34.903 - AUTOMATIC SPRINKLER SYSTEMS.
(1) The following requirements are in addition to the requirements found in IFC section 903.3.5: Automatic sprinkler systems shall provide a minimum safety factor of ten percent (10%) or 5 psi, whichever is greater, in the fire protection system hydraulic calculations below the water supply curve. (2) The following language is substituted for IFC section 903.4.2: Approved audible and visual notification devices shall be connected to every automatic sprinkler system. Such notification devices shall be activated by water flow equivalent to the flow of a single sprinkler of the smallest orifice size installed in the system. Alarm devices shall be provided on the exterior of the building located above the fire department connection. Where a fire alarm system is installed, actuation of the automatic sprinkler system shall actuate the building fire alarm system. (3) Records for the inspecting, testing and maintenance of automatic sprinkler systems shall be kept in accordance with Sec. 34.03, MGO.