§ 15-13-25 - OVERFLOW.
(A) A facility that treats or stores water from an OWRS must be designed and operated in a manner that complies with this section.
(B) A permittee may not allow graywater, condensate water, rainwater, stormwater, or foundation drain water to overflow except as set forth in this section.
(C) A permittee may not allow overflow into the sanitary sewer or storm sewer systems except as specifically described in this section.
(D) A permittee shall install an approved backwater valve to direct graywater, condensate water, rainwater, stormwater, or foundation drain water into the applicable discharge location.
(E) Graywater may overflow into the sanitary sewer or another approved discharge location.
(F) Condensate water may overflow into the sanitary sewer or another approved discharge location.
(G) Rainwater, stormwater, and foundation drain water may overflow to a storm sewer.
Source: Ord. No. 20201210-006, Pt. 2, 12-21-20.