, or twenty-five (25) percent of the value for an existing building or structure of other occupancies.
903.3 Installation requirements. Automatic sprinkler systems shall be designed and installed in accordance with NFPA 13, 13-R, or 13-D installation of sprinkler systems as modified by the fire department interpretation and applications manual.
903.3.4 Actuation. Automatic sprinkler systems shall be automatically actuated unless specifically provided for in this code.
903.3.5 Water supplies. Water supplies for automatic sprinkler systems shall comply with the fire department interpretation and applications manual.
903.3.6 Hose threads. Fire hose threads and fittings used in connection with automatic sprinkler systems shall be national standard thread (NST).
903.3.7 Fire department connections. The fire department connections shall be located in accordance with section 912 or as approved by the fire code official.
903.3.8 Limited area sprinkler systems. Limited area sprinkler systems shall be in accordance with the fire department interpretation and applications manual.
903.4 Sprinkler system supervision and alarms. Valves controlling the water supply for automatic sprinkler systems shall be installed in accordance with the fire department interpretation and applications manual.
903.5 Testing and maintenance. Sprinkler systems shall be tested and maintained in accordance with Section 901.
903.6 Where required in existing buildings and structures. An automatic sprinkler system shall be provided in existing buildings and structures where required in Chapter 11.
(Code 1972, § 9-207; Ord. No. 1709, § I, 6-4-85; Ord. No. 1925, § 1, 8-31-87; Ord. No. 1974, § 2, 7-20-87; Ord. No. 2308, 9-17-90; Ord. No. 2453, 6-15-92; Ord. No. 2786, §§ 1, 2, 12-18-95; Ord. No. 2939, § 1, 9-30-96; Ord. No. 3100, § 2, 2-17-98; Ord. No. 3507, § 6, 6-17-03; Ord. No. 3738, § 1, 7-10-07; Ord. No. 4045, § 2, 12-4-12, eff. 1-5-13; Ord. No. 4564, § 1, 9-20-22)
Scottsdale Revised Code § 36-18.1 Adoption and Amendments.
Sec. 36-18.1 - Adoption and Amendments.
(a) The 2021 edition of the International Fire Code (2021 IFC), published by the International Code Council, Inc., is adopted by reference. One (1) paper copy and one (1) electronic copy of it shall remain in the office of the city clerk and be open to inspection at all times.
(b) The text of the 2021 edition of the International Fire Code (2021 IFC), is amended only as shown in the following sections ("Scottsdale Amendments"). These Scottsdale Amendments include the addition of two Appendices: O and P. All other provisions remain as specified in the 2021 IFC.
(c) The 2021 edition of the International Fire Code (2021 IFC) and the Scottsdale Amendments shall be known as the "Fire Code of the City of Scottsdale."
CHAPTER 1 ADMINISTRATION
SECTION 101
SCOPE AND GENERAL REQUIREMENTS
101.1 Title is amended to read as follows:
These regulations shall be known as the Fire Code of the City of Scottsdale, hereinafter referred to in the IFC and Chapter 36 of the Scottsdale Revised Code as "this code."
101.2.1 Appendices is amended to read as follows:
Appendices B, C, D, E, F, G, H, I, J, K, M, N, O and P are adopted as part of this code as follows:
1. Appendices O and P are adopted as additional City of Scottsdale appendices to the 2021 IFC.
2. Appendices F, O, and P are adopted as regulatory and enforceable parts of this code.
3. Appendices B, C, D, E, G, H, I, J, K, M and N are adopted as reference guidelines.
SECTION 105
PERMITS
105.6.2, Compressed gases, is amended to add the following Exception to the existing Exceptions in the 2021 IFC:
3. Carbon Dioxide (Inert and simple asphyxiant) shall require a permit for 200 cubic feet or more at NTP.
105.6.15, LP-gas, is amended to read as follows:
105.6.15 LP-gas. A construction permit is required for:
1. Storage and use of LP-gas.
Exception: A permit is not required for individual containers with a 10-gallon (37.85L) water capacity or less serving occupancies in Group R-3.
2. Operation of cargo tankers that transport LP-gas.
3. The removal of underground LP-gas containers or tanks
SECTION 107
FEES
107.2, Schedule of permit fees, is amended to read as follows:
107.2 Fee schedule.
(a) Fees shall be paid in accordance with the City Council adopted fee schedule for charges associated with permitting and inspections, special event staffing, CPR classes, copies of records and reports, and other services provided by the Fire Department.
(b) A schedule of fees is available at the Fire Department's administrative offices and on the City's website.
SECTION 111
MEANS OF APPEALS
111.1, Board of appeals established, is amended to read as follows:
111.1 Board of appeals established. Reference to the "board" or "the board of appeals" in this code shall mean the Building Advisory Board of Appeals as established and referred to in Chapter 31, Article I, Division 2, Section 31-11 of the Scottsdale Revised Code (IBC Section 113). The Board shall hear all appeals of orders, decisions or determinations made by the fire code official to apply and interpret this code. The board shall render all decisions and findings in writing to the appellant with a copy to the fire code official.
SECTION 112
VIOLATIONS
112.4, Violation Penalties, is amended to read as follows:
112.4 Violation Penalties are provided in section 36-19 of the Scottsdale Revised Code.
112.4.1 Abatement of violation. In addition to the imposition of the penalties provided in S.R.C. section 36-19, the fire code official is authorized to institute appropriate action to prevent unlawful construction or to restrain, correct or abate a violation; or to prevent illegal occupancy of a structure or premises; or to stop an illegal act, conduct of business or occupancy of a structure on or about any premises.
CHAPTER 2
DEFINITIONS
SECTION 202
GENERAL DEFINITIONS
(a) The following definitions are added to Section 202:
ACCESS CHALLENGED RESIDENCE. Single family homes with additional challenges including, but not limited to, access, or size, as determined by fire code official.
BIG BOX SINGLE FAMILY RESIDENCE (BB-SFR). Single family residences over 12,000 square foot in area.
LANDLORD. Shall have the meanings given in Arizona Revised Statutes.
MULTIPLE SINGLE-FAMILY. Attached single family dwellings not more than three (3) stories in height with a separate means of egress constructed under the International Residential Code (IRC).
NICET. National Institute for the Certification of Engineering Technologies, 1420 King Street, Alexander, VA 22314-2915.
(b) The definition of "OCCUPANCY CLASSIFICATION" is amended as follows but only for the specified paragraphs. The rest of the definition remains the same.
The introductory paragraph of Institutional Group I-1 is hereby amended as follows:
Institutional Group I-1. Institutional Group I-1 occupancy shall include buildings, structures or portions thereof for more than 10 persons, excluding staff, who reside on a 24-hour basis in a supervised environment and receive custodial care. Buildings of Group I-1 shall be classified as one of the occupancy conditions indicated below and shall comply with Section 420 of the International Building Code. This group shall include, but not be limited to, the following:
Institutional Group I-1 is amended to add the following in alphabetical order to the list following the words "This group shall include, but not be limited to, the following":
Convalescent facilities
The subsection entitled "Six to 16 persons receiving custodial care" within Institutional Group I-1 is hereby amended to read as follows:
Six to 10 persons receiving custodial care. A facility housing not fewer than six and not more than 10 persons receiving custodial care shall be classified as Group R-4.
Residential Group R-1 remains in its entirety except that certain categories are amended as follows:
Boarding houses (transient) with more than 5 occupants.
