§ 301 — Amendments to the ICC International Fuel Gas Code, 2018 Edition
Tulsa Revised Ordinances (Supp. No. 3, Update 2: codified through Ordinance No. 25794, passed May 13, 2026) · Tulsa Revised Ordinances tit. 59, § 301
Corpus is an independent public-information project, not the official City of Tulsa website. Stable reference: corpuslaw.us/code/cbb58939-fc19-4127-ad7f-829346c4be7d
Section 301. - Amendments to the ICC International Fuel Gas Code, 2018 Edition.
The following provisions of the ICC International Fuel Gas Code, 2018 Edition, are hereby added, deleted, or amended to read as follows: Chapter 1 - Administration 106.1 When Required-Amendatory. A contractor who desires to erect, install, enlarge, alter, repair, remove, convert, or replace a fuel gas piping system or fuel gas appliance, the installation of which is regulated by this code, or to cause such work to be done, shall first make application and obtain the required permit for the work contemplated. Exception: Where equipment replacements and repairs must be performed in an emergency situation, the permit application shall be submitted within the next working business day. 106.1.1 Annual Permit—Amendatory. An annual permit is a yearly permit which represents a group of individual permits for each alteration to an already existing electrical, gas, mechanical or plumbing installation. The building official is authorized to issue an annual permit upon application therefor to any person, firm or corporation regularly employing one or more qualified tradespersons in the building, structure or on the premises owned or operated by the applicant for the permit. 106.1.2 Annual permit records—Amendatory. The person to whom an annual permit is issued shall keep a detailed record of alterations made under such annual permit. The building official shall have access to such detailed records of alterations at all times. At the completion of the entity's annual permit term, the applicant shall file such detailed records of alterations with the building official. Pursuant to the authority of 59 O.S. § 1000.25, the building official shall collect fees for each individual permit which is part of the annual permit once the detailed records are submitted and remit such fees to the OUBCC. 106.1.3 Tulsa Revised Ordinances, Title 50—Added. Annual permits shall comply with Tulsa Revised Ordinances, Title 50. 106.3 Application for permit—Amendatory. No permit shall be issued to any person, firm, limited liability company, or corporation until such person, firm, limited liability company, or corporation has received a Certificate of Registration appropriate for the work contemplated. 106.6.1 Work Commencing Before Permit Issuance—Amendatory. Any person who commences work on a mechanical system before obtaining the necessary permits shall be subject to penalty fees established in Title 49, Tulsa Revised Ordinances. 106.6.2 Fee Schedule—Amendatory. Permit and inspection fees for all work shall be the same as set forth in Chapters 1 and 5 of Title 49, Tulsa Revised Ordinances. 108.4 Violation Penalties—Amendatory. Any person violating any of the provisions of this code shall be guilty of a misdemeanor offense and, upon conviction thereof, shall be punished by a fine of not more than One Thousand Two Hundred Dollars ($1,200.00), excluding cost, fees, and assessments or by imprisonment in the City Jail for a period not exceeding six (6) months or by both such fine and imprisonment. Each day that a violation continues shall be deemed a separate offense. 108.7.2 Authority to disconnect service utilities—Amendatory. The code official shall have the authority to require disconnection of utility service to eliminate an immediate hazard to life or property or to abate a violation of any provision of this code. The code official shall notify the serving utility and, where possible, the owner or the owner's authorized agent and occupant of the building, structure or service system of the decision to disconnect prior to taking such action. If not notified prior to disconnection, the owner or occupant of the building, structure or service system shall be notified in writing, as soon as practicable thereafter. Section 109. Means of Appeal—Amendatory. Appeals of orders, decisions or determinations made by the code official relative to the application and interpretation of this code, shall be made to the Board of Appeals as established by Title 51, Chapter 1, Tulsa Revised Ordinances. 306.5 Equipment and appliances on roofs or elevated structures. Where equipment requiring access or appliances are located on an elevated structure or the roof of a building such that personnel will have to climb higher than 16 feet (4877 mm) above grade to access such equipment or appliances, an interior or exterior means of access shall be provided. Such access shall not require climbing over obstructions greater than 30 inches (762 mm) in height or walking on roofs having a slope greater than 4 units vertical in 12 units horizontal (33-percent slope). Such access shall not require the use of portable ladders. Where access involves climbing over parapet walls, the height shall be measured to the top of the parapet wall. (A) Permanent ladders installed to provide the required access shall comply with the following minimum design criteria: (i) The side railing shall extend above