18.48.500 - CFC Chapter 9, Section 903.4—Sprinkler system supervision and alarms.
Section 903.4 of Chapter 9 of the California Fire Code is amended by the addition of Section 903.4.4 to read as follows: 903.4.4 Remote annunciator. A remote annunciator shall be provided at the main entrance, the first suite in a multi suite building, or in a location as approved by the Fire Code Official. The remote annunciator shall be key operated and have the capability to silence and reset the system, or by other approved means. The visual description shall lock in until the system is reset and shall not be cancelled by the operation of an audible alarm-silencing switch.
(ORD-25-0019 § 1(Exh. A), 2025; ORD-22-0033 § 1(Exh. A), 2022)