§ 617 — Impounding around tanks by diking
Tulsa Revised Ordinances (Supp. No. 3, Update 2: codified through Ordinance No. 25794, passed May 13, 2026) · Tulsa Revised Ordinances tit. 42-A, § 617
Corpus is an independent public-information project, not the official City of Tulsa website. Stable reference: corpuslaw.us/code/c968db9d-cbca-4023-896f-270f38d5a016
Section 617. - Impounding around tanks by diking.
When protection of adjoining property or waterways is by means of impounding by diking around the tanks, such system shall comply with the following: A. A slope of not less than one (1) percent away from the tank shall be provided for at least fifty (50) feet (fifteen (15) m) or to the dike base, whichever is less. B. The volumetric capacity of the diked area shall not be less than the greatest amount of liquid that can be released from the largest tank within the diked area, assuming a full tank. To allow for volume occupied by tanks, the capacity of the diked area enclosing more than one (1) tank shall be calculated after deducting the volume of the tanks, other than the largest tank, below the height of the dike. C. To permit access, the outside base of the dike at ground level shall be no closer than ten (10) feet (three (3) m) to any property line that is or can be built upon. D. Walls of the diked area shall be of earth, steel, concrete, or solid masonry designed to be liquid tight and to withstand a full hydrostatic head. Earthen walls three (3) feet (0.90 m) or more in height shall have a flat section at the top not less than two (2) feet (0.60 m) wide. The slope of an earthen wall shall be consistent with the angle of repose of the material of which the wall is constructed. Diked areas for tanks containing Class I liquids located in extremely porous soils may require special treatment to prevent seepage of hazardous quantities of liquids to low-lying areas or waterways in case of spills. E. Every tank battery associated with a well or group of wells shall be separated from any other tank battery associated with any other well or wells by a dike of a height as required in Subsection 617.B. of this title. A dike shall also be constructed to separate the crude storage tanks and water storage tanks from separators, heater treaters, and other vessels. The height of this dike shall meet the requirements of Subsection 617.B. of this title. The provisions of this subsection shall apply only to tanks or equipment installed, placed, or replaced on or after the effective date of this ordinance. F. There shall be a separation distance of at least twenty-five (25) feet between crude and water storage tanks and heater treaters or other equipment designed to be heated with burners or electric elements. The provisions of this subsection shall apply only to tanks or equipment installed, placed, or replaced on or after the effective date of this ordinance. G. Where provision is made for draining water from diked areas, such drains shall be controlled in a manner so as to prevent flammable or combustible liquids from entering natural watercourses, public sewers, or public drains, if their presence would constitute a hazard. Control of drainage shall be accessible under fire conditions from outside the dike. H. Storage of combustible materials shall not be permitted within the diked area.
(Ord. No. 22189, § 1, 1-14-2010)
Ask a question about Tulsa law
Corpus searches the Tulsa sections it holds and shows the ones that match, with their citations. Free, no sign-in.