the parapet or roof edge not less than 30 inches (762 mm), (ii) Ladders shall have rung spacing not to exceed 14 inches (356 mm) on center. The upper-most rung shall be not more than 24 inches (610 mm) below the upper edge of the roof hatch, roof or parapet, as applicable, (iii) Ladders shall have a toe spacing not less than 6 inches (152 mm) deep, (iv) There shall be not less than 18 inches (457 mm) between rails, (v) Rungs shall have a diameter not less than 0.75-inch (19 mm) and be capable of withstanding a 300-pound (136.1 kg) load, (vi) Ladders over 30 feet (9144 mm) in height shall be provided with offset sections and landings capable of withstanding 100 pounds per square foot (488.2 kg divided by meters squared). Landing dimensions shall be not less than 18 inches (457 mm) and not less than the width of the ladder served. A guard rail shall be provided on all open sides of the landing, (vii) Climbing clearance. The distance from the centerline of rungs to the nearest permanent object on the climbing side of the ladder shall be not less than 30 inches (762 mm) measured perpendicular to the rungs. This distance shall be maintained from the point of ladder access to the bottom of the roof hatch. A minimum clear width of 15 inches (381 mm) shall be provided on both sides of the ladder measured from the midpoint of and parallel with the rungs, except where cages or wells are installed, (viii) Landing required. The ladder shall be provided with a clear and unobstructed bottom landing area having a minimum dimension of 30 inches (762 mm) by 30 inches (762 mm) centered in front of the ladder, (ix) Ladders shall be protected against corrosion by approved means. (x) Access to ladders shall be provided at all times. (B) Catwalks installed to provide the required access shall be not less than 24 inches (610 mm) wide and shall have railings as required for service platforms. Exceptions: (i) This section shall not apply to Group R-3 occupancies, (ii) This section shall not apply to appliance replacement. 306.6 Guards—Amendatory. Guards shall be provided where various components that require service are located on a roof or elevated structure and have a condition as set forth in Sections 306.1 through 306.6.3. The top of the guard shall be located not less than 42 inches (1067 mm) above the elevated surface adjacent to the guard. The guard shall be constructed so as to prevent the passage of a 21-inch diameter (533 mm) sphere and shall comply with the loading requirements for guards as specified in the International Building Code. Guards shall be provided at new components when added or replaced on an existing roof or elevated structure and have a condition as set forth in Sections 306.1 through 306.6.3. Exception: When approved by the authority having jurisdiction, guards are not required where permanent fall arrest/restraint anchorage connector devices that comply with ANSI/ASSE Z 359.1 are affixed for use during the entire roof covering lifetime. The devices shall be reevaluated for possible replacement when the entire roof covering is replaced. The devices shall be placed no more than 10 feet (3048 mm) on center along hip and ridge lines and placed not less than 10 feet (3048 mm) from roof edges and the open sides of walking surfaces. 306.6.1 Roof edge—Added. Guards complying with Section 306.1 shall be provided when components are located within 10 feet (3048 mm) of a roof edge or open side of a walking surface or elevated structure and such edge or open side is located more than 30 inches (762 mm) above the floor, roof, or grade below. The guard shall extend not less than 30 inches (762 mm) beyond each end of the component that requires service. 306.6.2 Skylights—Added. Guards complying with Section 306.6 shall be provided when a skylight is within 10 feet (3048 mm) of the component that requires service. The guard shall extend 30 inches (762 mm) beyond the edge of the skylight. Exceptions: (A) Guards are not required when the skylight is located at least 42 inches (1067 mm) above the highest point of the walking surface adjacent to the skylight or components. (B) Guards are not required if some other provision for skylight fall-through protection is provided and approved by the authority having jurisdiction. 306.6.3 Roof hatch—Added. Guards complying with Section 306.6 shall be provided when a roof hatch is within 10 feet (3048 mm) of the component that requires service. The guard shall extend 30 inches (762 mm) beyond the edge of the roof hatch. If the component is within 10 feet (3048 mm) of the ladder access side of the roof hatch, the guard shall incorporate a self-closing, self-latching gate. The gate shall have a top edge of not less than 42 inches (1067 mm) above the elevated surface adjacent to the gate and shall not allow the passage of a 21 inch (533 mm) sphere. If a roof hatch exists within 10 feet of a roof edge that is located more than 30 inches (762 mm) above the floor, roof or grade below and a new component that requires services on that existing roof or elevated structure, then a guard complying with Section 306.6 shall be added between the existing roof hatch and the roof edge. 307.2.1 Condensate drains—Added. Where condensing appliances are in locations subject to freezing conditions, the condensate drain line shall be protected from freezing in an approved manner and in accordance with manufacturer's installation instructions. 