Congregate living facilities (transient) with more than 5 occupants.
Residential Group R-2 remains in its entirety except that the following category is amended as follows:
Congregate living facilities (non-transient) with more than 5 occupants.
Residential Group R-3 remains in its entirety except that certain categories are amended as follows:
Congregate living facilities (non-transient) with 5 or fewer occupants.
Congregate living facilities (transient) with 5 or fewer occupants.
Lodging houses (transient) with 5 or fewer guestrooms and 5 or fewer occupants.
The subsection entitled "Lodging houses" within Residential Group R-3 is amended as follows:
Lodging houses. Owner-occupied lodging houses with five or fewer guestrooms and 5 or fewer total occupants shall be permitted to be constructed in accordance with the International Residential Code provided that an automatic sprinkler system is installed in accordance with Section 903.3.1.3 or Section P2904 of the International Residential Code.
Residential Group R-4 remains in its entirety except that the introductory paragraph is amended as follows:
Residential Group R-4. Residential Group R-4 occupancies shall include buildings that do not contain more than two dwelling units, structures or portions thereof for more than five but not more than 10 persons excluding staff, who reside on a 24-hour basis in a supervised residential environment and receive custodial care. Buildings of Group R-4 shall be classified as one of the occupancy conditions indicated below. This group shall include, but not be limited to, the following:
(c) The following definitions are added to Section 202:
RENTAL AGREEMENT. Shall have the meanings given in Arizona Revised Statutes.
TENANT. Shall have the meanings given in Arizona Revised Statutes.
UNIFORM TRAFFIC COMPLAINT. The form approved by the State Supreme Court in their "Rules of Procedure in Civil Traffic Violation cases".
CHAPTER 3
GENERAL REQUIREMENTS
SECTION 308
OPEN FLAMES
308.1.4, Open-flame cooking devices, is retitled and amended to read as follows:
308.1.4 Open-flame devices. Charcoal burners, chimineas, barbecues fixed or portable, open flame heaters, firepots and other open-flame devices are prohibited on combustible balconies or within 10 feet (3048 mm) of combustible construction.
Exceptions:
1. One- and two-family dwellings.
2. When all of the following conditions are met:
a. Where buildings including garages, balconies and decks are protected by an automatic sprinkler system,
b. Device(s) is/are fueled by natural gas or LP-gas
c. LP-gas portable tank having a water capacity not greater than 5 gallons.
CHAPTER 4
EMERGENCY PLANNING AND PREPAREDNESS
SECTION 403
EMERGENCY PREPAREDNESS REQUIREMENTS
403.9, Group R Occupancies, is amended by adding a new subsection 403.9.4 and amending the introductory paragraph to read as follows:
403.9 Group R Occupancies. Group R Occupancies shall comply with Sections 403.9.1 through 403.9.4.
Add a new section 403.9.4 to read as follows:
403.9.4 Group R-3 group care home/assisted living facility. An approved fire safety evacuation plan in accordance with section 404 shall be prepared and maintained for Group R group care home/assisted living occupancies.
CHAPTER 5
FIRE SERVICE FEATURES
SECTION 503
FIRE APPARATUS ACCESS ROADS
503.2, Specifications, is amended to read as follows:
503.2 Specifications. Fire apparatus access roads shall be installed and arranged in accordance with Sections 503.2.1 through 503.2.8 and the Scottsdale Design Standards and Policies Manual (DS&PM).
503.2.1, Dimensions, is amended to read as follows, including the addition of a new subsection 503.2.1.1:
503.2.1 Dimensions. Fire apparatus access roads shall have an unobstructed width of not less than 24 feet (7315 mm) except for approved security gates in accordance with Section 503.6, and an unobstructed vertical clearance of not less than 13 feet 6 inches (4115 mm).
503.2.1.1 Temporary fire department access. Temporary fire department access roadway prior to and during construction of every facility, building or portion of a building shall install and maintain a roadway 16'-0" (4,877mm) wide, with minimum 0'-4" (101.6mm) thickness of aggregate base course or decomposed granite compacted to a 90% density where natural soil will not meet compaction requirements.
503.2.4, Turning radius, is amended to read as follows:
503.2.4 Turning radius. The required turning radius of a fire apparatus access road shall be determined by the fire code official and the Scottsdale DS&PM.
503.2.7, Grade, is amended to read as follows:
503.2.7 Grade. The grade of the fire apparatus access road shall be within the limits established by the fire code official based on the fire department's apparatus and Scottsdale DS&PM.
503.3, Marking, is amended to read as follows:
503.3 Marking. Where required by the fire code official, approved signs or other approved notices shall be provided for fire apparatus access roads (fire lanes) to identify such roads or prohibit the obstruction thereof on public and private property. Signs or notices shall be maintained in a clean and legible condition at all times and shall be replaced or repaired when necessary to provide adequate visibility. All fire lanes shall be marked in the following manner:
1. Fire lane signs per City of Scottsdale standard detail, and/or
2. Curb, street or driveway painted red to indicate fire lane and labeled "FIRE LANE NO PARKING" in white block letters 3 inches (76.2mm) in height, ¾ in. (19.5 mm) stroke, on the vertical face of the curb to indicate fire lane.
3. Lettering shall not be greater than 50'-0" (15.24m) apart and shall be posted at the beginning and end of the fire lane.
It shall be unlawful for any vehicle, equipment or device to park in or block the fire lane. Any vehicle, equipment or device found parked in or blocking a fire lane shall be cited by the police or the fire department.
503.4, Obstruction of fire apparatus access roads, is amended to read as follows, including the addition of a new subsection 503.4.2:
503.4 Obstruction of fire apparatus access roads. Fire apparatus access roads shall not be obstructed in any manner, including the parking of vehicles. The minimum widths and clearances established in Section 503.2.1 shall be maintained at all times.
503.4.2 Traffic control spikes. Traffic control spike or similar devices that immobilize a vehicle shall be prohibited.
503.6, Security gates, is amended by adding the following subsections to read as follows:
503.6.1 Key switch and sensor pre-emption location. A key switch and pre-emption sensor shall be required on all electric entry control gates. Key switch shall be installed in a location on the gate control panel that is readily visible and accessible. The pre-emption sensor shall be at or behind the gate.
EXCEPTION: Single Family Residence: A pre-emption sensor is optional.
503.6.2 Manual gates. An approved dual padlock locking system shall be used on manual gates. An approved Fire Department Knox padlock shall be used on one side and the owners/management on the other.
503.6.3 Retro-fit of security gates. The installation of a key switch and pre-emption sensor shall be required on all existing electric entry-controlled security gates across a fire apparatus access road. All gates shall be in compliance on or before July 1, 2014.
SECTION 505
PREMISES IDENTIFICATION
505.1, Address identification, is replaced with new section 505.1 and subsection 505.1.1 to read as follows:
505.1 Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. Address numbers shall be Arabic numerals or alphabet letters. Address and building numbers for commercial properties shall be a minimum of 12 inches (305 mm) high with a minimum stroke width of 2.0 inches (51 mm). Units within a building shall be a minimum of 6 inches (152 mm) high with a minimum stroke width of 1.0 inch (25.4 mm). Individual unit or suite numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). One and two family dwelling shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). Where access is by means of a private road and the building cannot be viewed from the public way, a monument, pole or other sign or means shall be used to identify the structure. Address numbers shall be maintained.
