Sec. 58-37. - Amendments to International Fire Code.
(a) For purposes of the City of Jackson's adoption of the 2024 Edition of the International Fire Code, the term "fire code official" shall be the City Fire Marshal.
(b) the following sections of the 2024 Edition of the International Fire Code are amended as follows:
101.1: Title. These regulations shall be known as the Fire Code of the City of Jackson, Mississippi, hereinafter referred to as "this code."
103.1: Creation of agency. The Office of the City Fire Marshal is hereby created and the official in charge thereof shall be known as the fire code official. The function of the agency shall be the implementation, administration and enforcement of the provisions of this code.
103.2: Appointment. The fire code official shall be appointed by the Chief of the Fire Department.
103.3: Deputies. In accordance with the prescribed procedures of this jurisdiction Chief of the Fire Department shall have the authority to appoint a deputy fire code official, other related technical officers, inspectors and other employees. Such employees shall have powers as delegated by the fire code official.
113.4: Violation penalties. Persons who shall violate a provision of this code or shall fail to comply with any of the requirements thereof or who shall erect, install, alter, repair or do work in violation of the approved construction documents or directive of the fire code official, or of a permit or certificate used under provisions of this code, shall be guilty of a misdemeanor, punishable by a fine of not more than One Thousand Dollars ($1,000.00) dollars or by imprisonment not exceeding ninety (90) days, or both such fine and imprisonment. Each day that a violation continues after due notice has been served shall be deemed a separate offense.
903.2: Where required. Approved automatic sprinkler systems in new buildings and structures shall be provided in the locations described in Sections 903.2.1 through 903.2.12.
903.2.1.1: Group A-1. An automatic sprinkler system shall be provided throughout stories containing Group A-1 occupancies and throughout all stories from the Group A-1 occupancy to and including the levels of exit discharge serving that occupancy where one of the following conditions exists:
1. The fire area exceeds 5,000 square feet (464 m 2 ).
2. The fire area has an occupant load of 300 or more.
3. The fire area is located on a floor other than a level of exit discharge serving such occupancies.
4. The fire area contains a multiple-theater complex.
903.2.1.3: Group A-3. An automatic sprinkler system shall be provided throughout stories containing Group A-3 occupancies and throughout all stories from the Group A-3 occupancy to and including the levels of exit discharge serving that occupancy where one of the following conditions exists:
1. The fire area exceeds 5,000 square feet (464 m 2 ).
2. The fire area has an occupant load of 300 or more.
3. The fire area is located on a floor other than a level of exit discharge serving such occupancies.
903.2.1.4: Group A-4. An automatic sprinkler system shall be provided throughout stories containing Group A-4 occupancies and throughout all stories from the Group A-4 occupancy to and including the levels of exit discharge serving that occupancy where one of the following conditions exists:
1. The fire area exceeds 5,000 square feet (464 m 2 ).
2. The fire area has an occupant load of 300 or more.
3. The fire area is located on a floor other than a level of exit discharge serving such occupancies.
903.2.2: Group B. An automatic sprinkler system shall be provided for Group B occupancies for new, renovated, or modified buildings where the fire area exceeds 5,000 square feet (464 m 2 ).
903.2.2.1: Ambulatory care facilities. [deleted]
903.2.2.2: Laboratories involving research and development or testing. [deleted]
903.2.3 Group E. An automatic sprinkler system shall be provided for Group E occupancies as follows:
1. Throughout all Group E fire areas greater than 5,000 square feet (464 m 2 ) in area.
2. The Group E fire area is located on a floor other than a level of exit discharge serving such occupancies.
Exception: In buildings where every classroom has not fewer than one exterior exit door at ground level, an automatic sprinkler system is not required in any area below the lowest level of exit discharge serving that area.
1. The Group E fire area has an occupant load of 300 or more.
903.2.4 Group F-1. An automatic sprinkler system shall be provided throughout all new, renovated, or modified buildings containing a Group F-1 occupancy where one of the following conditions exists:
1. A Group F-1 fire area exceeds 5,000 square feet (464 m 2 ).
2. A Group F-1 fire area is located more than three stories above grade plane.
3. The combined area of all Group F-1 fire areas on all floors, including any mezzanines, exceeds 10,000 square feet (929 m 2 ).
4. A Group F-1 occupancy is used to manufacture lithium-ion or lithium metal batteries.
5. A Group F-1 occupancy is used to manufacture vehicles, energy storage systems or equipment containing lithium-ion or lithium metal batteries where the batteries are installed as part of the manufacturing process.
903.2.7 Group M. An automatic sprinkler system shall be provided throughout new, renovated, or modified buildings containing a Group M occupancy where one of the following conditions exists:
1. A Group M fire area exceeds 5,000 square feet (464 m 2 ).
2. A Group M fire area is located more than three stories above grade plane.
3. The combined area of all Group M fire areas on all floors, including any mezzanines, exceeds 10,000 square feet (929 m 2 ).
903.2.9 Group S-1. An automatic sprinkler system shall be provided throughout all new, renovated, or modified buildings containing a Group S-1 occupancy where one of the following conditions exists:
1. A Group S-1 fire area exceeds 5,000 square feet (464 m 2 ).
2. A Group S-1 fire area is located more than three stories above grade plane.
3. The combined area of all Group S-1 fire areas on all floors, including any mezzanines, exceeds 10,000 square feet (929 m 2 ).