310.1.1 CSST—Amendatory. Corrugated stainless steel (CSST) gas piping systems and piping systems containing one or more segments of CSST shall be bonded to the electrical service grounding electrode system or, where provided, the lightning protection grounding electrode system. Exception: Corrugated stainless steel gas piping or tubing products or systems that have been designed, manufactured and listed for installation without bonding to the grounding electrode system, shall be permitted to be installed in accordance with the manufacturer's installation instructions. 307.2.3 Work on Consumer's Gas Piping Containing Unmeasured Gas—Added. Repair, alterations, relocations, or any other work conducted on any portion of a consumer's gas piping, containing unmeasured gas, shall only be performed by a qualified person or installation agency authorized to do such work. When such work is done, the gas utility company shall be notified. The movement, connection, or disconnection of gas meters shall only be performed by gas utility company employees or others authorized by the gas utility company. For unmeasured gas pressure above three (3) psig, the line shall be tested at ninety (90) psig. 402.1. General Considerations—Amendatory. Piping systems shall be of such size and so installed as to provide a supply of gas sufficient to meet the maximum demand and supply gas to each appliance inlet at not less than the minimum supply pressure required by the appliance, but not less than 1" to the first connected appliance or regulator. 404.7.4 Protection against physical damage—Added. Gas piping other than steel piping installed less than 1½ inches from roof decking shall be protected against physical damage by an approved method. 404.10.2 Separation of gas piping from other piping systems—Added. There shall be a minimum 12 inches of undisturbed or compacted earth separation between buried gas piping and any other electrical service lines, water piping or sewer piping systems. 404.12. Minimum burial depth—Amendatory. Underground piping systems shall be installed a minimum depth of 18 inches (457 mm) below grade, except as provided for in Section 404.10.1. Exception: Where a minimum depth of 18 inches (457 mm) of cover cannot be provided, the pipe shall be installed in conduit or bridged (shielded). 406.4.1 Test pressure—Amendatory. The test pressure to be used shall be no less than 1½ times the proposed maximum working pressure, but not less than 3 psi on a five (5) psi gauge registered in one-tenth pound increments or ten (10) psi on a fifteen (15) psi gauge registered in one pound increments or ten (10) psi on a thirty (30) psi gauge registered in one (1) pound increments. Where the test pressure exceeds 125 psig (862 kPa gauge), the test pressure shall not exceed a value that produces a hoop stress in the piping greater than 50 percent of the specified minimum yield strength of the pipe. 406.6.2.1 General—Added. At least one appliance shall be connected prior to final release of the gas meter. 411.2.1 Location, Protection and Sizing of Riser—Added. The gas riser to each manufactured home site shall be placed in the rear one-third (a) section of the site, within eighteen (18) inches of the roadside wall of the manufactured home (i.e., the right side of the manufactured home when viewing the tongue of the manufactured home). It shall be located and protected or supported so as to minimize the likelihood of damage by moving vehicles. The minimum size of the gas piping outlet at such a site shall be three-fourths (¾) inch for other than undiluted, liquefied petroleum gases. 411.2.2 Location of Shut-off Valves—Added. A. Outlets for the individual manufactured homes and gas piping to any building supplied by the system shall be provided with a readily accessible, approved valve which cannot be locked in the open position. B. A readily accessible valve shall be provided near the point of gas delivery for shutting off the entire manufactured home park system. The valve provided by the serving gas supplier may be considered acceptable for this purpose, provided it is readily accessible. 412.5 Attendants. Motor fuel-dispensing operations shall be conducted by qualified attendants or in accordance with Section 412.9 by persons trained in the proper handling of LP-gas. Exception: When the dispensing equipment meets the guidelines of NFPA® 58 for "Low emission transfer" an attendant is not required. 412.6.1 Low emission transfer. When the dispensing equipment is installed in accordance with Section 6.30.5 of NFPA® 58 for "Low emission transfer," the transfer distance requirements in Table 6.7.2.1 and Section 6.27.4.3 of NFPA® 58 shall be reduced by one-half. 412.9 Public fueling of motor vehicles. (A) Self-service LP-gas dispensing systems, including key, code and card lock dispensing systems, shall be limited to the filling of permanently mounted containers providing fuel to the LP-gas-powered vehicle. (B) The requirements for self-service LP-gas dispensing systems shall be in accordance with the following: (i) The arrangement and operation of the transfer of product into a vehicle shall be in accordance with this section and Chapter 61 of the International Fire Code®, (ii) The system shall be provided with an emergency shut-off switch located