505.1.1 Interior room numbers. New and existing buildings shall have an approved room and suite numbers identification placed in positions that are plainly legible and visible. Numbers shall contrast with their background; interior suite and room numbers shall be Arabic numeral or alphabet letters. Interior room and suite numbers shall be a minimum of 1.25 (1¼) inches (31.75 mm) high with a brush stroke width of 0.25 (¼) inches (6.35 mm).
SECTION 506
KEY BOXES
506.1, Where required, is amended to read as follows:
506.1 Where required. A key box shall be required on all commercial structures that contain off-site monitored fire systems or where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes. The fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type listed in accordance with UL 1037, and shall contain keys to gain necessary access as required by the fire code official.
1. The first key box shall be installed at the main entrance of the structure. Additional key boxes may be required based on the size, layout, and location of fire sprinkler riser room. (Example: strip malls may have one centered on the front and at the riser room; large office, warehouses and big box retail buildings would have boxes at the main entry, rear or additional entry and the riser room.)
2. The key box shall be installed between 4'-0" (1.219 m) to 6'-0" (1.829 m) above finished grade. The key box shall be immediately visible to fire personnel from the emergency apparatus. Posts, fences, vehicles, vegetation, trash, storage and other materials shall not be placed or kept near the key boxes in a manner that would prevent the key boxes from being immediately discernible.
SECTION 507
FIRE PROTECTION WATER SUPPLIES
507.4, Water supply test, is amended to read as follows:
507.4 Water supply test. Testing of water supply system shall comply with the procedures in the Scottsdale DS&PM.
507.5, Fire hydrant systems, is amended to read as follows:
507.5 Fire hydrant systems. Fire hydrant systems shall comply with Sections 507.5.1 through 507.5.8.
507.5.1, Where required, is amended by adding new subsections 507.5.1.2, Hydrant spacing, and 507.5.1.3, Dead ends, to read as follows:
507.5.1.2 Hydrant spacing. Fire hydrants shall be spaced on fire apparatus access roads as follows:
1. Commercial, multi-family (R-1 and R-2) and multiple single-family development hydrant spacing will be a maximum of 700 feet (213,360mm) on center.
2. Non-hillside. One- and two-family dwellings (IRC and R-3) development hydrant spacing will be a maximum of 1,200 feet (365,760mm) on center.
3. Hillside. One- and two-family dwellings (IRC and R-3) development hydrant spacing will be a maximum of 600 feet (182,880mm) on center.
507.5.1.3 Dead ends. On cul-de-sacs in residential and commercial developments the maximum distance to a hydrant shall not exceed one half (½) of the maximum allowable distance between fire hydrants designated in 507.5.1.2.
Section 507.5, Fire hydrant systems, is amended by adding new subsections 507.5.7, 507.5.7.1, and 507.5.8, to read as follows:
507.5.7. Fire hydrant color. All fire hydrants shall have aboveground barrels painted with a primer coat plus two (2) coats of OSHA yellow paint.
507.5.7.1 Reclaimed water fire hydrant color. All fire hydrants using a reclaimed water supply shall have the caps and bonnet painted with a prime coat plus two (2) coats of purple paint. A placard shall be affixed to the hydrant in English and Spanish "DO NOT DRINK WATER."
507.5.8 Reflective markers. All fire protection equipment, fire department connections and hydrants shall be clearly identified by installation of reflective blue markers and comply with the City of Scottsdale supplement to MAG Uniform Standard Details for Public Works Construction, standard, detail 2363.
SECTION 508
FIRE COMMAND CENTER
508.1.1, Location and access, is amended to read as follows:
508.1.1 Location and access. The fire command center shall be in a location that is easily identifiable and accessible from the main lobby of the building and provide quick access to the building tower stairways. The location and accessibility of the fire command center shall be approved by the fire chief.
508.1.3, Size, is amended to read as follows:
508.1.3 Size. The fire command center shall be a minimum of 96 square feet (8.91m 2 ) in area with a minimum dimension of 8 feet (2438 mm).
SECTION 510
EMERGENCY RESPONDER COMMUNICATION COVERAGE
510.1, Emergency responder communication coverage in new buildings, is amended by adding a new the following new subsection 510.1.1 to read as follows:
510.1.1 City of Scottsdale Radio Engineer. The fire code official may designate the City of Scottsdale Radio Engineer as the Authority having jurisdiction for purposes of this section.
CHAPTER 6
BUILDING SERVICES AND SYSTEMS
SECTION 604
ELEVATOR OPERATION,
MAINTENANCE AND FIRE SERVICE KEYS
604.2, Emergency operation, is amended by adding the following new subsection to read as follows:
604.2.1 Elevator car to accommodate ambulance stretcher. Where elevators are provided in buildings four or more stories above grade plane or four or more stories below grade plane, at least one elevator shall be provided for fire department emergency access to all floors. Elevators designated as emergency access shall be of such a size and arrangement to accommodate an ambulance stretcher 24 inches by 84 inches (610 mm by 2134 mm) with not less than 5-inch (127 mm) radius corners, in the horizontal, open position and shall be identified by the international symbol for emergency medical services (star of life). The symbol shall not be less than 3 inches (76 mm) high and shall be placed inside on both sides of the hoist way door frame.
SECTION 605
FUEL-FIRED APPLIANCES
605.4.1, Fuel oil storage in outside, above-ground tanks, is amended to read as follows:
605.4.1 Fuel oil storage in outside, above-ground tanks. Where connected to a fuel-oil piping system, the maximum amount of fuel oil storage allowed outside above ground without additional protection shall be 660 gallons (2498 L). The storage of fuel oil above ground in quantities exceeding 660 gallons (2498 L) may be approved by special permit by the fire code official.
605.4.2.2, Quantity limits for fuel oil storage inside buildings, is amended to read as follows:
605.4.2.2 Quantity limits. One or more fuel oil storage tanks containing Class II or III combustible liquid shall be permitted in a building. The aggregate capacity of all tanks shall not exceed the following:
1. 660 gallons (2498 L) in sprinklered buildings, where stored in a tank complying with UL 142 or UL 2085.
CHAPTER 9
FIRE PROTECTION AND LIFE SAFETY SYSTEMS
SECTION 901
GENERAL
901.2, Construction documents, is amended to read as follows and to add the following subsections 901.2.1 - 901.2.4:
901.2 Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
901.2.1 Plan certification for fire alarm systems and occupant notification. All fire monitoring and occupant notification system plans submitted to the fire department for review and approval shall bear a qualified registrant's seal or review certification of a minimum level III in Fire Alarms Systems from the National Institute for the Certification of Engineering Technologies (NICET).
901.2.2 Plan certification for fire sprinkler systems. All fire sprinkler plans submitted to the fire department for review and approval shall bear a qualified registrant's seal or review certification of a minimum level III NICET in Water Based Systems Layout (National Institute for the Certification of Engineering Technologies), in accordance with fire department Interpretation and Applications Manual.
901.2.3 Plan certification for all other fire protection systems. Plan certification for all other fire protection systems will be accompanied by a certification of competence when required.
901.2.4 On-site plans. Plans and specifications shall be submitted to the fire department for review and approval prior to construction. One set of fire department approved plans shall be on the job site for each inspection.
