Section 5.6.2. - Outdoor lighting standards.
A. Outdoor lighting fixtures. All outdoor lighting fixtures shall be installed in such a manner that the source of each individual light is shielded, positioned, and maintained so as not to be visible off the premises.
B. Light shielding for parking lot illumination. All parking lot lighting shall have no light emitted above 90 degrees.
C. Outdoor lighting fixtures adjacent to residential. Any outdoor lighting fixture providing light to any parcel adjacent to a residentially zoned parcel, whether adjoining or not, shall emit no more than 0.1 foot-candles of light, as measured from the property line of the adjacent residential parcel, using a standard light meter, the cell of which is directed towards the source of the light.
D. All areas designed for use after daylight hours shall be adequately lit, in accordance with Table 5.6.2. below.
Table 5.6.2. Lighting levels for commercial and industrial developments
Outdoor Lighting Area | Lighting Level minimum - maximum (foot-candles)
Entrance of commercial or industrial building | 1—5
Sidewalk or walkway from parking area to entrance | .5—2
Parking lot | .5—3
Gas station canopy | 10—15
Loading and unloading areas | 15—20
E. Illumination ratio. Luminaire fixtures in parking lots shall be arranged in order to provide uniform illumination throughout the parking lot area of not more than a 4:1 ratio of average to minimum illumination, and not more than 12:1 ratio of maximum to minimum illumination.
F. Automatic Switching Requirements. Controls shall be provided that automatically extinguish all outdoor lighting when sufficient daylight is available using a control device or system such as a photoelectric switch, astronomic time switch, or equivalent functions from a programmable lighting controller, building automation system, or lighting energy management system, all with battery or similar backup power or device.
G. Modifications. Additions, modifications, or replacement of more than 25 percent of outdoor lighting fixtures existing as of the effective date of this ordinance shall require the submission of a complete inventory and photometric plan detailing all existing and any proposed new outdoor lighting. Any new lighting shall meet the requirements of this ordinance.
H. Exempt lighting. The provisions above shall not apply to streetlights, single-family residences, duplexes, or governmental facilities.