Sec. 49-342. - Responsibility to provide testing materials and labor.

The license holder supervising the work shall furnish the equipment, material, power or labor necessary for all required inspections and tests. The test gauge dial used for pressure tests shall have the following pressure graduations or increments: (a) Tests requiring ten psig or less: One-tenth psig or less. (b) Tests requiring more than ten but less than 100 psig: Two psig or less. (c) Tests requiring more than 100 psig: Two percent of the required test pressure or less. (d) All gauges used in the hydrostatic testing of fire and domestic water services shall have a range of at least 25 percent greater than the required pressure with no more than increments of two psig. The face of the gauge shall have a minimum diameter of 3½ inches. A locking ball valve shall be installed before the gauge. (e) Test gauges shall have a maximum pressure reading not greater than twice the minimum required test pressure.

(Ord. No. 40524, § 1, 10-20-15)