SECTION 903
AUTOMATIC SPRINKLER SYSTEMS
Section 903 is amended by repealing the existing provisions and substituting the following:
903.1 General. Automatic sprinkler systems shall comply with Section 36-18 of the Scottsdale Revised Code.
SECTION 905
STANDPIPE SYSTEMS
905.3.4, Stages, is amended to read as follows, including the deletion of the Exception and subsection 905.3.4.1:
905.3.4 Stages. Stages greater than 1,000 square feet in area (93 m 2 ) shall be equipped with a Class I wet standpipe system with 2.5 inch (64 mm) hose connections on each side of the stage supplied from the automatic fire sprinkler system and shall have a flow rate of not less than that required for class 1 standpipes.
Section 905 is amended by adding the following section 905.13 to read as follows:
905.13. Hose connections for access challenges. Buildings exceeding 10,000 square feet (929 m 2 ) in area per story or when the exterior ground floor walls exceed the required distance from fire apparatus access roads not otherwise required to be equipped with a standpipe system by section 905.3 of the 2021 IFC, shall be equipped with class I manual hose connections (2-1/2" NST) for fire department use as follows:
(1) The locations shall be in accordance with Scottsdale Revised Code, NFPA 13, and 2021 IFC sec. 905.4, except item 1. 905.4, item 1 locations shall be at each floor-level landing, including grade level, within enclosed stairways, rather than located at intermediate floor level landings.
(2) Single story structures are not required to have hose connections except in those interior portions of the building that exceed 200 feet (60.96 m) of travel from an emergency access road.
(3) Where the most remote portion of a floor or story is more than 200 feet from a hose connection, additional hose connections are required.
(4) The hose connections may be combined with the fire sprinkler system and sized to deliver 250 gallons per minute at 100 psi from the most hydraulically remote outlet, using 150 psi fire department pump-in pressure. Calculations for hose demand shall be submitted with sprinkler plans.
SECTION 906
PORTABLE FIRE EXTINGUISHERS
906.1, Where required, is amended by amending subpoint 1 to add R-3 Residential Care/Assisted Living Facilities; and amending subpoint 1 of Exception 1 to read as follows, with the remaining portions of Section 906.1 remaining as in the 2021 IFC, including the Exceptions 2 and 3 and subpoints 2 through 6:
906.1 Where required. Portable fire extinguishers shall be installed in all the following locations:
1. In new and existing Group A, B, E, F, H, I, M, R-1, R-2, R-3 Residential Care/Assisted Living Facilities, R-4 and S occupancies
Exceptions:
1. In Group R-2 occupancies, portable fire extinguishers shall be required only in locations specified in Items 2 through 6.
SECTION 907
FIRE ALARM AND DETECTION SYSTEMS
907.2, Where required—new buildings and structures, is amended to read as follows, with the remaining portions of Section 907.2 remaining as in the 2021 IFC, including the Exceptions to 907.2 and subsections 907.2.1 through 907.2.23:
907.2 Where required—new buildings and structures. An approved manual, automatic or manual and automatic fire alarm system installed in accordance with the provisions of this code and NFPA 72 shall be provided in new buildings and structures in accordance with Sections 907.2.1 through 907.2.23 and fire department Interpretation and Applications Manual, and provide occupant notification in accordance with Section 907.5, unless other requirements are provided by another section of this code.
Not fewer than one manual fire alarm box shall be provided in an approved location to initiate a fire alarm signal for the fire alarm system employing automatic fire detectors or waterflow detection devices. Where other sections of this code allow elimination of the alarm boxes due to sprinklers, a single fire alarm box shall be installed.
Section 907.7, Acceptance tests and completion, is amended by adding a new subsection 907.7.4 Activation, to read as follows:
907.7.4 Activation. Where an alarm notification system is required by another section of this code, it shall be activated by:
1. Required automatic fire alarm system.
2. Sprinkler water-flow devices.
a. Multi-level structures: All multilevel structures are required to have a flow switch and tampered control valve per floor. See fire department Interpretation and Applications Manual.
3. Required manual fire alarm boxes.
SECTION 912
FIRE DEPARTMENT CONNECTIONS
912.1, Installation, is amended to read as follows:
912.1 Installation. Fire department connections shall be installed in accordance with the NFPA standard applicable to the system design and shall comply with Sections 912.2 through 912.7 and the City of Scottsdale fire department's Interpretation and Applications Manual.
912.2, Location, is amended by adding the following new subsections 912.2.3 and 912.2.4 to read as follows:
912.2.3 Remote Fire Department Connections. Remote fire department connections shall be located within four feet (1219.2mm) to eight feet (2438.4mm) of the curb line of an access road or public street, or as otherwise specified. The fire department connection line shall be a wet line with the check valve at the hose connection above grade.
912.2.4 Wall Mounted Fire Department Connections. Wall mounted fire department connections are permitted on systems not over ordinary hazard Group 2, when:
1. There are no glazed structural openings within 5 feet (1524mm) horizontally from inlet connection.
2. The structure is not classified as an "H" occupancy.
3. The fire department connection is within 50 feet of an approved roadway or driveway and arranged so that hose lines can be readily attached to the inlets without interference from any nearby objects including buildings, fences, post, plantings or other fire department connections or as approved by the fire code official (see fire department Interpretation and Applications Manual).
CHAPTER 10
MEANS OF EGRESS
SECTION 1004
OCCUPANT LOAD
1004.9, Posting of occupant load, is amended to read as follows:
1004.9 Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be maintained by the owner or authorized agent. The number of people occupying the room shall not exceed the maximum occupant load as posted on the sign pursuant to Section 109.6 of the 2021 IFC. The sign shall be as approved by City of Scottsdale Fire & Building Department.
CHAPTER 11
CONSTRUCTION REQUIREMENTS FOR EXISTING BUILDINGS
SECTION 1103
FIRE SAFETY REQUIREMENTS FOR EXISTING BUILDINGS
1103.5, Sprinkler systems, shall be amended by adding a new subsection 1103.5.6 and amending the introductory paragraph to read as follows:
1103.5 Sprinkler systems. An automatic sprinkler system shall be provided in existing buildings in accordance with section 1103.5.1 through 1103.5.6.
Subsection 1103.5.6, Group R-4, is added to read as follows:
1103.5.6 Group R-4. An automatic sprinkler system shall be installed in accordance with Scottsdale Revised Code 36-18.
1103.8.1, Where required, is amended by adding two new subsections 1103.8.1.1 and 1103.8.1.2 to read as follows:
1103.8.1.1 Owner landlord and occupant responsibilities. Devices provided and maintained. In a dwelling unit occupied under the terms of a rental agreement or under a month-to-month tenancy:
1. At the time of each occupancy the landlord shall provide smoke detection devices in working condition and, after written notification by the tenant, shall be responsible for replacement; and
2. The tenant shall keep the devices in working condition by keeping charged batteries in battery-operated devices, by testing the devices periodically, and by refraining from permanently disabling the devices.
1103.8.1.2 Records and maintenance. The landlord or owner of any rental property shall inspect all smoke detection devices as required under NFPA 72 annually and a record of all inspections and maintenance activities shall be kept by the landlord or owner and available for inspection upon request by fire code official. See fire department Interpretation and Applications Manual.
CHAPTER 12
ENERGY SYSTEMS
SECTION 1207
ELECTRICAL ENERGY STORAGE SYSTEMS (ESS)
1207.1.4, Hazard mitigation analysis, is amended to add the following subsection 1207.1.4 (4) to read as follows:
4. When required by the fire code official.
1207.3.4, Energy storage management system, is amended to add the following subsections 1207.3.4 (1) and 1207.3.4 (2) to read as follows:
1. The system shall transmit an alarm signal to an approved location and to an approved annunciator panel if potentially hazardous temperatures or other conditions such as short circuits, over voltage or under voltage are detected.