within 100 feet (30 480 mm) of, but not less than 20 feet (6096 mm) from dispensers, (iii) The owner of the LP-gas motor fuel-dispensing facility or the owner's designee shall provide for the safe operation of the system and the training of users. Exception: If the LP-gas motor fuel-dispensing facility meets the requirements of a low emission transfer station per NFPA® 58, then training of the users is not the responsibility of the facility, (iv) The dispenser and hose-end valve shall release not more than 4 cubic centimeters of liquid to the atmosphere upon breaking the connection with the fill valve on the vehicle, (v) Fire extinguishers shall be provided in accordance with Section 2305.5 of the International Fire Code®, (vi) Warning signs shall be provided in accordance with Section 2305.6 of the International Fire Code®, (vii) The area around the dispenser shall be maintained in accordance with Section 2305.7 of the International Fire Code®. 413.3.2 Warning signs. Warning signs complying with Section 310 of the International Fire Code® shall be posted as follows: (A) Warning sign(s) shall be conspicuously posted within sight of each dispenser in the fuel dispensing area and shall state the following: (i) No smoking, (ii) Shut off motor, (iii) Flammable Gas, (iv) Natural gas vehicle fuel cylinders shall be inspected at intervals not exceeding 3 years or 36,000 miles to ensure safe operation of the vehicle, (v) Natural gas fuel cylinders past their end-of-life date shall not be refueled and shall be removed from service. (B) A warning sign with the words "NO SMOKING, FLAMMABLE GAS" shall be posted in all compressor and storage areas. (C) The lettering on the sign shall be legible and large enough to be visible from each point of transfer. (D) The service pressure of each dispenser shall be posted in view of the operator. 413.5 Private fueling of motor vehicles. (A) Self-service CNG-dispensing systems, including key, code and card lock dispensing systems, shall be limited to the filling of approved, permanently mounted fuel containers. (B) In addition to the requirements in the International Fire Code, the owner of a self-service CNG-dispensing facility shall ensure the safe operation of the system. 413.8 Emergency shutdown devices. A remote and local emergency manual shutdown device shall be provided. Upon activation, the emergency shutdown system shall automatically close valves between the main gas supply and the compressor and between the storage containers and dispensers, and automatically shut off the power supply to the compressor and the following associated devices: dispensing enclosures; remote pumps; power, control, and signal circuits; and electrical equipment in the hazardous (classified) locations surrounding the fuel dispensing enclosures. All labeled emergency shutdown devices shall be interconnected, whether required or not. Resetting from an emergency shutoff condition shall require manual intervention and the manner of resetting shall be approved by the Authority Having Jurisdiction. Exception: In time-fill applications, in lieu of a defined remote and local emergency manual shutdown device, an emergency manual shutdown device shall be provided within 50 feet (15 240 mm) of each fixed point of dispensing hose attachment and located inside and outside the compressor area within 10 feet (3048 mm) of the main access to the compressor area. 413.8.1 Remote emergency shutdown device. A remote emergency manual shutdown device shall be located within 100 feet (30 480 mm) of, but not less than 20 feet (6096 mm) from all dispensing enclosures and shall be provided inside and outside the compressor area within 10 feet (3048 mm) of the main access to the compressor area. Exception: A remote emergency manual shutdown device may be located greater than 100 feet (30 480 mm) from one or more dispensing enclosures when within line of sight of the dispensing enclosures and approved by the Authority Having Jurisdiction. Section 413.8.2 Local emergency shutdown device. This section has been added to require a local emergency shutdown device be provided within 15 feet (4572 mm) of each dispensing enclosure. This section has been added to read: 413.8.2 Local emergency shutdown device. A local emergency manual shutdown device shall be located within 15 feet (4572 mm) of each dispensing enclosure. Chapter 8 Referenced Standards—Amendatory. Chapter 8 of the IFGC 2018 is adopted with the following modifications: IBC® 18 International Building Code® as adopted and modified by the State of Oklahoma through the OUBCC. IECC®-06 International Energy Conservation Code®. IFC® 18 International Fire Code® as adopted and modified by the State of Oklahoma through the OUBCC. IMC® 18 International Mechanical Code® as adopted and modified by the State of Oklahoma through the OUBCC. IPC® 18 International Plumbing Code® as adopted and modified by the State of Oklahoma through the OUBCC. IRC® 15 International Residential Code® as adopted and modified by the State of Oklahoma through the OUBCC. NFPA 70-14 National Electrical Code® as adopted and modified by the State of Oklahoma through the OUBCC.
(Ord. No. 23436, § 1, 2-11-2016; Ord. No. 24894, § 1, 8-24-2022)
Ask a question about Tulsa law
Corpus searches the Tulsa sections it holds and shows the ones that match, with their citations. Free, no sign-in.