4. A Group S-1 fire area used for the storage of commercial motor vehicles where the fire area exceeds 5,000 square feet (464 m 2 ).
5. A Group S-1 fire area used for the storage of lithium-ion or lithium metal powered vehicles where the fire area exceeds 500 square feet (46.4 m 2 ).
903.2.9.1 Repair garages. An automatic sprinkler system shall be provided throughout all new, renovated, or modified buildings used as repair garages in accordance with Section 406.8 of the International Building Code, as shown:
1. Buildings having two or more stories above grade plane, including basements, with a fire area containing a repair garage exceeding 5,000 square feet (464 m 2 ).
2. Buildings not more than one story above grade plane, with a fire area containing a repair garage exceeding 5,000 square feet (464 m 2 ).
3. Buildings with repair garages servicing vehicles parked in basements.
4. A Group S-1 fire area used for the repair of commercial motor vehicles where the fire area exceeds 5,000 square feet (464 m 2 ).
5. A Group S-1 fire area used for the storage of lithium-ion or lithium metal powered vehicles where the fire area exceeds 500 square feet (46.4 m 2 ).
Section 903.2.9 shall be amended to add a new Section 903.2.9.5, which shall read as follows:
Section 903.2.9.5 Self-Service storage facility. An automatic sprinkler system shall be installed in new, renovated, or modified self-service storage facilities. A screen shall be installed at eighteen (18) inches below the level of the sprinkler heads to restrict storage above that level. This screen shall be a mesh not less than one (1) inch nor greater than six (6) inches in size. The screen and its supports shall be installed such that all elements are at least eighteen (18) inches below any sprinkler heads.
903.2.10 Group S-2 parking garages. An automatic sprinkler system shall be provided throughout new, renovated, or modified buildings classified as parking garages where any of the following conditions exist:
1. Where the fire area of the enclosed parking garage, in accordance with Section 406.6 of the International Building Code, exceeds 12,000 square feet (1115 m 2 ).
2. Where the enclosed parking garage, in accordance with Section 406.6 of the International Building Code, is located beneath other groups.
Exception: Enclosed parking garages located beneath Group R-3 occupancies.
1. Where the fire area of the open parking garage, in accordance with Section 406.5 of the International Building Code, exceeds 48,000 square feet (4460 m 2 ).
Section 903.2.11.7. High combustible storage. For buildings with a clear height exceeding 12 feet (4,572 mm) see Chapter 32 to determine if those provisions apply.
Section 903.2.11.8. Spray booths and rooms. New, renovated, or modified spray booths and spraying rooms shall be protected by an approved automatic fire extinguishing system.
Section 903.3.1.1.1 Exempt locations. If approved by fire code official, automatic sprinklers shall not be required in the following rooms or areas where such rooms or areas are protected with an approved automatic fire detection system in accordance with Section 907.2 that will respond to visible or invisible particles of combustion. Sprinklers shall not be omitted from any room merely because it is damp, of fire-resistance rated construction or contains electrical equipment.
1. Any room where the application of water, or flame and water, constitutes a serious life or fire hazard.
2. Generator and transformer rooms, under the direct control of a public utility, separated from the remainder of the building by walls and floor/ceiling or roof/ceiling assemblies having a fire-resistance rating of not less than 2 hours.
3. Elevator machine rooms, machinery spaces, and hoist ways, other than pits where such sprinklers would not necessitate shunt trip requirements under any circumstances.
903.3.1.4 Automatic sprinkler installation. Automatic sprinkler systems shall be designed, installed, and maintained in accordance with the current edition of the NFPA 13 Standards for the Installation of Sprinkler Systems.
903.3.5 Water supplies. Water supplies for automatic sprinkler systems shall comply with this section and the standards referenced in Section 903.3.1. The potable water supply shall be protected against backflow in accordance with the requirements of this section and the International Plumbing Code. For connections to public waterworks systems, the water supply test used for design of fire protection systems shall be adjusted to account for seasonal and daily pressure fluctuations based on information from the water supply authority and as approved by the fire code official.
Water supply as required for automatic sprinkler systems shall be provided in conformance with the supply requirements of the respective standard.
1103.5.3 Group I-2, Condition 2. In addition to the requirements of Section 1103.5.2, existing buildings of Group I-2, Condition 2 occupancy shall be equipped throughout with an approved automatic sprinkler system in accordance with Section 903.3.1.1. The automatic sprinkler system shall be installed as established by the adopting ordinance. All Group 1-2, Condition 2 occupancies shall be equipped throughout with an approved automatic sprinkler system in accordance with Section 903.3.1.1 by January 1, 2026.
A101.3 Membership of board. The board shall consist of five voting members appointed by the chief appointing authority of the jurisdiction. Each member shall serve for four (4) years or until a successor has been appointed. The board member's terms shall be staggered at intervals, so as to provide continuity. The fire code official shall be an ex officio member of said board but shall not vote on any matter before the board.
(Code 1971, § 12-19.1; Ord. No. 2004-38(2), § 2, 9-7-04; Ord. No. 2015-4(2), § 2, 2-24-15; Ord. No. 2020-16(5), 8-14-20; Ord. No. 2021-23(5), 8-4-20; Ord. No. 2022-55(2), 8-16-22; Ord. No. 2025-29(10), § 2, 5-20-25)