2. The approved annunciator panel shall visibly indicate any hazardous temperature or other conditions. The location of the annunciator panel shall be approved by the fire code official.
1207.4, General installation requirements, is amended to add the following subsection 1207.4.13 to read as follows:
1207.4.13 Testing, maintenance and repair. Storage batteries and associated equipment and systems shall be tested and maintained in accordance with the manufacturer's instructions. Any storage batteries or system components used to replace existing units shall be compatible with the battery charger, energy management systems, other storage batteries and other safety systems. Introducing other types of storage batteries into the stationary storage battery system or other types of electrolytes into flow battery systems shall be treated as a new installation and require approval by the fire code official before the replacements are introduced into service.
1207.6, Electrochemical ESS technology-specific protection, is amended to add the following subsection 1207.6.6 to read as follows:
1207.6.6 Emergency energy release. An approved means must be provided to safely release stored energy from the batteries in an emergency situation.
1207.11, ESS in Group R-3 and R-4 occupancies, remains in its entirety with amendments as follows in sections 1207.11.3 (4) and 1207.11.4:
1207.11.3 Location. ESS shall be installed only in the following locations:
. . . .
4. Other locations with the approval of the fire code official.
1207.11.4 Energy ratings. Individual ESS units shall have a maximum rating of 20 kWh. The aggregate rating structure shall not exceed:
1. 80 kWh in attached or detached garages and detached accessory structures.
2. 80 kWh on exterior walls.
3. 80 kWh outdoors on the ground.
CHAPTER 23
MOTOR FUEL-DISPENSING FACILITIES AND REPAIR GARAGES
SECTION 2301 GENERAL
2301.4, Indoor motor fuel-dispensing facilities, and its subsection, is amended to read as follows:
2301.4 Indoor motor fuel-dispensing facilities. Motor fuel-dispensing facilities located inside buildings are prohibited.
Section 2301 is amended to add the following new section 2301.7 to read as follows:
2301.7 Fire Protection. Fire sprinkler protection shall be designed in accordance with the building code as required for minimum Ordinary Group Hazard 2.
SECTION 2304
DISPENSING OPERATIONS
2304.3, Unattended self-service motor fuel-dispensing facilities, is amended to read as follows:
2304.3 Unattended self-service motor fuel-dispensing facilities. Unattended self-service motor fuel-dispensing facilities are prohibited.
Exception: Unattended self-serve stations may be allowed by special permit by the fire code official for private commercial use only. Written request and documentation shall be submitted showing compliance with two (2) way communications and cameras that are monitored off site at a 24 hour location and shall comply with subsections 2304.3.1 through 2304.3.7 and all other applicable codes and ordinances.
Subsections 2304.3.1 through 2304.3.7 remain as written in the 2021 IFC.
SECTION 2306
FLAMMABLE AND COMBUSTIBLE
LIQUID MOTOR FUEL-DISPENSING FACILITIES
2306.2.2, Above-ground tanks located inside buildings, is amended to read as follows:
2306.2.2 Above-ground tanks located inside buildings. Above-ground tanks, located inside buildings and used for the storage of Class I, II and IIIA liquid fuels, are prohibited.
2306.2.3, Above-ground tanks located outdoors, above grade, is amended to read as follows:
2306.2.3 Above-ground tanks located outdoors, above grade. Above-ground tanks shall not be used for the storage of Class I, II or IIIA liquid motor fuels.
Exception: Installation of 2000 gallons (7,570.8L) or less aggregate quantity may be approved by special permit by fire code official.
CHAPTER 53
COMPRESSED GASSES
SECTION 5307
COMPRESSED GASES
NOT OTHERWISE REGULATED
Section 5307.3, Insulated liquid carbon dioxide systems used in beverage dispensing applications, remains as in the 2021 IFC., except as amended below.
Subsection 1 under Section 5307.3.2, Gas detection systems, is amended to read as follows:
1. Activates an audible and visible supervisory alarm at a normally attended location upon detection of a carbon dioxide concentration of 15,000 parts per million (27,000 mg/m 3 ).
Section 5307.3 is amended by adding a new subsection 5307.3.3 to read as follows:
5307.3.3 Alarm monitoring and power supply. Emergency alarm system shall be monitored and powered by the buildings alarm/monitoring system where an alarm notification system is required by another section of this code.
Exception: If no building alarm system exists or is required by another section of this code, a gas detection device or system shall have a 90-minute backup power supply.
CHAPTER 57
FLAMMABLE AND COMBUSTIBLE LIQUIDS
5704.2.9.5, Above-ground tanks inside of buildings, and its subsections, is replaced with the following:
5704.2.9.5 Above-ground tanks inside buildings. Above-ground tanks inside of buildings are prohibited.
5704.2.9.6, Above-ground tanks outside of buildings, and its subsections, is replaced with the following:
5704.2.9.6. Above-ground tanks outside of buildings. Above-ground tanks outside of buildings including gravity discharge tanks are prohibited.
Exception: Installations of 2000 gallons (7,570.8L) or less aggregate quantity may be approved by special permit application by fire code official.
5704.2.13.1.4, Tanks abandoned in place, and its subsections, is replaced with the following:
5704.2.13.1.4 Tanks abandoned in place. Tanks abandoned in place shall be prohibited within the entire city.
CHAPTER 61
LIQUEFIED PETROLEUM GASES
SECTION 6104
LOCATION OF LP-GAS CONTAINERS
6104.3, Container location, is hereby amended by substituting the following for footnote e to Table 6104.3:
e. The following shall apply to above-ground containers installed alongside buildings:
1. Containers of less than a 125-gallon water capacity are allowed next to the building they serve when in compliance with Items 2, 3 and 4.
2. Department of Transportation (DOT) specification containers shall be located and installed so that the discharge from the container pressure relief device is at least 3 feet horizontally from building openings below the level of such discharge and shall not be beneath buildings unless the space is well ventilated to the outside and is not enclosed for more than 50 percent of its perimeter. The discharge from container pressure relief devices shall be located not less than 5 feet from exterior sources of ignition, openings into direct-vent (sealed combustion system) appliances or mechanical ventilation air intakes.
3. ASME containers of less than a 125-gallon water capacity shall be located and installed such that the discharge from pressure relief devices shall not terminate in or beneath buildings and shall be located at least 5 feet horizontally from building openings below the level of such discharge and not less than 5 feet from exterior sources of ignition, openings into direct vent (sealed combustion system) appliances, or mechanical ventilation air intakes.
4. The filling connection and the vent from liquid-level gauges on either DOT or ASME containers filled at the point of installation shall not be less than 10 feet from exterior sources of ignition, openings into direct vent (sealed combustion system) appliances or mechanical ventilation air intakes.
5. A container less than 125 gallons (473.2l) may be located next to a block fence when the tank is not within 5 feet (1524mm) of a structure on adjoining property.
CHAPTER 80
REFERENCED STANDARDS
For purposes of this Fire Code, the applicable National Fire Protection Association (NFPA) referenced standards shall be those standards in effect on the date the 2021 edition of the International Fire Code was adopted by the City of Scottsdale.
APPENDIX O
SECTION O101
GENERAL
O101.1 Scope. The unrestricted use of grass-, grain-, brush- or forest-covered land in hazardous fire areas is a potential menace to life and property from fire and resulting erosion. Safeguards to prevent the occurrence of fire and provide adequate fire-protection facilities to control the spread of fire which might be caused by recreational, residential, commercial, industrial, or other activities conducted in hazardous fire areas shall be in accordance with Appendix O.
SECTION O102
DEFINITIONS
O102.1 Definitions. For the purpose of Appendix O, certain terms are defined as follows:
Tracer is any bullet or projectile incorporating a feature which marks or traces the flight of said bullet or projectile by flame, smoke or other means which result in fire or heat.
Tracer charge is any bullet or projectile incorporating a feature designed to create a visible or audible effect which result in fire or heat and shall include any incendiary bullets or projectiles.
SECTION O103
PERMITS
O103.1 Permits. Fire code official is authorized to stipulate conditions for permits. Permits shall not be issued when public safety would be at risk, as determined by fire code official.
SECTION O104
RESTRICTED ENTRY
O104.1 Restricted entry. Fire code official shall determine and publicly announce when hazardous fire areas shall be closed to entry and when such areas shall again be opened to entry. Entry on and occupation of hazardous fire areas, except public roadways, inhabited areas or established trails and campsites which have not been closed during such time when the hazardous fire is closed to entry, is prohibited.
Exceptions:
1. Residents and owners of private property within hazardous fire areas and their invitees and guests going to or being upon their land.
2. Entry, in the course of duty, by peace or police officer, and other duly authorized public officers, members of a fire department and members of the United States forest service.
SECTION O105
TRESPASSING ON POSTED PROPERTY
O105.1 General. When fire code official determines that a specific area within a hazardous fire area presents an exceptional and continuing fire danger because of the density of natural growth, difficulty of terrain, proximity to structures or accessibility to public, such areas shall be closed until changed conditions warrant termination of closure. Such areas shall be posted as hereafter provided.
O105.2 Signs. Approved signs prohibiting entry by unauthorized persons and referring to Appendix O shall be placed on every closed area.
O105.3 Trespassing. Entering and remaining within areas closed and posted is prohibited.
Exception: Owners and occupiers of private or public property within closed and posted areas, their guest or invitees, and local state and federal public officers and their authorized agents acting in the course of duty.
SECTION O106
SMOKING
O106.1 General. Lighting, igniting or otherwise setting fire to or smoking tobacco, cigarettes, pipes or cigars in hazardous fire areas is prohibited.
Exception: Places of habitation or within the boundaries of established smoking areas or campsites as designated by fire code official.
SECTION O107
SPARK ARRESTERS
O107.1 Spark arresters. Chimneys used in conjunction with fireplaces, barbecues, incinerators or heating appliances in which solid or liquid fuel is used, upon buildings, structures or premises located within 200 feet (60 960 mm) of hazardous fire areas, shall be provided with a spark arrester constructed with heavy wire mesh or other noncombustible material with openings not to exceed ½ inch (12.7mm).
SECTION O108
TRACER BULLETS, TRACER CHARGES,
DISCHARGE OF FIREARMS, ROCKETS AND MODEL AIRCRAFT.
O108.1 General. Tracer bullets and tracer charges shall not be possessed, fired or caused to be fired into or across hazardous fire areas.
Firearms, rockets, model planes, gliders and balloons powered with an engine, propellant or other features liable to start or cause fire shall not be fired or projected into or across hazardous fire areas.
SECTION O109
EXPLOSIVES AND BLASTING
O109.1 Explosives and blasting. Explosives shall not be possessed, kept, stored, sold, offered for sale, given away, used, discharged, transported or disposed of within hazardous fire areas except by permit from fire code official.
SECTION O110
FIREWORKS
O110.1 Fireworks. Fireworks shall not be used or possessed in hazardous fire areas. Fire code official is authorized to seize, take, remove or cause to be removed fireworks in violation of section 110.
SECTION O111
APIARIES
O111.1 Apiaries. Lighted and smoldering material shall not be used in connection with smoking bees in or upon hazardous fire areas except by permit from fire code official.
SECTION O112
OPEN-FLAME DEVICES
O112.1 Open-flame devices. Welding torches, tar pots, decorative torches, sky lanterns and other devices, machines or processes liable to start or cause fire shall not be operated or used in or upon hazardous fire areas, except by permit from fire code official.
Exception: Use within habited premises or designated campsites which are a minimum of 30 feet (9144 mm) from grass-, grain-, brush-, or forest-covered areas.
O112.2 Flame-employing devices. Flame-employing devices, such as lanterns or kerosene road flares, shall not be operated or used as a signal or marker in or upon hazardous fire areas.
Exception: The proper use of fuses at the scene of emergencies or as required by standard operating procedures.
SECTION O113
OUTDOOR FIRES
O113.1 Outdoor fires. Outdoor fires shall not be built, ignited, or maintained in or upon hazardous fire areas, except by permit from fire code official.
Exception: Outdoor fires within habited premises or designated campsites where such fires are built in a permanent barbecue, portable barbecue, outdoor fireplace, incinerator, or grill and are a minimum of 30 feet (9144 mm) from a grass-, grain-, brush-, or forest-covered area.
Permits shall incorporate such terms and conditions which will reasonably safeguard public safety and property. Outdoor fires shall not be built, ignited, or maintained in or upon hazardous fire areas under the following conditions:
1. When high winds are blowing,
2. When a person aged 17 or over is not present at all times to watch and tend fire, or:
3. When public announcement is made that open burning is prohibited.
4. Permanent barbecue, portable barbecues, outdoor fireplaces, or grills shall not be used for the disposal of rubbish, trash or combustible waste material.
SECTION O114
INCINERATORS AND FIREPLACES
O114.1 General: Incinerators, outdoor fireplaces, permanent barbecues, and grills shall not be built, installed, or maintained in hazardous fire areas without prior approval of fire code official.
Incinerators, outdoor fireplaces, permanent barbecues, and grills shall be maintained in good repair and in a safe condition at all times. Openings in such appliances shall be provided with an approved spark arrester, screen, or door.
Exception: When approved, unprotected openings in barbecues and grills are necessary for proper function.
SECTION O115
CLEARANCE OF BRUSH AND VEGETATIVE GROWTH FROM ELECTRICAL TRANSMISSION LINES
O115.1 General. Clearance of brush and vegetative growth from electrical transmission lines shall be in accordance with Section 115.
Exception: Section 115 does not authorize persons not having legal right of entry to enter upon or damage the property of others without consent of the owner.
O115.2 Support clearance. Persons owning, controlling, operating or maintaining electrical transmission lines upon hazardous fire areas shall, at all times, maintain around and adjacent to poles supporting a switch, fuse, transformer, lightning arrester, line junction, dead end, corner pole, towers, or other poles or towers at which power company employees are likely to work most frequently an effective firebreak consisting of a clearing or not less than 10 feet (3048 mm) in each direction from the outer circumference of such pole of tower.
Exception: Lines used exclusively as telephone, telegraph, messenger call, alarm transmission or other lines classed as communication circuits by a public utility.
O115.3 High tension line clearance. Persons owning, controlling, operating, or maintaining electrical transmission lines upon hazardous fire areas shall maintain the clearance specified in Section 115.3 in all directions between vegetation and conductors carrying electrical current:
1. For lines operating at 2,400 volts and less than 68,000 volts, 4 feet (1219 mm).
2. For lines operating at 68,000 volts and less than 110,000 volts, 6 feet (1829 mm).
3. For lines operating at 110,000 volts and over, 10 feet (3048 mm).
Such distance shall be sufficiently great to furnish the required clearance from the particular wire or conductor to positions of such wire or conductor at temperatures of 120 F (48.9 C) or less. Forked, dead, old, decadent and rotten trees; trees weakened by decay or disease; and trees leaning toward the line, which could contact the line from the side or fall on the line, shall be felled, cut or trimmed to remove the hazard.
O115.4 Self-supporting aerial cable. Line clearance is not required for self-supporting aerial cable, except that forked trees, leaning trees and other growth which could fall across the cable and break it shall be removed.
SECTION O116
CLEARANCE OF BRUSH OR VEGETATION GROWTH FROM STRUCTURES
O116.1 General. Persons owning, leasing, controlling, operating or maintaining buildings or structures in, upon or adjoining hazardous fire areas, and persons owning, leasing or controlling land adjacent to such buildings or structures, shall at all times:
1. Maintain an effective firebreak by removing and clearing away flammable vegetation and combustible growth from areas within 30 feet (9144 mm) of such buildings or structures.
Exception: Single specimens of trees, ornamental shrubbery or similar plants used as ground covers, provided that they do not form a means of rapidly transmitting fire from the native growth to any structure.
2. Maintain additional fire protection or firebreak by removing brush, flammable vegetation and combustible growth located from areas within 30 feet to 100 feet (9144 mm to 30 480 mm) from such buildings or structures, when required by fire code official because of extra-hazardous conditions causing a firebreak of only 30 feet (9144 mm) to be insufficient to provide reasonable fire safety.
Exception: Grass and other vegetation located more than 30 feet (9144 mm) from buildings or structures and less than 18 inches (457 mm) in height above the ground need not be removed where necessary to stabilize the soil and prevent erosion.
3. Remove portions of trees which extend within 10 feet (3048 mm) of the outlet of a chimney.
4. Maintain trees adjacent to or overhanging a building free of deadwood; and
5. Maintain the roof of a structure free of leaves, needles, or other dead vegetative growth.
O116.2 Corrective actions. The executive body is authorized to instruct fire code official to give notice to the owner of the property upon which conditions regulated by Section 116.1 exist to correct such conditions. If the owner fails to correct conditions, the executive body is authorized to cause the same to be done and make the expense of such correction a lien upon the property where such condition exists.
SECTION O117
CLEARANCE OF BRUSH OR VEGETATION GROWTH FROM ROADWAYS
O117.1 Clearance of brush or vegetation. Fire code official is authorized to cause areas within 10 feet (3048 mm) on each side of portions of highways and private streets which are improved, designed, or ordinarily used for vehicular traffic to be cleared of flammable vegetation and other combustible growth. Fire code official is authorized to enter upon private property to do so.
Exception: Single specimens of trees, ornamental shrubbery, or cultivated ground such as green grass, ivy, succulents or similar plants used as ground cover, provided that they do not form a means of readily transmitting fire.
SECTION O118
UNUSUAL CIRCUMSTANCES
O118.1 Unusual circumstances. If fire code official determines that difficult terrain, danger of erosion or other unusual circumstances make strict compliance with the clearance of vegetation provisions of Sections 115, 116, or 117 of Appendix O undesirable or impractical, enforcement thereof may be suspended, and reasonable alternative measures shall be provided.
SECTION O119
DUMPING
O119.1 Dumping. Garbage, cans, bottles, papers, ashes, refuse, trash, or rubbish or combustible waste material shall not be placed, deposited or dumped in or upon hazardous fire areas, in or upon or along trails, and roadways or highways in hazardous fire areas.
Exception: Approved public and private dumping areas.
SECTION O120
DISPOSAL OF ASHES
O120.1 Disposal of ashes. Ashes and coals shall not be placed, deposited, or dumped in or upon hazardous fire areas. Exceptions:
1. In the hearth of an established fire pit, camp stove or fireplace.
2. In a noncombustible container with a tight-fitting lid, which is kept or maintained in a safe location not less than 10 feet (3048 mm) from combustible vegetation or structures.
3. Where such ashes or coals are buried and covered with 1 foot (304.8 mm) of mineral earth not less than 25 feet (7620 mm) from combustible vegetation or structures.
SECTION O121
USE OF FIRE ROADS AND FIREBREAKS
O121.1 Use of fire roads and firebreaks. Motorcycles, motor scooters and motor vehicles shall not be driven or parked upon, and trespassing is prohibited upon, fire roads or firebreaks beyond the point where travel is resisted buy a cable, gate or sign, without the permission of the property owners. Vehicles shall not be parked in a manner which obstructs the entrance to a fire road or firebreak.
Exception: Public officers acting within their scope of duty.
Radio and television aerials, guy wires thereto, and other obstructions shall not be installed or maintained on fire roads or firebreaks unless located 16 feet (5877 mm) or more above such fire road or firebreak.
SECTION O122
USE OF MOTORCYCLES, MOTOR SCOOTERS AND MOTOR VEHICLES
O122.1 Use of motor vehicles. Motorcycles, motor scooters and motor vehicles shall not be operated within hazardous fire areas, without a permit by fire code official, except upon clearly established public or private roads. Permission from the property owner shall be presented when requesting a permit.
SECTION O123
TAMPERING WITH FIRE DEPARTMENT LOCKS, BARRICADES AND SIGNS
O123.1 Tampering with fire department locks, barricades, and signs. Locks, barricades, seals, cables, signs and markers installed within hazardous fire areas, by or under the control of fire code official, shall not be tampered with, mutilated, destroyed or removed.
Gates, doors, barriers and locks installed by or under the control of fire code official shall not be unlocked.
SECTION O124
LIABILITY FOR DAMAGE
O124.1 Liability for damage. The expenses of fighting fires which result from a violation of Appendix O shall be a charge against the person whose violation of Appendix O caused the fire. Damages caused by such fires shall constitute a debt of such person and are collectable by fire code official in the same manner as in the case of an obligation under a contract, expressed or implied.
APPENDIX P
EXCAVATION AND CONFINEMENT
SECTION P101
GENERAL
P101.1 Scope. The provisions of this appendix shall apply to any man-made cut, cavity, trench or depression in an earth surface formed by earth removal, and the provisions identify procedures to protect employees from the hazards of entry into confined spaces.
SECTION P102
DEFINITIONS
P102.1 Definitions. The following words and terms shall, for the purpose of this appendix and as used elsewhere in this code, have the meanings shown herein.
CONFINED SPACE. Is a space that:
1. Is large enough and so configured that an employee can bodily enter and perform assigned work; and
2. Has limited or restricted means for entry or exit;
3. Is not designed for continuous employee occupancy.
EXCAVATION. Any man-made cut, cavity, trench or depression in an earth surface, formed by earth removal.
TRENCH. A narrow excavation made below the surface of the ground. In general, the depth is greater than the width, but the width of a trench (measured at the bottom) is not greater than 15 feet. If forms or other structures are installed or constructed in an excavation so as to reduce the dimension measured from the form or structures to the side of the excavation to 15 feet or less, the excavation is a trench.
SECTION P103
EXCAVATION AND TRENCHES
P103.1 Excavation and trenches. Excavation and trenches shall be in accordance with the 29 CFR, Part 1926, Subpart P, Sections 1926.650-652.
SECTION P104
CONFINED SPACES
P104.1 Confined spaces. Confined spaces shall be in accordance with 29 CFR, Part 1910.146. Other recognized standards that must be adhered to include 40 CFR, Part 280 - Technical Standards and Corrective Action Requirements for Owners and Operators of Underground Storage Tanks (UST) and Part 281 - Approval of State Underground Storage Tank Programs
SECTION P105
UNSAFE CONDITIONS
P105.1 Unsafe conditions. When in the opinion of the fire code official or his/her designee, an unsafe condition exists, excavation and confined space operations shall cease until such time as adequate means have been taken to provide for the safety of persons working in or around the excavation or confined space. Failure to do so may result in citations and fines.
(Ord. No. 4283, § 2(Res. No. 10598, § 1(Exh. A)), 11-28-16, eff. 1-1-17; Ord. No. 4562, § 2(Res. No. 12583, § 1(Exh. A)), 9-20-22, eff. 1-1-23)
Scottsdale Revised Code § 36-19 Classification of penalty.
Sec. 36-19. - Classification of penalty.
(a) Any person, firm corporation, partnership, enterprise or association whether as principal, owner, agent, tenant, or otherwise who violates, disobeys, omits or refuses to comply with, or who resists the enforcement of any of the provisions of this chapter is subject to a civil sanction.
(b) Notwithstanding subsection (a) of this section, a second or subsequent violation of any of the provisions of this chapter within a two-year period shall be deemed a misdemeanor.
(Code 1972, § 9-208; Ord. No. 1709, § I, 6-4-85; Ord. No. 1925, § 1, 8-31-87; Ord. No. 2786, §§ 1, 2, 12-18-95; Ord. No. 4045, § 6, 12-4-12; Ord. No. 4562, § 5, 9-20-22, eff. 1-1-23)
Scottsdale Revised Code § 36-19.1 Penalties.
Sec. 36-19.1. - Penalties.
(a) Upon a finding of responsible to civil violation, the court shall impose a fine not to exceed two thousand five hundred dollars ($2,500.00).
(b) Upon a conviction of a misdemeanor, the defendant shall be sentenced pursuant to the provisions of section 1-8 of this Code.
(c) The application of the penalties provided for in paragraphs (a) and (b) of this section shall not be held to prevent the enforced removal of prohibited conditions.
(Ord. No. 1925, § 1, 8-31-87; Ord. No. 2786, §§ 1, 2, 12-18-95; Ord. No. 4045, § 6, 12-4-12; Ord. No. 4283, § 3, 11-28-16, eff. 1-1-17; Ord. No. 4562, § 5, 9-20-22, eff. 1-1-23)
Scottsdale Revised Code § 36-19.2 Misdemeanor violations.
Sec. 36-19.2. - Misdemeanor violations.
A violation of this chapter may only be deemed a class one misdemeanor if the violation is a second or subsequent violation of this chapter within two (2) years of the first violation.
(Ord. No. 1925, § 1, 8-31-87; Ord. No. 2786, §§ 1, 2, 12-18-95; Ord. No. 3507, § 6, 6-17-03; Ord. No. 4283, § 3, 11-28-16, eff. 1-1-17; Ord. No. 4562, § 5, 9-20-22, eff. 1-1-23)
Scottsdale Revised Code § 36-19.3 Authority to issue citation.
Sec. 36-19.3. - Authority to issue citation.
Any City of Scottsdale peace officer, the City Attorney, the Fire Chief or Fire Marshal, or duly authorized agent of the Fire Chief or Fire Marshal may issue a civil citation pursuant to this chapter.
(Ord. No. 1925, § 1, 8-31-87; Ord. No. 2786, §§ 1, 2, 12-18-95; Ord. No. 4283, § 3, 11-28-16, eff. 1-1-17)
Scottsdale Revised Code § 36-19.4 Authority to issue criminal complaints.
Sec. 36-19.4. - Authority to issue criminal complaints.
Any City of Scottsdale peace officer or the City Attorney may issue criminal complaints to enforce this chapter.
(Ord. No. 4283, § 3, 11-28-16, eff. 1-1-17)
Scottsdale Revised Code § 36-19.5 Reserved.
Scottsdale Revised Code § 36-19.6 Rules of procedure.
Sec. 36-19.6. - Rules of procedure.
The Arizona Rules of Court for Civil Traffic Violation Cases shall be followed by the city court for civil violations of this chapter, except as modified or where inconsistent with the provisions of this article, local rules of the city court or rules of the Arizona Supreme Court.
(Ord. No. 1925, § 1, 8-31-87; Ord. No. 2786, §§ 1, 2, 12-18-95; Ord. No. 4283, § 3, 11-28-16, eff. 1-1-17)
Scottsdale Revised Code § 36-19.7 Collection of fines.
Sec. 36-19.7. - Collection of fines.
Any judgement for civil sanctions taken pursuant to this article may be collected as any other civil judgment.
(Ord. No. 1925, § 1, 8-31-87; Ord. No. 2786, §§ 1, 2, 12-18-95)
Scottsdale Revised Code § 36-19.8 Violations not exclusive.
Sec. 36-19.8. - Violations not exclusive.
Violations of this chapter are in addition to any other violation enumerated within the Scottsdale ordinances and Code and in no way limit the penalties, actions or abatement procedures which may be taken by the city for any violation of this chapter which is also a violation of any other ordinance or Code provision of the city, or statutes of the state.
(Ord. No. 1925, § 1, 8-31-87; Ord. No. 2786, §§ 1, 2, 12-18-95)
Scottsdale Revised Code § 36-19.9 Each day separate violation.
Sec. 36-19.9. - Each day separate violation.
Each day any violation of any provision of this chapter or the failure to perform any act or duty required by this chapter continues shall constitute a separate offense.
(Ord. No. 1925, § 1, 8-31-87; Ord. No. 2786, §§ 1, 2, 12-18-95)
Scottsdale Revised Code § 36-20 Bureau of fire prevention.
Sec. 36-20. - Bureau of fire prevention.
(a) The International Fire Code shall be enforced by the bureau of fire prevention of the fire department which is hereby established and which shall be operated under the supervision of the chief of the fire department.
(b) A report of the Bureau of Fire Prevention shall be made annually and transmitted to the city manager. The report shall contain all proceedings under this chapter, with such statistics as the chief of the fire department may wish to include therein. The chief of the fire department shall also recommend any amendments to this article which, in his judgement, are desirable.
(Code 1972, § 9-202; Ord. No. 1709, § I, 6-4-85; Ord. No. 1925, § 1, 8-31-87; Ord. No. 2786, §§ 1, 2, 12-18-95; Ord. No. 3507, § 6, 6-17-03)
Scottsdale Revised Code § 36-21 Entry of building or structure declared unsafe or uninhabitable prohibited.
Sec. 36-21. - Entry of building or structure declared unsafe or uninhabitable prohibited.
(A) It shall be unlawful for any person, without prior authorization from the city, to enter a building or structure that has been declared unsafe or uninhabitable by the fire chief or designee, fire marshal or a city building official.
(B) A violation of this section is a class one misdemeanor.
(Ord. No. 4157, § 1, 6-3-14)
Source: City of Scottsdale, Arizona, Revised Code and City Charter (Municode Library, library.municode.com)URL: https://library.municode.com/az/scottsdale/codes/code_of_ordinances?nodeId=VOLII_CH36FIPRPR_ARTIIFICO_DIV1GEFetched: 11/8/2026
